# 2025-10-15 09:32:00
|
||||
|
||||
%%
|
||||
Content extracted from [[wiring-method-selection]],
|
||||
timestamp based on my teams message to Joel.
|
||||
%%
|
||||
|
||||
## Vanderbilt Central Neighborhood Residential College Spec Interpretation
|
||||
|
||||
[[vanderbilt-central-neighborhood-residential-college]]
|
||||
|
||||
> [!cite] Project Specifications (pp.)
|
||||
> Fittings for Type EMT Duct Raceways:
|
||||
> * Coupling Method: Compression coupling or Setscrew coupling.
|
||||
> Setscrew couplings with only single screw per conduit are unacceptable.
|
||||
|
||||
> [!quote] Joel Jansen via Microsoft Teams @ 2025-10-15 09:33 AM
|
||||
> use set screw 🙂
|
||||
@@ -23,7 +23,7 @@ yearly: "[[2026]]"
|
||||
|
||||
Applies to "Equipment intended to interrupt current".
|
||||
|
||||
[[nfpa-70_110_requirements#110.9 Interrupting Rating.|NEC 110.9 Interrupting Rating.]]
|
||||
[[nfpa-70_110_requirements#^9|NEC 110.9 Interrupting Rating.]]
|
||||
|
||||
Maximum current that the equipment can interrupt without damage.
|
||||
Measured in amperes, usually shown as kAIC.
|
||||
@@ -32,7 +32,7 @@ Measured in amperes, usually shown as kAIC.
|
||||
|
||||
* "withstand rating"
|
||||
|
||||
[[nfpa-70_110_requirements#110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics.|NEC 110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics.]]
|
||||
[[nfpa-70_110_requirements#^10|NEC 110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics.]]
|
||||
|
||||
Applies to **assemblies**: distribution equipment like switchboards, panelboards, switches, etc.
|
||||
|
||||
|
||||
@@ -34,11 +34,13 @@ Please confirm you have received this email and respond with any questions or co
|
||||
### Project Specification Callouts
|
||||
|
||||
* **Conduit:**
|
||||
%% GRC, coupling specs, etc. %%
|
||||
* EMT Fittings: _---Spec 260510 2.4(N)(2) (p. 2226)_
|
||||
* Smaller than trade size 2-1/2": Compression
|
||||
* Trade size 2-1/2" and larger: Set-screw
|
||||
|
||||
* **Wire:**
|
||||
* Material: Aluminum 100A and larger _---E021 "ALUMINUM FEEDER SCHEDULE" Note 1(b)_
|
||||
* Acceptable Manufacturers: _---Spec 260510-2 (p. 2224)_
|
||||
* Material: Aluminum 1 AWG and larger _---Spec 260510 2.2(C)(1) (p. 2224)_
|
||||
* Acceptable Manufacturers: _---Spec 260510 2.2(D) (p. 2224)_
|
||||
* Encore Wire
|
||||
* General Cable
|
||||
* Okonite
|
||||
@@ -48,69 +50,80 @@ Please confirm you have received this email and respond with any questions or co
|
||||
* Southwire
|
||||
|
||||
* **MC Cable:**
|
||||
* Application: Concealed feeders and branch circuits _---Spec XXXXXX (p. XXXX)_
|
||||
%% Branch homeruns only; Not permitted %%
|
||||
* Acceptable Manufacturers: _---Spec 260510-2 (p. 2224)_
|
||||
* Application: "dry locations only where approved by code authority."
