vault backup: 2026-05-29 10:58:08
This commit is contained in:
@@ -22,7 +22,7 @@ The inevitable retort is
|
||||
"It's an *est*imate, not an *exact*imate,"
|
||||
or some other such reductive dismissal.
|
||||
True enough, this method is _a_ way
|
||||
of getting close to the true answer of project cost and schedule,
|
||||
of _getting close_ to the true answer of project cost and schedule,
|
||||
but it's not an intuitive one.
|
||||
|
||||
For an organizational process to be economical
|
||||
|
||||
@@ -15,21 +15,24 @@ daily: "[[2026-05-28]]"
|
||||
~~not shown on mech, plumbing, otherwise~~
|
||||
~~despite Keynote 4 "SEE MECHANICAL WATER PIPING DIAGRAM FOR EXACT LOCATIONS OF PUMPS."~~
|
||||
~~We could assume that these are intended for the pool equipment~~
|
||||
~~and delete the takeoff.~~
|
||||
~~and delete the takeoff.~~[^1]
|
||||
|
||||
> M3.00, being a diagram, does not show exact locations,
|
||||
> _but does show the pumps being used for domestic water._
|
||||
> (Also the diagram suggests
|
||||
> that the pumps may be spread much far than implied by Electrical,
|
||||
> that our takeoff may be missing a large amount of cable.)
|
||||
> (Also four water heaters are shown
|
||||
> which were not shown on electrical.)
|
||||
[^1]: M3.00, being a diagram, does not show exact locations,
|
||||
_but does show the pumps being used for domestic water._
|
||||
(Also the diagram suggests
|
||||
that the pumps may be spread much far than implied by Electrical,
|
||||
that our takeoff may be missing a large amount of cable.)
|
||||
(Also four water heaters are shown
|
||||
which were not shown on electrical.)
|
||||
|
||||
SP400 shows an electrical panel Keynote 16
|
||||
|
||||
> [!quote] SP400 Keynote 16
|
||||
> NOT SHOWN ON PLANS.
|
||||
> PROVIDE DISCONNECTS IF PANEL IS NOT IN EQUIPMENT ROOM.
|
||||
> IF ELECTRICAL PANEL IS LOCATED IN EQUIPMENT ROOM,
|
||||
> THEN THE PANEL MUST BE NEMA-4X RATED...
|
||||
|
||||
SP400 shows an electrical panel Keynote 16
|
||||
"NOT SHOWN ON PLANS.
|
||||
PROVIDE DISCONNECTS IF PANEL IS NOT IN EQUIPMENT ROOM.
|
||||
IF ELECTRICAL PANEL IS LOCATED IN EQUIPMENT ROOM,
|
||||
THEN THE PANEL MUST BE NEMA-4X RATED..."
|
||||
No panel schedule is provided.
|
||||
|
||||
SP400 Pool Equipment Room is not shown
|
||||
@@ -38,8 +41,10 @@ It is not shown enclosed, even on the Spa set.
|
||||
It seems like the Spa set was done last
|
||||
with no coordination with other disciplines.
|
||||
|
||||
With no other information I'd assume PVC, LFMC, and NEMA 4X disconnects to all equipment shown on SP400
|
||||
from the Garage panels.
|
||||
> With no other information
|
||||
> I'd assume PVC, LFMC, and NEMA 4X disconnects
|
||||
> to all equipment shown on SP400
|
||||
> from the Garage panels.
|
||||
|
||||
Water Feature plans are a similar case.
|
||||
|
||||
@@ -53,5 +58,9 @@ Water Feature plans are a similar case.
|
||||
Neither [[jared-defanti]] nor I am satisfied with this answer.
|
||||
This would mean excluding a significant number of connections.
|
||||
|
||||
> [!quote] [[joel-jansen]] 2026-05-28 13:10 (pp.)
|
||||
>
|
||||
Around 13:10 we spoke to [[joel-jansen]] about the issues.
|
||||
He tended to agree with us
|
||||
that the drawings suggested the EC would be responsible for more,
|
||||
but said he would confirm with [[christian-pereiro]].
|
||||
|
||||
Christian directed us to respect Komis's direction.
|
||||
|
||||
@@ -0,0 +1,7 @@
|
||||
---
|
||||
id: 2026-05-29T10:45:09-0400
|
||||
title: 2026-05-29 10:45:09
|
||||
tags: []
|
||||
daily: "[[2026-05-29]]"
|
||||
---
|
||||
# 2026-05-29 10:45:09
|
||||