From 854a7700485ad99a622e0214f2b72a7d8732b824 Mon Sep 17 00:00:00 2001 From: Zane Meyers Date: Wed, 12 Nov 2025 16:49:17 -0500 Subject: [PATCH] vault backup: 2025-11-12 16:49:17 --- alternating-current.md | 40 +- conductor-sizing.md | 27 +- distributed-antenna-systems-takeoff.md | 2 +- lighting-controls-takeoff.md | 42 +- nfpa-70_215_feeders.md | 207 +- nfpa-70_250_grounding-and-bonding.md | 2460 ++++++++++++++++++++++++ nfpa-70_300_general-requirements.md | 2 +- nfpa-70_450_transformers.md | 571 +++++- nfpa-70_national-electric-code.md | 2 +- twisted-pair-cable.md | 35 + voltage-drop.md | 7 +- 11 files changed, 3272 insertions(+), 123 deletions(-) create mode 100644 nfpa-70_250_grounding-and-bonding.md create mode 100644 twisted-pair-cable.md diff --git a/alternating-current.md b/alternating-current.md index 9c0c43b..1f78fb6 100644 --- a/alternating-current.md +++ b/alternating-current.md @@ -41,7 +41,7 @@ The voltage measured between any line and neutral is called **phase voltage**. The formula for active power in a three phase system is given by $$ -P = \sqrt{3} \times V_{L} \times I_{L} \times PF +P = \sqrt{3} \times V_{L} \times I_{L} \times \text{PF} $$ where: @@ -49,7 +49,7 @@ where: * $P$ is the active power, * $V_{L}​$ is the line voltage, * $I_{L}$ is the line current, -* $PF$ is the power factor. +* $\text{PF}$ is the power factor. The formula for apparent power in a three phase system is given by @@ -65,28 +65,26 @@ where: ### Voltage Systems -208Y/120V -480Y/277V - 120/240V 1-Phase 3-Wire: -* 120V 1-Phase 2-Wire # Line to Neutral -* 240V 1-Phase 2-Wire # Line to Line +* 120V 1-Phase 2-Wire --- Line to Neutral +* 240V 1-Phase 2-Wire --- Line to Line -120/208V 3-Phase 4-Wire: -* 120V 1-Phase 2-Wire # Line to Neutral -* 208V 1-Phase 2-Wire # Line to Line -* 208V 3-Phase 3-Wire # Line to Lines +208Y/120V 3-Phase 4-Wire: +* 120V 1-Phase 2-Wire --- Line to Neutral +* 208V 1-Phase 2-Wire --- Line to Line +* 208V 3-Phase 3-Wire --- Line to Lines -277/480V 3-Phase 4-Wire: -* 277V 1-Phase 2-Wire # Line to Neutral -* 480V 1-Phase 2-Wire # Line to Line -* 480V 3-Phase 3-Wire # Line to Lines +480Y/277V 3-Phase 4-Wire: +* 277V 1-Phase 2-Wire --- Line to Neutral +* 480V 1-Phase 2-Wire --- Line to Line +* 480V 3-Phase 3-Wire --- Line to Lines -wiring-configurations: -* 1-Phase 2-Wire # Line to Line (2-Pole) or Line to Neutral (1-Pole) -* 1-Phase 3-Wire # Line to Line and Line to Neutral (2-Pole) -* 3-Phase 3-Wire # Line to Lines (3-Pole) -* 3-Phase 4-Wire # Line to Lines and Line to Neutral (3-Pole) +Wiring Configurations + +* 1-Phase 2-Wire --- Line to Line (2-Pole) or Line to Neutral (1-Pole) +* 1-Phase 3-Wire --- Line to Line and Line to Neutral (2-Pole) +* 3-Phase 3-Wire --- Line to Lines (3-Pole) +* 3-Phase 4-Wire --- Line to Lines and Line to Neutral (3-Pole) ## Active and Reactive Power @@ -120,7 +118,7 @@ derived from these components are others: is the ratio of active power to apparent power. $$ -P = S \times \text{PF}, \quad S = \frac{P}{\text{PF}}, \quad PF = \frac{P}{\text{S}} +P = S \times \text{PF}, \quad S = \frac{P}{\text{PF}}, \quad \text{PF} = \frac{P}{\text{S}} $$ ### Power Factor Correction diff --git a/conductor-sizing.md b/conductor-sizing.md index 323b5a8..e4bb7aa 100644 --- a/conductor-sizing.md +++ b/conductor-sizing.md @@ -16,6 +16,16 @@ overcurrent protection is sized to protect the conductors. ## "The 80% Rule" +> [!danger] +> This description is provided _for reference only_. +> +> Like every NEC "rule" +> that isn't preceded by a section reference, +> it is _not_ code. +> +> It is my opinion that this should never be repeated, +> even as shorthand. + "The 80% Rule" is a rule of thumb referring to a common convention of several articles including: @@ -36,12 +46,16 @@ and it is stated that conductors are suitable for 80% their listed rating, since 80% is the reciprocal of 125%. +The rule neglects important context and common exceptions, +namely transformers, whose feeder conductors are sized at 100%. + +![[nfpa-70_215_feeders#215.2(B)(1) Feeders Supplying Transformers.]] + ## Branch Circuits ### Receptacle Branch -> [!important] -> There is no maximum number of receptacles per circuit _in any occupancy_. +There is no maximum number of receptacles per circuit _in any occupancy_. It