|
||||
_---Spec 260510 2.4(N)(8) (p. 2227)_
|
||||
|
||||
* Acceptable Manufacturers: _---Spec 260510 2.2(E) (p. 2224)_
|
||||
* Alflex
|
||||
* AFC
|
||||
* America Metal Moulding
|
||||
* Encore Wire
|
||||
* Southwire
|
||||
* ==Conductors: Copper _---Spec XXXXXX (p. XXXX)_==
|
||||
* ==Armor: Steel _---Spec XXXXXX (p. XXXX)_==
|
||||
* ==Jacket: PVC _---Spec XXXXXX (p. XXXX)_==
|
||||
|
||||
* **Steel Box Depth:**
|
||||
* Telecom: 2-1/8" _---Spec XXXXXX (p. XXXX)_
|
||||
* Security: 2-1/8" _---Spec XXXXXX (p. XXXX)_
|
||||
* Other Applications: Not specified
|
||||
%% 1-1/2", 2-1/8" %%
|
||||
* **Steel Box Depth:** Not specified _---Spec 260510 2.12(A) (p. 2231)_
|
||||
|
||||
* **Floor Boxes:** Sheet metal with brass or aluminum covers _---Spec XXXXXX (p. XXXX)_
|
||||
* **Floor Boxes:** _---Spec 260510 2.12(E) (p. 2231)_
|
||||
* Box Material:
|
||||
* Slab on grade: Cast iron
|
||||
* Slabs above grade: Stamped steel
|
||||
|
||||
* Cover Material: Not specified.
|
||||
|
||||
* **Wiring Devices:**
|
||||
* Units:
|
||||
* Current rating: Unspecified. Assuming 15A for takeoff.
|
||||
* Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff.
|
||||
%% 15A Decora %%
|
||||
* BOH/Common Areas:
|
||||
* Current rating: Unspecified. Assuming 20A for takeoff.
|
||||
* Standard/Decora: Unspecified. Assuming Toggle/Duplex for takeoff.
|
||||
%% 20A Toggle/Duplex %%
|
||||
* All Areas:
|
||||
* Current rating: 20A _---Spec 260510 2.16(B)(1) (p. 2231)_
|
||||
* Standard/Decora: Decora _---Spec 260510 2.16(D) (p. 2231)_
|
||||
|
||||
* **Switchboards:**
|
||||
* Acceptable Manufacturers: _---Spec XXXXXX (p. XXXX)_
|
||||
* ???
|
||||
* Bus Material: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* Interrupting Current Rating: ???
|
||||
* Bus Material: "aluminum or copper, tin or silver plated" _---Spec 262000 2.6(C)(4) (p. 2297)_
|
||||
* OCPD Interrupting Current Ratings: Not specified.
|
||||
* Acceptable Manufacturers: _---Spec 262000 2.17(C) (p. 2307)_
|
||||
* Eaton
|
||||
* ABB/GE
|
||||
* Schneider Electric
|
||||
* Siemens
|
||||
|
||||
* **Distribution Panelboards:**
|
||||
* Acceptable Manufacturers: _---Spec XXXXXX (p. XXXX)_
|
||||
* ???
|
||||
* Bus Material: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* Breaker Types: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
%% Snap-on, bolt on %%
|
||||
* Interrupting Current Rating: ???
|
||||
* **Panelboards:**
|
||||
* Bus Material: "silver plated copper or electro-tin plated aluminum"
|
||||
_---Spec 262000 2.8(E) (p. 2303)_
|
||||
|
||||
* Breaker Types: Bolt-on _---Spec 262000 2.9(C) (p. 2303)_
|
||||
|
||||
* **Load Centers:**
|
||||
* Acceptable Manufacturers: _---Spec XXXXXX (p. XXXX)_
|
||||
* ???
|
||||
* Bus Material: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* Breaker Types: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
%% Snap-on, bolt on %%
|
||||
* Interrupting Current Rating: ???
|
||||
* OCPD Interrupting Current Ratings:
|
||||
* Distribution Panelboards: Not specified.
|
||||
* Lighting and Appliance Panelboards: Not less than 10kAIC
|
||||
_---Spec 262000 2.10(A)(3) (p. 2304)_
|
||||
|
||||
* Acceptable Manufacturers: _---Spec 262000 2.17(C) (p. 2307)_
|
||||
* Eaton
|
||||
* ABB/GE
|
||||
* Schneider Electric
|
||||
* Siemens
|
||||
|
||||
* **Transformers:**
|
||||
* Winding Material: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* K-Rating: ???
