vault backup: 2025-10-23 10:52:59

This commit is contained in:
2025-10-23 10:52:59 -04:00
parent b107039e14
commit 0158208a10
17 changed files with 0 additions and 0 deletions
-56
View File
@@ -1,56 +0,0 @@
---
id:
aliases: []
tags:
- destiny/permanent
- occupational/systems/electrical
- status/draft
- type/guide
title: Lighting Controls
---
# Lighting Controls
## Information
### Methods
> [!info] Lighting Control Technologies
> * Triac (Line voltage dim)
> * Analog (0-10V dim)
> * Digital
> * Wireless
All these control methods are likely to appear in drawings.
#### 0-10V Dimming
In conduit:
```
Southwire 64350501
SIMpull® 16/2 Low Voltage Signal Cable, Blue
```
This method is compliant with NEC 725.136(I)(1),
which allows control circuits to share a raceway with power conductors
if either all of the power conductors or all of the control conductors
are themselves in a raceway,
or in metal-sheathed, metal-clad, nonmetallic-sheathed, or Type UF cable.
## Conventions
> [!info] "Local Control" as a PDI proposal qualification
> The term "local control only" is sometimes used to indicate
> no consideration for _any_ lighting control beyond standard devices,
> (with `$D`'s being the triac type)
> however, this phrasing is ambiguous and non-universal.
> Confirm with the bid team on what must be included.
## Scope
### Designations
#### Custom Switch Boxes
For switch combinations not in `COMMON ASSEMBLIES`,
create heating designations based on the most similar.