@@ -25,6 +25,11 @@ THE CONTRACTOR IS RESPONSIBLE TO BE FAMILIAR WITH THE 2020 FBC ENERGY CONSERVATI
|
||||
AND SHALL UPSIZE THE CONDUCTORS FOR FEEDER AND BRANCH CIRCUITS
|
||||
BASED ON THE ACTUAL ROUTING IN THE FIELD.
|
||||
|
||||
**C405.10 Voltage drop.**
|
||||
The total voltage drop across the combination of customer-owned service conductors,
|
||||
feeder conductors and branch circuit conductors
|
||||
shall not exceed 5 percent.
|
||||
|
||||
### Floor Boxes
|
||||
|
||||
> [!cite] E.0.X.1 - "ELECTRICAL NOTES" Note 25
|
||||
@@ -34,11 +39,6 @@ BASED ON THE ACTUAL ROUTING IN THE FIELD.
|
||||
> SHALL BE FLUSH FLOOR DUPLEX RECEPTACLES
|
||||
> MOUNTED ADJACENT TO BASE OR WALLS.
|
||||
|
||||
**C405.10 Voltage drop.**
|
||||
The total voltage drop across the combination of customer-owned service conductors,
|
||||
feeder conductors and branch circuit conductors
|
||||
shall not exceed 5 percent.
|
||||
|
||||