vault backup: 2025-10-27 16:34:32

This commit is contained in:
2025-10-27 16:34:32 -04:00
parent ee0948dd00
commit 68bb25782b
39 changed files with 19498 additions and 426 deletions
+19 -5
View File
@@ -2,18 +2,28 @@
id:
aliases: []
tags:
- authorship/original
- destiny/permanent
- occupational/takeoff/fire-alarm
- status/draft
- type/guide
- authorship/original
title: Fire Alarm
title: Fire Alarm Takeoff
---
# Fire Alarm
# Fire Alarm Takeoff
> [!important]
> Complete [[emergency-systems-research]] before beginning takeoff.
> [!info]
> See [[fire-alarm]] for information about fire alarm systems.
## Assembly Selection
Free Air < PVC in Slab < EMT
_High Rise (Steel & slab):_ Free air in Units, use conduit elsewhere.
_Mid Rise, High Density (Wood frame):_ Free air, conduit only where required.
## Backbone
Put all backbone takeoff in the `Area` of the Fire Command Center.
@@ -43,7 +53,7 @@ Input adder length to reach the bottom of the pit (Minimum 15ft).
> [!important] Counting Elevator Shafts
> Adjacent elevators may be in the same or parallel shafts.
> Count the shafts accordingly:
>
>
> ```
> | | |
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
@@ -119,7 +129,7 @@ Count every stairwell at every level.
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...`
_Design Build:_
Count every set of double doors.
Count 2 for every set of double doors.
(Typical of elevator lobbies and corridors)
### Speaker Strobes
@@ -132,6 +142,10 @@ _Design Build:_
* every elevator lobby,
* and every BOH room on the first floor and garage levels.
_Design Build (alt):_
* 15ft from end of corridor,
* then every 50ft
## Firefighter Phone System
* firefighter phone jacks