|
||||
%% Windings AL or CU, K-rating %%
|
||||
* Winding Material:
|
||||
"Transformer windings shall be manufacturer's standard design,
|
||||
copper or aluminum conductor. Bussing shall be copper."
|
||||
_---Spec 262002.5(L) (p. 2296)_
|
||||
|
||||
* K-Rating: Only as shown (None shown)
|
||||
_---Spec 262002.5(K) (p. 2295)_
|
||||
|
||||
* **Generator:** (1) 500kW Diesel
|
||||
* Enclosure Specs: ??? _---Dwg. E014_
|
||||
* Remote Tank: ???
|
||||
* Tank Size: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* Load Banks: ??? _---Spec XXXXXX (p. XXXX)_
|
||||
* Acceptable Manufacturers: _---Spec 263213-3 (p. 2323)_
|
||||
* Acceptable Manufacturers: _---Spec 262000 2.17(D) (p. 2307)_
|
||||
* Eaton
|
||||
* ABB/GE
|
||||
* Heavy Duty
|
||||
* MGM
|
||||
* Siemens
|
||||
* Schneider Electric
|
||||
* United Power Corp
|
||||
|
||||
* **Generator:** (1) 500kW Diesel _---Dwg. E05-12_
|
||||
* Enclosure Specs: Not specified.
|
||||
* Remote Tank: None shown or specified.
|
||||
* Tank Size: 12hrs at full load _---Spec 263213 2.7(C) (p. 2326)_
|
||||
* Load Banks: None shown or specified.
|
||||
* Acceptable Manufacturers: _---Spec 263213 2.1(A) (p. 2323)_
|
||||
* Caterpillar Tractor Co.
|
||||
* Cummins/Power Generation
|
||||
* Kohler Power Systems (MTU Engine Only)
|
||||
@@ -125,28 +138,31 @@ Please confirm you have received this email and respond with any questions or co
|
||||
|
||||
### PDI System Execution Plan
|
||||
|
||||
* **Primaries:**
|
||||
%% Installation only, (9) 6" PVC %%
|
||||
* **Primaries:** Wiring only, duct bank by others.
|
||||
|
||||
* **Secondaries:**
|
||||
*
|
||||
* **Secondaries:** Aluminum bus duct. _---Spec 262000 2.11(D) (p. 2305)_
|
||||
%% PVC UG, GRC Stub-ups, AL %%
|
||||
|
||||
* **Feeders:**
|
||||
PVC UG, EMT OH;
|
||||
Size and material per E05-10 schedule
|
||||
==(Transformer primaries and secondaries all copper)==
|
||||
==(AL 100A and larger,==
|
||||
==transformer primaries and secondaries all copper)==
|
||||
%% PVC UG, EMT OH, AL over 100A, 2% VD %%
|
||||
%% Emergency Feeds MI Cable %%
|
||||
|
||||
* **Unit Subfeeds:** ???
|
||||
* **Unit Subfeeds:** #12 Multi-Circuit MC OH (alternate for voltage drop)
|
||||
%% MC OH AL, VD per Chart on E5.01 %%
|
||||
|
||||
* **Units:**
|
||||
* ???
|
||||
%% [[2026-03-10_13-51-32#Voltage Drop]] %%
|
||||
|
||||
* **==Units==:**
|
||||
* VFCU HVAC
|
||||
* 20A Decora Switches
|
||||
* 20A Decora Receptacles
|
||||
%% 15A Decora, Disposals, T-stat, Floor Boxes, Shade Control, Doorbells, Dimmer Switches, etc. %%
|
||||
|
||||
* **Telecom:**
|
||||
* **Telecom:** Rough-in only
|
||||
* ???
|
||||
%% 42" MSDE, No Cable Homeruns, (1) 1" Back to IDF, CAT6 with Stub-ups %%
|
||||
|
||||
@@ -164,21 +180,24 @@ Please confirm you have received this email and respond with any questions or co
|
||||
|
||||
### Lighting Control
|
||||
|
||||
* **Basis of Takeoff:** ??? _---???_
|
||||
%% Code Minimum per Energy Code Assigned, P&S, PDI Design %%
|
||||
* **Basis of Takeoff:** Central dimming system per P&S, PDR quote.