is a common misconception that the limit can be calculated with a formula like @@ -67,14 +81,7 @@ or at least was at some point in the design. ## Feeders -> [!cite] NEC Article 250 (emphasis added) -> ### 250.122 Size of Equipment Grounding Conductors -> #### (A) General. -> Copper, aluminum, or copper-clad aluminum -> equipment grounding conductors of the wire type -> shall not be smaller than shown in Table 250.122, -> but in no case shall they be required to be larger -> than the circuit conductors supplying the equipment... +![[nfpa-70_250_grounding-and-bonding#250.122(A) General.]] Apparently in the 2026 NEC First Draft Meetings, Code Making Panel 5 clarified that the equipment grounding conductor (EGC) diff --git a/distributed-antenna-systems-takeoff.md b/distributed-antenna-systems-takeoff.md index 6715651..2a37287 100644 --- a/distributed-antenna-systems-takeoff.md +++ b/distributed-antenna-systems-takeoff.md @@ -39,7 +39,7 @@ Match Fire Alarm takeoff Length and Count ### Stairwell Riser Every 2 Floors > [!info] Takeoff -> * `Area` = "Typical - Building Even Levels" +> * `Area` = "Typical - Stairwells Building Even Levels" > > 1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`STAIRWELL RISER EVERY 2 FLRS = ...` > * **Count** = Each stairwell diff --git a/lighting-controls-takeoff.md b/lighting-controls-takeoff.md index d259691..257dc95 100644 --- a/lighting-controls-takeoff.md +++ b/lighting-controls-takeoff.md @@ -26,6 +26,9 @@ Determine which Systems and Codes are required: ## PDI Lighting Control Configurations +> [!important] +> This section is currently not practical + ### Stand Alone 0-10V dim -- "LV cable" is 2 conductor @@ -42,19 +45,19 @@ Takeoff homeruns to the DLM (one per controlled circuit) ### Networked -#### Devices +"LV Cable" is [[twisted-pair-cable]] -##### Room Controllers +#### Room Controllers No room controllers are necessary, lighting zones are switched from a central lighting control panel (LCP) -##### Switches and Sensors +#### Switches and Sensors Takeoff rough-in for switches and occupancy sensors ?? -(only if time based; length based on closeness to sw/occ sensor) +(only if time based; length based on proximity to switch or occupancy sensor) ?? #### Homeruns @@ -65,18 +68,26 @@ Takeoff 1 circuit homerun per lighting zone. PDI default configuration -Takeoff (1) DLM controller for the fixtures -and (1) Plug controller for the receptacle -* If room has both dimmable fixtures and the controlled receptacle, - only (1) DLM controller and (1) Plug controller -* Use MC to cover room if drop -* Use EMT if exposed or MC not permitted +#### Room Controllers + +For all rooms with dimmable fixtures +and/or automatically controlled receptacles, +take off (1) of either or both as appropriate. + +`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...` + +`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`REC PLUG CONTROLLER - ...` Takeoff normal power to the controlled load * Add LV cable to fixture branch -* Use 12/3 for receptacles +* Use \#12/3 for controlled receptacles Takeoff rough-in for both the occ sensors and the LV switch + +`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... LV SW - WALL ROUGH IN ...` + +`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... SENSOR LOW VOLTAGE - ROUGH IN ...` + * Free air if possible * **Length** = length of room @@ -90,7 +101,14 @@ If occupancy sensors are shown in the corridors: Takeoff homerun back to the electric room Takeoff (1) DLM controller for each electric room -* Run free air down corridor + +`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...` + +?? +Run free-air down corridor +?? + +* **Length** = Length of corridor Takeoff rough-in for each occupancy sensor shown. diff --git a/nfpa-70_215_feeders.md b/nfpa-70_215_feeders.md index 36e738d..ac43931 100644 --- a/nfpa-70_215_feeders.md +++ b/nfpa-70_215_feeders.md @@ -15,11 +15,10 @@ title: Article 215 Feeders ## 215.1 Scope. -This article covers the installation requirements, overcurrent protection requirements, minimum size, and ampacity of conductors for -feeders. +This article covers the installation requirements, overcurrent protection requirements, minimum size, and ampacity of conductors for feeders. -Exception: -Feeders for electrolytic cells as covered in 668.3(C)(1) and (C)(4). +> [!important] Exception: +> Feeders for electrolytic cells as covered in 668.3(C)(1) and (C)(4). #### 215.2 Minimum Rating and Size. @@ -35,54 +34,180 @@ and shall comply with 110.14(C). or any combination of continuous and noncontinuous loads, the minimum feeder conductor size shall have an ampacity not less than the noncontinuous load plus 125 percent of the continuous load. - + + > [!important] Exception No. 1: + > If the assembly, including the overcurrent devices protecting the feeder(s), is listed for operation at 100 percent of its rating, the ampacity of the feeder conductors shall be permitted to be not less than the sum of the continuous load plus the noncontinuous load. + + > [!important] Exception No. 2: + > Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections as covered in 110.14(C)(2), it shall be permitted to have an ampacity not less than the sum of the continuous load plus the noncontinuous load. No portion of a feeder installed under this exception shall extend into an enclosure containing either the feeder supply or the feeder load terminations, as covered in 110.14(C)(1). + + > [!important] Exception No. 3: + > Grounded conductors that are not connected to an overcurrent device shall be permitted to be sized at 100 percent of the continuous and noncontinuous load. + + * (b) The minimum feeder conductor size shall have an ampacity not less than the maximum load to be served after the application of any adjustment or correction factors in accordance with [[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts -- 2000 Volts.|310.14]]. -Exception No. 1: -If the assembly, including the overcurrent devices protecting the feeder(s), -is listed for operation at 100 percent of its rating, -the ampacity of the feeder conductors shall be permitted to be not less -than the sum of the continuous load plus the noncontinuous load. +> [!info] Informational Note No. 1: +> See Examples D1 through D11 in Informative Annex D. -Exception No. 2: -Where a portion of a feeder is connected at both its supply and load ends -to separately installed pressure connections as covered in 110.14(C)(2), -it shall be permitted to have an ampacity -not less than the sum of the continuous load plus the noncontinuous load. -No portion of a feeder installed under this exception -shall extend into an enclosure containing either the feeder supply -or the feeder load terminations, as covered in 110.14(C)(1). +> [!info] Informational Note No. 2: +> Conductors for feeders, as defined in Article 100, sized to prevent a voltage drop exceeding 3 percent at the farthest outlet of power, heating, and lighting loads, or combinations of such loads, and where the maximum total voltage drop on both feeders and branch circuits to the farthest outlet does not exceed 5 percent, will provide reasonable efficiency of operation. -Exception No. 3: -Grounded conductors that are not connected to an overcurrent device -shall be permitted to be sized at 100 percent -of the continuous and noncontinuous load. +> [!info] Informational Note No. 3: +> See 210.19(A), Informational Note No. 4, for voltage drop for branch circuits. -Informational Note No. 1: -See Examples D1 through D11 in Informative Annex D. +##### 215.2(A)(2) Grounded Conductor. -Informational Note No. 2: -Conductors for feeders, as defined in Article 100, -sized to prevent a voltage drop exceeding 3 percent -at the farthest outlet of power, heating, and lighting loads, -or combinations of such loads, -and where the maximum total voltage drop on both feeders and branch circuits -to the farthest outlet does not exceed 5 percent, -will provide reasonable efficiency of operation. +The size of the feeder circuit grounded conductor shall not be smaller than that required by 250.122, except that 250.122(F) shall not apply where grounded conductors are run in parallel. -Informational Note No. 3: -See 210.19(A), Informational Note No. 4, for voltage drop for branch circuits. +Additional minimum sizes shall be as specified in 215.2(A)(3) under the conditions stipulated. -#### 215.2(A)(2) Grounded Conductor. +##### 215.2(A)(3) Ampacity Relative to Service Conductors. -The size of the feeder circuit grounded conductor -shall not be smaller than that