diff --git a/nfpa-70_110_requirements-for-electrical-installations.md b/nfpa-70_110_requirements-for-electrical-installations.md index a293c14..7faf674 100644 --- a/nfpa-70_110_requirements-for-electrical-installations.md +++ b/nfpa-70_110_requirements-for-electrical-installations.md @@ -461,13 +461,17 @@ or from the enclosure or opening if the live parts are enclosed. ### Table 110.26(A)(1) Working Spaces -Minimum Clear Distance - -| Nominal Voltage to Ground | Condition 1 | Condition 2 | Condition 3 | -| ------------------------- | ------------- | ------------------ | ------------- | -| 0--150 | 900 mm (3 ft) | 900 mm (3 ft) | 900 mm (3 ft) | -| 151--600 | 900 mm (3 ft) | 1.0 m (3 ft 6 in.) | 1.2 m (4 ft) | -| 601--1000 | 900 mm (3 ft) | 1.2 m (4 ft) | 1.5 m (5 ft) | +| Nominal Voltage to Ground | Condition | Minimum Clear Distance | +| ------------------------- | ----------- | ---------------------- | +| 0--150 | Condition 1 | 900 mm (3 ft) | +| 0--150 | Condition 2 | 900 mm (3 ft) | +| 0--150 | Condition 3 | 900 mm (3 ft) | +| 151--600 | Condition 1 | 900 mm (3 ft) | +| 151--600 | Condition 2 | 1.0 m (3 ft 6 in.) | +| 151--600 | Condition 3 | 1.2 m (4 ft) | +| 601--1000 | Condition 1 | 900 mm (3 ft) | +| 601--1000 | Condition 2 | 1.2 m (4 ft) | +| 601--1000 | Condition 3 | 1.5 m (5 ft) | Note: Where the conditions are as follows: