# Article 220 Branch-Circuit, Feeder, and Service Load Calculations
@@ -87,8 +88,8 @@ for each required branch circuit specified in 600.5(A).
Show windows shall be calculated
in accordance with either of the following:
- (1) The unit load per outlet as required in other provisions of this section
- (2) At 200 volt-amperes per linear 300 mm (1 ft) of show window
* (1) The unit load per outlet as required in other provisions of this section
* (2) At 200 volt-amperes per linear 300 mm (1 ft) of show window
#### 220.14(H) Fixed Multioutlet Assemblies.
@@ -99,12 +100,12 @@ For the purposes of this section,
the calculation shall be permitted
to be based on the portion that contains receptacle outlets.
- (1) Where appliances are unlikely to be used simultaneously,
* (1) Where appliances are unlikely to be used simultaneously,
each 1.5 m (5 ft) or fraction thereof
of each separate and continuous length
shall be considered as one outlet of not less than 180 volt-amperes.
- (2) Where appliances are likely to be used simultaneously,
* (2) Where appliances are likely to be used simultaneously,
each 300 mm (1 ft) or fraction thereof
shall be considered as an outlet of not less than 180 volt-amperes.
@@ -132,19 +133,19 @@ and the floor area as determined in 220.11 for dwelling occupancies.
Motors rated less than 18 hp and connected to a lighting circuit
shall be considered part of the minimum lighting load.
- (1) All general-use receptacle outlets of 20-ampere rating or less,
* (1) All general-use receptacle outlets of 20-ampere rating or less,
including receptacles connected to the circuits in 210.11(C)(3) and 210.11(C)(4)
- (2) The receptacle outlets specified in 210.52(E) and (G)
- (3) The lighting outlets specified in 210.70
* (2) The receptacle outlets specified in 210.52(E) and (G)
* (3) The lighting outlets specified in 210.70
#### 220.14(K) Office Buildings.
In office buildings, the receptacle loads
shall be calculated to be the larger of (1) or (2):
- (1) The calculated load from 220.14(I)
* (1) The calculated load from 220.14(I)
after all demand factors have been applied
- (2) 11 volt-amperes/m$^2$ or 1 volt-ampere/ft$^2$
* (2) 11 volt-amperes/m$^2$ or 1 volt-ampere/ft$^2$
#### 220.14(L) Other Outlets.