required by 250.122, -except that 250.122(F) shall not apply -where grounded conductors are run in parallel. +The feeder conductor ampacity shall not be less than that of the service conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of 55 amperes or less. -Additional minimum sizes shall be as specified in 215.2(A)(3) -under the conditions stipulated. +#### 215.2(B) Feeders over 1000 Volts. + +The ampacity of conductors shall be in accordance with 310.14 and 311.60 as applicable. Where installed, the size of the feeder-circuit grounded conductor shall not be smaller than that required by 250.122, except that 250.122(F) shall not apply where grounded conductors are run in parallel. Feeder conductors over 1000 volts shall be sized in accordance with 215.2(B)(1), (B)(2), or (B)(3). + +##### 215.2(B)(1) Feeders Supplying Transformers. + +The ampacity of feeder conductors +shall not be less than the sum of the nameplate ratings of the transformers supplied +when only transformers are supplied. + +##### 215.2(B)(2) Feeders Supplying Transformers and Utilization Equipment. + +The ampacity of feeders supplying a combination +of transformers and utilization equipment +shall not be less than the sum of the nameplate ratings of the transformers +and 125 percent of the designed potential load of the utilization equipment +that will be operated simultaneously. + +##### 215.2(B)(3) Supervised Installations. + +For supervised installations, feeder conductor sizing shall be permitted to be determined by qualified persons under engineering supervision in accordance with 310.14(B) or 311.60(B). Supervised installations are defined as those portions of a facility where all of the following conditions are met: + +* (1) Conditions of design and installation are provided under engineering supervision. + +* (2) Qualified persons with documented training and experience in over 1000-volt systems provide maintenance, monitoring, and servicing of the system. + +### 215.3 Overcurrent Protection. + +Feeders shall be protected against overcurrent in accordance with Part I of Article 240. Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125 percent of the continuous load. + +> [!important] Exception: +> Where the assembly, including the overcurrent devices protecting the feeder(s), is listed for operation at 100 percent of its rating, the ampere rating of the overcurrent device shall be permitted to be not less than the sum of the continuous load plus the noncontinuous load. + +### 215.4 Feeders with Common Neutral Conductor. + + +#### 215.4(A) Feeders with Common Neutral. + +Up to three sets of 3-wire feeders or two sets of 4-wire or 5-wire feeders shall be permitted to utilize a common neutral. + +#### 215.4(B) In Metal Raceway or Enclosure. + +Where installed in a metal raceway or other metal enclosure, all conductors of all feeders using a common neutral conductor shall be enclosed within the same raceway or other enclosure as required in 300.20. + +### 215.5 Diagrams of Feeders. + +If required by the authority having jurisdiction, a diagram showing feeder details shall be provided prior to the installation of the feeders. + +Such a diagram shall show the area in square feet of the building or other structure supplied by each feeder, the total calculated load before applying demand factors, the demand factors used, the calculated load after applying demand factors, and the size and type of conductors to be used. + +### 215.6 Feeder Equipment Grounding Conductor. + +Where a feeder supplies branch circuits +in which equipment grounding conductors are required, +the feeder shall include or provide an equipment grounding conductor, +to which the equipment grounding conductors of the branch circuits shall be connected. +Where the feeder supplies a separate building or structure, +the requirements of [[nfpa-70_250_grounding-and-bonding#250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s).