@@ -714,7 +714,7 @@ Intermediate supports shall be provided
|
||||
as necessary to limit supported conductor lengths
|
||||
to not greater than those values specified in Table 300.19(A).
|
||||
|
||||
#### Table 300.19(A) Spacings for Conductor Supports ^t300-19a
|
||||
#### Table 300.19(A) Spacings for Conductor Supports
|
||||
|
||||
| Conductor Size | Aluminum or Copper-Clad Aluminum | Copper |
|
||||
| -------------------------------- | --------------------------------:| ------:|
|
||||
@@ -731,33 +731,31 @@ to not greater than those values specified in Table 300.19(A).
|
||||
Support methods and spacing intervals for fire-rated cables and conductors
|
||||
shall comply with any restrictions provided in the listing
|
||||
of the electrical circuit protective system used
|
||||
and in no case shall exceed the values in [[#^t300-19a|Table 300.19(A)]].
|
||||
and in no case shall exceed the values in [[#Table 300.19(A) Spacings for Conductor Supports|Table 300.19(A)]].
|
||||
|
||||
#### 300.19(C) Support Methods.
|
||||
|
||||
One of the following methods of support shall be used:
|
||||
|
||||
1. Clamping devices constructed of or employing insulating wedges
|
||||
inserted in the ends of the raceways.
|
||||
Where clamping of insulation does not adequately support the cable,
|
||||
the conductor also shall be clamped.
|
||||
inserted in the ends of the raceways.
|
||||
Where clamping of insulation does not adequately support the cable,
|
||||
the conductor also shall be clamped.
|
||||
|
||||
2. Inserting boxes at the required intervals
|
||||
in which insulating supports are installed and secured
|
||||
in an approved manner to withstand the weight of the conductors attached thereto,
|
||||
the boxes being provided with covers.
|
||||
in which insulating supports are installed and secured
|
||||
in an approved manner to withstand the weight of the conductors attached thereto,
|
||||
the boxes being provided with covers.
|
||||
|
||||
3. In junction boxes, deflecting the cables not less than 90 degrees
|
||||
and carrying them horizontally to a distance not less than twice the diameter of the cable,
|
||||
the cables being carried on two or more insulating supports
|
||||
and additionally secured thereto by tie wires, if desired.
|
||||
Where this method is used, cables shall be supported at intervals
|
||||
not greater than 20 percent of the support spacing in [[#^t300-19a|Table 300.19(A)]].
|
||||
and carrying them horizontally to a distance not less than twice the diameter of the cable,
|
||||
the cables being carried on two or more insulating supports
|
||||
and additionally secured thereto by tie wires, if desired.
|
||||
Where this method is used, cables shall be supported at intervals
|
||||
not greater than 20 percent of the support spacing in [[#Table 300.19(A) Spacings for Conductor Supports|Table 300.19(A)]].
|
||||
|
||||
4. Other approved means.
|
||||
|
||||
%% TODO: TEXT OMITTED %%
|
||||
|
||||
### 300.20 Induced Currents in Ferrous Metal Enclosures or Ferrous Metal Raceways.
|
||||
|
||||
#### 300.20(A) Conductors Grouped Together.
|
||||
|
||||
Reference in New Issue