@@ -308,9 +308,7 @@ In other than dwelling units, in addition to the requirements in 110.16(A), a pe
|
||||
> ANSI Z535.4-2011, Product Safety Signs and Labels, provides guidelines for the design of safety signs and labels for application to products.
|
||||
|
||||
> [!info] Informational Note No. 3:
|
||||
> Acceptable industry practices for equipment labeling are described in NFPA 70E-2018, Standard for Electrical
|
||||
|
||||
Safety in the Workplace. This standard provides specific criteria for developing arc-flash labels for equipment that provides nominal system voltage, incident energy levels, arc-flash boundaries, minimum required levels of personal protective equipment, and so forth.
|
||||
> Acceptable industry practices for equipment labeling are described in NFPA 70E-2018, Standard for Electrical Safety in the Workplace. This standard provides specific criteria for developing arc-flash labels for equipment that provides nominal system voltage, incident energy levels, arc-flash boundaries, minimum required levels of personal protective equipment, and so forth.
|
||||
|
||||
### 110.18 Arcing Parts.
|
||||
|
||||
@@ -356,7 +354,8 @@ Reconditioned equipment shall be identified as "reconditioned" and the original
|
||||
|
||||
Where caution, warning, or danger signs or labels are required by this Code, the labels shall meet the following requirements:
|
||||
|
||||
* (1) The marking shall warn of the hazards using effective words, colors, symbols, or any combination thereof.
|
||||
* (1) The marking shall warn of the hazards
|
||||
using effective words, colors, symbols, or any combination thereof.
|
||||
|
||||
> [!info] Informational Note:
|
||||
> ANSI Z535.4-2011, Product Safety Signs and Labels, provides guidelines for suitable font sizes, words, colors, symbols, and location requirements for labels.
|
||||
@@ -799,9 +798,9 @@ Doors shall be equipped with locks, and doors shall be kept locked, with access
|
||||
Where a transformer is installed in a vault as required by Article 450, the vault shall be constructed in accordance with the requirements of Part III of Article 450.
|
||||
|
||||
> [!info] Informational Note No. 1:
|
||||
> For additional information, see ANSI/ASTM E119-2018a, Method for Fire Tests of Building Construction and
|
||||
|
||||
Materials, and NFPA 80-2019, Standard for Fire Doors and Other Opening Protectives.
|
||||
> For additional information, see ANSI/ASTM E119-2018a,
|
||||
> Method for Fire Tests of Building Construction and Materials,
|
||||
> and NFPA 80-2019, Standard for Fire Doors and Other Opening Protectives.
|
||||
|
||||
> [!info] Informational Note No. 2:
|
||||
> A typical 3-hour construction is 150 mm (6 in.) thick reinforced concrete.
|
||||
@@ -945,17 +944,12 @@ The points of control shall be located so that persons are not likely to come in
|
||||
|
||||
Unguarded live parts above working space shall be maintained at elevations not less than required by Table 110.34(E).
|
||||
|
||||
Table 110.34(E) Elevation of Unguarded Live Parts
|
||||
Table 110.34(E) Elevation of Unguarded Live Parts Above Working Space
|
||||
|
||||
Above Working Space
|
||||
|
||||
Nominal Voltage
|
||||
|
||||
Between Phases
|
||||
|
||||
Elevation m ft
|
||||
1001--7500 V 2.7 9
|
||||
7501--35,000 V 2.9 9 ft 6 in.
|
||||
| Nominal Voltage Between Phases | Elevation |
|
||||
| ------------------------------ | ----------------- |
|
||||
| 1001--7500 V | 2.7m (9 ft) |
|
||||
| 7501--35,000 V | 2.9m (9 ft 6 in.) |
|
||||
|
||||
Over 35 kV Add 9.5 mm per kV above 35 kV
|
||||
|
||||
|
||||