|250.32]] shall apply. + +### 215.7 Ungrounded Conductors Tapped from Grounded Systems. + +Two-wire dc circuits and ac circuits of two or more ungrounded conductors shall be permitted to be tapped from the ungrounded conductors of circuits having a grounded neutral conductor. Switching devices in each tapped circuit shall have a pole in each ungrounded conductor. + +### 215.9 Ground-Fault Circuit-Interrupter Protection for Personnel. + +Feeders shall be permitted to be protected by a ground-fault circuit interrupter installed in a readily accessible location in lieu of the provisions for such interrupters as specified in 210.8 and 590.6(A). + +### 215.10 Ground-Fault Protection of Equipment. + +Each feeder disconnect rated 1000 amperes or more and installed on solidly grounded wye electrical systems of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase, shall be provided with ground-fault protection of equipment in accordance with 230.95. + +> [!info] Informational Note: +> For buildings that contain health care occupancies, see 517.17. + +> [!important] Exception No. 1: +> This section shall not apply to a disconnecting means for a continuous industrial process where a nonorderly shutdown will introduce additional or increased hazards. + +> [!important] Exception No. 2: +> This section shall not apply if ground-fault protection of equipment is provided on the supply side of the feeder and on the load side of any transformer supplying the feeder. + +> [!important] Exception No. 3: +> If temporary feeder conductors are used to connect a generator to a facility for repair, maintenance, or emergencies, ground-fault protection of equipment shall not be required. Temporary feeders without ground-fault protection shall be permitted for the time period necessary but shall not exceed 90 days. + +### 215.11 Circuits Derived from Autotransformers. + +Feeders shall not be derived from autotransformers unless the system supplied has a grounded conductor that is electrically connected to a grounded conductor of the system supplying the autotransformer. + +> [!important] Exception No. 1: +> An autotransformer shall be permitted without the connection to a grounded conductor where transforming from a nominal 208 volts to a nominal 240-volt supply or similarly from 240 volts to 208 volts. + +> [!important] Exception No. 2: +> In industrial occupancies, where conditions of maintenance and supervision ensure that only qualified persons service the installation, autotransformers shall be permitted to supply nominal 600-volt loads from nominal 480-volt systems, and 480-volt loads from nominal 600-volt systems, without the connection to a similar grounded conductor. + +### 215.12 Identification for Feeders. + + +#### 215.12(A) Grounded Conductor. + +The grounded conductor of a feeder, if insulated, shall be identified in accordance with 200.6. + +#### 215.12(B) Equipment Grounding Conductor. + +The equipment grounding conductor shall be identified in accordance with 250.119. + +#### 215.12(C) Identification of Ungrounded Conductors. + +Ungrounded conductors shall be identified in accordance with 215.12(C)(1) or (C)(2), as applicable. + +##### 215.12(C)(1) Feeders Supplied from More Than One Nominal Voltage System. + +Where the premises wiring system has feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feeder shall be identified by phase or line and system at all termination, connection, and splice points in compliance with 215.12(C)(1) + +* (a) and (b). + +* (a) Means of Identification. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means. + +* (b) Posting of Identification Means. The method utilized for conductors originating within each feeder panelboard or similar feeder distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each feeder panelboard or similar feeder distribution equipment. + +##### 215.12(C)(2) Feeders Supplied from Direct-Current Systems. + +Where a feeder is supplied from a dc system operating at more than 60 volts, each ungrounded conductor of 4 AWG or larger shall be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor of 6 AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 215.12(C)(2)(a) and (b). The identification methods utilized for conductors originating within each feeder panelboard or similar feeder distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each feeder panelboard or similar feeder distribution equipment. + +* (a) Positive Polarity, Sizes 6 AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means: + + * (1) A continuous red outer finish + + * (2) A continuous red stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or black + + * (3) Imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.8(B) + + * (4) An approved permanent marking means such as sleeving or shrink-tubing that is suitable for the conductor size, at all termination, connection, and splice points, with imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black + +* (b) Negative Polarity, Sizes 6 AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means: + + * (1) A continuous black outer finish + + * (2) A continuous black stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or red + + * (3) Imprinted minus signs (–) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.8(B) + + * (4) An approved permanent marking means such as sleeving or shrink-tubing that is suitable for the conductor size, at all termination, connection, and splice points, with imprinted minus signs (–) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red diff --git a/nfpa-70_250_grounding-and-bonding.md b/nfpa-70_250_grounding-and-bonding.md new file mode 100644 index 0000000..1081f3b --- /dev/null +++ b/nfpa-70_250_grounding-and-bonding.md @@ -0,0 +1,2460 @@ +--- +id: +aliases: + - nec-250 +tags: + - authorship/other + - destiny/uncertain + - exclude-from-word-count + - status/draft + - topic/construction/electrical + - type/media +title: Article 250 Grounding and Bonding +--- +# Article 250 Grounding and Bonding + +## Part I. General + +### 250.1 Scope. + +This article covers general requirements for grounding and bonding of electrical installations, and the specific requirements in (1) through (6). + +* (1) Systems, circuits, and equipment required, permitted, or not permitted to be grounded + +* (2) Circuit conductor to be grounded on grounded systems + +* (3) Location of grounding connections + +* (4) Types and sizes of grounding and bonding conductors and electrodes + +* (5) Methods of grounding and bonding + +* (6) Conditions under which guards, isolation, or insulation may be substituted for grounding + +> [!info] Informational Note: +> See Figure 250.1 for information on the organization of Article 250 covering grounding and bonding requirements. + +Figure 250.1 Grounding and Bonding. + +### 250.3 Application of Other Articles. + +For other articles applying to particular cases of installation of conductors and equipment, grounding and bonding requirements are identified in Table 250.3 that are in addition to, or modifications of, those of this article. + +#### Table 250.3 Additional Grounding and Bonding Requirements + +| Conductor/Equipment | Article | Section | +| ------------------------------------------------------------------------------------------- | ------- | ------------------------------------------ | +| Agricultural buildings | | 547.9 and 547.10 | +| Audio signal processing, amplification, and reproduction equipment | | 640.7 | +| Branch circuits | | 210.5, 210.6, 406.3 | +| Cablebus | | 370.60 | +| Cable trays | 392 | 392.60 | +| Capacitors | | 460.10, 460.27 | +| Circuits and equipment operating at less than 50 volts | 720 | | +| Communications circuits | 800 | | +| Community antenna television and radio distribution systems | | 820.93, 820.100, 820.103, 800.106, 800.100 | +| Conductors for general wiring | 310 | | +| Medium voltage conductors and cables | 311 | | +| Cranes and hoists | 610 | | +| Electrically driven or controlled irrigation machines | | 675.11(C), 675.12, 675.13, 675.14, 675.15 | +| Electric signs and outline lighting | 600 | | +| Electrolytic cells | 668 | | +| Elevators, dumbwaiters, escalators, moving walks, wheelchair lifts, and stairway chairlifts | 620 | | +| Fixed electric heating equipment for pipelines and vessels | | 427.29, 427.48 | +| Fixed outdoor electric deicing and snow-melting equipment | | 426.27 | +| Flexible cords and cables | | 400.22, 400.23 | +| Floating buildings | | 555.54, 555.55, 555.56 | +| Grounding-type receptacles, adapters, cord connectors, and attachment plugs | | 406.10 | +| Hazardous (classified) locations | 500--517 | | +| Health care facilities | 517 | | +| Induction and dielectric heating equipment | 665 | | +| Industrial machinery | 670 | | +| Information technology equipment | | 645.14, 645.15 | +| Intrinsically safe systems | | 504.50 | +| Luminaires and