|
||||
|
||||
* **Area:** _---Dwg. E06-01 "LIGHTING CONTROL NARRATIVE"_
|
||||
*
|
||||
* Units: Master Switch, Digital Standalone Control, 0-10V dimming.
|
||||
* Amenity: Digital Central Control, 0-10V dimming
|
||||
* Garage: Integral dimming occupancy sensors, 120V wiring only.
|
||||
%% Assign Method to Areas: Line Voltage, Low-Voltage Stand Alone or Centralized System %%
|
||||
|
||||
### Tasks/Quotes Needed for WBS
|
||||
|
||||
%% Delete any completed %%
|
||||
|
||||
%%
|
||||
* Electrical Constructability Review
|
||||
* Electrical VDC
|
||||
* Coordination Study
|
||||
* DAS Public Safety Raceway Design
|
||||
%%
|
||||
|
||||
<!--
|
||||
DAS Public Safety Raceway Design is necessary
|
||||
|
||||
@@ -0,0 +1,118 @@
|
||||
---
|
||||
id: 2026-03-10T13:51:32-04:00
|
||||
aliases: []
|
||||
title: 2026-03-10 13:51:32
|
||||
tags:
|
||||
- authorship/original
|
||||
- destiny/permanent
|
||||
- status/draft
|
||||
- type/timestamped
|
||||
dg-publish: true
|
||||
date-created: 2026-03-10T13:51:32-04:00
|
||||
daily: "[[2026-03-10]]"
|
||||
weekly: "[[2026-W11]]"
|
||||
monthly: "[[2026-03]]"
|
||||
quarterly: "[[2026-Q1]]"
|
||||
yearly: "[[2026]]"
|
||||
---
|
||||
# 2026-03-10 13:51:32
|
||||
|
||||
## Charlotte South End Hotel Spec Interpretation
|
||||
|
||||
[[charlotte-south-end-hotel|Charlotte South End Hotel]]
|
||||
|
||||
### EMT Fittings
|
||||
|
||||
> [!quote] Spec 260510 2.4(E)
|
||||
> EMT - Electrical metallic tubing, "thin wall" zinc coated steel, enameled interior, ANSI C80.3, UL-797,
|
||||
> assembled using concrete tight and rain tight gland-ring compression threaded type fittings
|
||||
> except where alternate type fittings are allowable by the NEC
|
||||
> and authorities have jusrisdiction \[sic\].
|
||||
|
||||
> [!quote] Spec 260510 2.4(N)(2)
|
||||
> EMT connectors - Provide gland ring compression threaded fittings, except-
|
||||
> * a. Concrete tight double set screw type connectors
|
||||
> are acceptable in 2 1/2-inch and larger sizes
|
||||
> in dry locations only.
|
||||
|
||||
> [!quote] Joel Jansen 2026-03-10 (pp.)
|
||||
> Takeoff as specified
|
||||
|
||||
### Liquid-Tight Conduit
|
||||
|
||||
> [!quote] Spec 260510 2.4(G)
|
||||
> Liquid-tight flexible metallic raceway
|
||||
> shall be similar to standard flexible steel conduit
|
||||
> except encased in liquid tight neoprene outer jacket.
|
||||
|
||||
No definition is provided for a liquid-tight flexible non-metallic raceway
|
||||
|
||||
> [!quote] Spec 260510 2.4(G)(7) (text decoration added)
|
||||
> Provide _liquid-tight flexible conduit_
|
||||
> for each motor and rotating device for power and control, ~~computer room~~[^1]
|
||||
> and for other equipment requiring adjustments or removal for service
|
||||
> in mechanical rooms or where subject to moisture or weather.
|
||||
|
||||
> [!quote] Joel Jansen 2026-03-10 (pp.)
