title: Article 215 Feeders
|
||||
---
|
||||
# Article 215 Feeders
|
||||
|
||||
@@ -29,12 +30,12 @@ Feeder conductors shall have an ampacity
|
||||
not less than the larger of 215.2(A)(1)(a) or (A)(1)(b)
|
||||
and shall comply with 110.14(C).
|
||||
|
||||
- (a) Where a feeder supplies continuous loads
|
||||
* (a) Where a feeder supplies continuous loads
|
||||
or any combination of continuous and noncontinuous loads,
|
||||
the minimum feeder conductor size shall have an ampacity
|
||||
not less than the noncontinuous load plus 125 percent of the continuous load.
|
||||
|
||||
- (b) The minimum feeder conductor size
|
||||
* (b) The minimum feeder conductor size
|
||||
shall have an ampacity not less than the maximum load to be served
|
||||
after the application of any adjustment or correction factors
|
||||
in accordance with
|
||||
|
||||