# 2026-03-10 13:51:32
|
||||
|
||||
## Charlotte South End Hotel Spec Interpretation
|
||||
|
||||
[[charlotte-south-end-hotel|Charlotte South End Hotel]]
|
||||
|
||||
### EMT Fittings
|
||||
|
||||
> [!quote] Spec 260510 2.4(E)
|
||||
> EMT - Electrical metallic tubing, "thin wall" zinc coated steel, enameled interior, ANSI C80.3, UL-797,
|
||||
> assembled using concrete tight and rain tight gland-ring compression threaded type fittings
|
||||
> except where alternate type fittings are allowable by the NEC
|
||||
> and authorities have jusrisdiction \[sic\].
|
||||
|
||||
> [!quote] Spec 260510 2.4(N)(2)
|
||||
> EMT connectors - Provide gland ring compression threaded fittings, except-
|
||||
> * a. Concrete tight double set screw type connectors
|
||||
> are acceptable in 2 1/2-inch and larger sizes
|
||||
> in dry locations only.
|
||||
|
||||
> [!quote] Joel Jansen 2026-03-10 (pp.)
|
||||
> Takeoff as specified
|
||||
|
||||
### Liquid-Tight Conduit
|
||||
|
||||
> [!quote] Spec 260510 2.4(G)
|
||||
> Liquid-tight flexible metallic raceway
|
||||
> shall be similar to standard flexible steel conduit
|
||||
> except encased in liquid tight neoprene outer jacket.
|
||||
|
||||
No definition is provided for a liquid-tight flexible non-metallic raceway
|
||||
|
||||
> [!quote] Spec 260510 2.4(G)(7) (text decoration added)
|
||||
> Provide _liquid-tight flexible conduit_
|
||||
> for each motor and rotating device for power and control, ~~computer room~~[^1]
|
||||
> and for other equipment requiring adjustments or removal for service
|
||||
> in mechanical rooms or where subject to moisture or weather.
|
||||
|
||||
> [!quote] Joel Jansen 2026-03-10 (pp.)
|
||||
>
|
||||
|
||||
[^1]: I feel fairly confident this is erroneous.
|
||||
|
||||
### Voltage Drop
|
||||
|
||||
> [!quote] Spec 260510 2.2(C)(4) (text decoration added)
|
||||
> Sizing of conductors and conduits
|
||||
> shall be solely the responsibility of the Contractor
|
||||
> and shall be based on the NEC, [[nfpa-70_310_conductors_for_general_wiring|Article 310]].
|
||||
> Ampacity shall be equal to, or greater than, the required load specified.
|
||||
> ==Voltage drop shall be no greater than that allowed by the NEC.==
|
||||
|
||||
> [!quote] Dwg. E00-00 "GENERAL PRICING NOTES" Note 9
|
||||
> PROVIDE ALLOWANCE TO UPSIZE FEEDERS/BRANCH CIRCUITS
|
||||
> (OVER 100 FEET FOR 120/208V, OVER 200 FEET FOR 277/480V)
|
||||
> FOR A MAXIMUM OF 3% VOLTAGE DROP.
|
||||
|
||||
### Lighting Control
|
||||
|
||||
> [!quote] LD 03-XX Typical Master Switch Callout
|
||||
> MASTER - TO CONTROL ENTRY AND ROOM ONLY. ELECTRICAL ENGINEER TO SPECIFY ENERGY CODE COMPLIANT “MASTER OFF” FOR THE REQUIRED GUESTROOM LOADS. GMLD RECOMMENDS LUTRON’S "CODE-SMART" SYSTEM THAT POWERS THE LIGHTING SHOWN HERE AS WELL AS TAKES INPUT FROM THIRD-PARTYDOOR CONTACTS, THERMOSTATS AND OCCUPANCY SENSORS. THIS SYSTEM MEETS THE ENERGY CODE REQUIREMENT TO TURN OFF LOADS AFTER A SPECIFIC PERIOD OF TIME AND ALSO PREVENTS LOADS FROM TURNING ON OR OFF UNEXPECTEDLY IN THE MIDDLE OF THE NIGHT.
|
||||
|
||||
Lighting control quote does not include master switches
|
||||
|
||||
> [!quote] PDR Lutron Lighting Control Quote 2025-12-10
|
||||
> (13) Pre-Assembled Processor Panel,
|
||||
> (14) Athena Centralized Din Lighting Control Panel,
|
||||
> (14) DALI ESN Panel,
|
||||
> (14) QS Sensor Module,
|
||||
> (4) Touchscreen,
|
||||
> (112) QS Wired Keypads,
|
||||
> (2) Partition Sensor,
|
||||
> (31) Wired Occupancy Sensor,
|
||||
> (2) 5 Contact Closure Inputs and 5 Relay Outputs
|
||||
|
||||
> [!quote] Proposal 2025-12-12, Pricing Summary
|
||||
> Lighting Controls – Lutron (turnkey) $ 850,000
|
||||
|
||||
Assuming that this line includes master switches
|
||||
based on sum of quote and switch allowance
|
||||
|
||||
> [!quote] PDR Lutron Lighting Control Quote 2025-12-10, Pricing Summary –Turnkey
|
||||
> Lighting Control: Lutron $ 738,400.00
|
||||
|
||||
> [!quote] 2025.12.09 - Charlotte South End Hotel - Bid Sheet v16-4-2, "Add-On Items"
|
||||
> master switch in guestrooms - TBD | $ 72,023
|
||||
|
||||
### EV Chargers
|
||||
|
||||
> [!quote] Proposal 2025-12-12, Alternates
|
||||
> Add: (21) EV-Capable and (3) EV-Installed per Building Connected $ 38,000
|
||||
|
||||
Panel LG's schedule (E06-13)
|
||||
shows (10) 40A/2P circuits
|
||||
with description "EV CHARGER".
|
||||
|
||||
These circuits are not shown on the electrical set,
|
||||
nor are any chargers besides.
|
||||
|
||||
|
||||
> this is a quote
|
||||