|
||||
>
|
||||
|
||||
[^1]: I feel fairly confident this is erroneous.
|
||||
|
||||
### Voltage Drop
|
||||
|
||||
> [!quote] Spec 260510 2.2(C)(4) (text decoration added)
|
||||
> Sizing of conductors and conduits
|
||||
> shall be solely the responsibility of the Contractor
|
||||
> and shall be based on the NEC, [[nfpa-70_310_conductors_for_general_wiring|Article 310]].
|
||||
> Ampacity shall be equal to, or greater than, the required load specified.
|
||||
> ==Voltage drop shall be no greater than that allowed by the NEC.==
|
||||
|
||||
> [!quote] Dwg. E00-00 "GENERAL PRICING NOTES" Note 9
|
||||
> PROVIDE ALLOWANCE TO UPSIZE FEEDERS/BRANCH CIRCUITS
|
||||
> (OVER 100 FEET FOR 120/208V, OVER 200 FEET FOR 277/480V)
|
||||
> FOR A MAXIMUM OF 3% VOLTAGE DROP.
|
||||
|
||||
### Lighting Control
|
||||
|
||||
> [!quote] LD 03-XX Typical Master Switch Callout
|
||||
> MASTER - TO CONTROL ENTRY AND ROOM ONLY. ELECTRICAL ENGINEER TO SPECIFY ENERGY CODE COMPLIANT “MASTER OFF” FOR THE REQUIRED GUESTROOM LOADS. GMLD RECOMMENDS LUTRON’S "CODE-SMART" SYSTEM THAT POWERS THE LIGHTING SHOWN HERE AS WELL AS TAKES INPUT FROM THIRD-PARTYDOOR CONTACTS, THERMOSTATS AND OCCUPANCY SENSORS. THIS SYSTEM MEETS THE ENERGY CODE REQUIREMENT TO TURN OFF LOADS AFTER A SPECIFIC PERIOD OF TIME AND ALSO PREVENTS LOADS FROM TURNING ON OR OFF UNEXPECTEDLY IN THE MIDDLE OF THE NIGHT.
|
||||
|
||||
Lighting control quote does not include master switches
|
||||
|
||||
> [!quote] PDR Lutron Lighting Control Quote 2025-12-10
|
||||
> (13) Pre-Assembled Processor Panel,
|
||||
> (14) Athena Centralized Din Lighting Control Panel,
|
||||
> (14) DALI ESN Panel,
|
||||
> (14) QS Sensor Module,
|
||||
> (4) Touchscreen,
|
||||
> (112) QS Wired Keypads,
|
||||
> (2) Partition Sensor,
|
||||
> (31) Wired Occupancy Sensor,
|
||||
> (2) 5 Contact Closure Inputs and 5 Relay Outputs
|
||||
|
||||
> [!quote] Proposal 2025-12-12, Pricing Summary
|
||||
> Lighting Controls – Lutron (turnkey) $ 850,000
|
||||
|
||||
Assuming that this line includes master switches
|
||||
based on sum of quote and switch allowance
|
||||
|
||||
> [!quote] PDR Lutron Lighting Control Quote 2025-12-10, Pricing Summary –Turnkey
|
||||
> Lighting Control: Lutron $ 738,400.00
|
||||
|
||||
> [!quote] 2025.12.09 - Charlotte South End Hotel - Bid Sheet v16-4-2, "Add-On Items"
|
||||
> master switch in guestrooms - TBD | $ 72,023
|
||||
|
||||
### EV Chargers
|
||||
|
||||
> [!quote] Proposal 2025-12-12, Alternates
|
||||
> Add: (21) EV-Capable and (3) EV-Installed per Building Connected $ 38,000
|
||||
|
||||
Panel LG's schedule (E06-13)
|
||||
shows (10) 40A/2P circuits
|
||||
with description "EV CHARGER".
|
||||
|
||||
These circuits are not shown on the electrical set,
|
||||
nor are any chargers besides.
|
||||
|
||||
|
||||
> this is a quote
|
||||