lighting equipment | | 410.40, 410.42, 410.46, 410.155(B) | +| Luminaires, lampholders, and lamps | 410 | | +| Marinas and boatyards | | 555.37, 555.38 | +| Mobile homes and mobile home park | 550 | | +| Motion picture and television studios and similar locations | | 530.20, 530.64(B) | +| Motors, motor circuits, and controllers | 430 | | +| Natural and artificially made bodies of water | 682 | 682.30, 682.31, 682.32, 682.33 | +| Network powered broadband communications circuits | | 800.100, 800.106, 830.93 | +| Optical fiber cables | | 770.100 | +| Outlet, device, pull, and junction boxes; conduit bodies; and fittings | | 314.4, 314.25 | +| Over 600 volts, nominal, underground wiring methods | | 300.50(C) | +| Panelboards | | 408.40 | +| Pipe organs | 650 | | +| Radio and television equipment | 810 | | +| Receptacles and cord connectors | | 406.3 | +| Recreational vehicles and recreational vehicle parks | 551 | | +| Services | 230 | | +| Solar photovoltaic systems | | 690.41, 690.42, 690.43, 690.45, 690.47 | +| Swimming pools, fountains, and similar installations | 680 | | +| Switchboards and panelboards | | 408.18(C) | +| Switches | | 404.12 | +| Theaters, audience areas of motion picture and television studios, and similar locations | | 520.81 | +| Transformers and transformer vaults | | 450.10 | +| Use and identification of grounded conductors | 200 | | +| X-ray equipment | 660 | 517.78 | + +### 250.4 General Requirements for Grounding and Bonding. + +The following general requirements identify what grounding and bonding of electrical systems are required to accomplish. The prescriptive methods contained in Article 250 shall be followed to comply with the performance requirements of this section. + +#### 250.4(A) Grounded Systems. + +##### 250.4(A)(1) Electrical System Grounding. + +Electrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that will stabilize the voltage to earth during normal operation. + +> [!info] Informational Note No. 1: +> An important consideration for limiting the imposed voltage is the routing of bonding and grounding electrode conductors so that they are not any longer than necessary to complete the connection without disturbing the permanent parts of the installation and so that unnecessary bends and loops are avoided. + +> [!info] Informational Note No. 2: +> See NFPA 780-2017, Standard for the Installation of Lightning Protection Systems, for information on installation of grounding and bonding for lightning protection systems. + +##### 250.4(A)(2) Grounding of Electrical Equipment. + +Normally non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth so as to limit the voltage to ground on these materials. + +##### 250.4(A)(3) Bonding of Electrical Equipment. + +Normally non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected together and to the electrical supply source in a manner that establishes an effective ground-fault current path. + +##### 250.4(A)(4) Bonding of Electrically Conductive Materials and Other Equipment. + +Normally non-current-carrying electrically conductive materials that are likely to become energized shall be connected together and to the electrical supply source in a manner that establishes an effective ground-fault current path. + +##### 250.4(A)(5) Effective Ground-Fault Current Path. + +Electrical equipment and wiring and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit facilitating the operation of the overcurrent device or ground detector for high-impedance grounded systems. It shall be capable of safely carrying the maximum ground-fault current likely to be imposed on it from any point on the wiring system where a ground fault may occur to the electrical supply source. The earth shall not be considered as an effective ground-fault current path. + +#### 250.4(B) Ungrounded Systems. + +##### 250.4(B)(1) Grounding Electrical Equipment. + +non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected to earth in a manner that will limit the voltage imposed by lightning or unintentional contact with higher-voltage lines and limit the voltage to ground on these materials. + +> [!info] Informational Note: +> See NFPA 780-2017, Standard for the Installation of Lightning Protection Systems, for information on installation of grounding