title: Article 215 Feeders
---
# Article 215 Feeders
@@ -29,12 +30,12 @@ Feeder conductors shall have an ampacity
not less than the larger of 215.2(A)(1)(a) or (A)(1)(b)
and shall comply with 110.14(C).
- (a) Where a feeder supplies continuous loads
* (a) Where a feeder supplies continuous loads
or any combination of continuous and noncontinuous loads,
the minimum feeder conductor size shall have an ampacity
not less than the noncontinuous load plus 125 percent of the continuous load.
- (b) The minimum feeder conductor size
* (b) The minimum feeder conductor size
shall have an ampacity not less than the maximum load to be served
after the application of any adjustment or correction factors
in accordance with