and bonding for lightning protection systems. + +##### 250.4(B)(2) Bonding of Electrical Equipment. + +non-current-carrying conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, shall be connected together and to the supply system grounded equipment in a manner that creates a low-impedance path for ground-fault current that is capable of carrying the maximum fault current likely to be imposed on it. + +##### 250.4(B)(3) Bonding of Electrically Conductive Materials and Other Equipment. + +Electrically conductive materials that are likely to become energized shall be connected together and to the supply system grounded equipment in a manner that creates a low-impedance path for ground-fault current that is capable of carrying the maximum fault current likely to be imposed on it. + +##### 250.4(B)(4) Path for Fault Current. + +Electrical equipment, wiring, and other electrically conductive material likely to become energized shall be installed in a manner that creates a low-impedance circuit from any point on the wiring system to the electrical supply source to facilitate the operation of overcurrent devices should a second ground fault from a different phase occur on the wiring system. The earth shall not be considered as an effective fault-current path. + +### 250.6 Objectionable Current. + +#### 250.6(A) Arrangement to Prevent Objectionable Current. + +The grounding of electrical systems, circuit conductors, surge arresters, surge-protective devices, and conductive normally non-current-carrying metal parts of equipment shall be instal led and arranged in a manner that will prevent objectionable current. + +#### 250.6(B) Alterations to Stop Objectionable Current. + +If the use of multiple grounding connections results in objectionable current and the requirements of 250.4(A)(5) or (B)(4) are met, one or more of the following alterations shall be permitted: + +* (1) Discontinue one or more but not all of such grounding connections. + +* (2) Change the locations of the grounding connections. + +* (3) Interrupt the continuity of the conductor or conductive path causing the objectionable current. + +* (4) Take other suitable remedial and approved action. + +#### 250.6(C) Temporary Currents Not Classified as Objectionable Currents. + +Temporary currents resulting from abnormal conditions, such as ground faults, shall not be classified as objectionable current for the purposes specified in 250.6(A) and (B). + +#### 250.6(D) Limitations to Permissible Alterations. + +This section shall not be considered as permitting electronic equipment to be operated on ac systems or branch circuits that are not connected to an equipment grounding conductor as required by this article. Currents that introduce electromagnetic interference or data errors in electronic equipment shall not be considered the objectionable currents addressed in this section. + +#### 250.6(E) Isolation of Objectionable Direct-Current Ground Currents. + +Where isolation of objectionable dc ground currents from cathodic protection systems is required, a listed ac coupling/dc isolating device shall be permitted in the equipment grounding conductor path to provide an effective return path for ac ground-fault current while blocking dc current. + +### 250.8 Connection of Grounding and Bonding Equipment. + +#### 250.8(A) Permitted Methods. + +Equipment grounding conductors, grounding electrode conductors, and bonding jumpers shall be connected by one or more of the following means: + +* (1) Listed pressure connectors + +* (2) Terminal bars + +* (3) Pressure connectors listed as grounding and bonding equipment + +* (4) Exothermic welding process + +* (5) Machine screw-type fasteners that engage not less than two threads or are secured with a nut + +* (6) Thread-forming machine screws that engage not less than two threads in the enclosure + +* (7) Connections that are part of a listed assembly + +* (8) Other listed means + +#### 250.8(B) Methods Not Permitted. + +Connection devices or fittings that depend solely on solder shall not be used. + +### 250.10 Protection of Ground Clamps and Fittings. + +Ground clamps or other fittings exposed to physical damage shall be enclosed in metal, wood, or equivalent protective covering. + +### 250.12 Clean Surfaces. + +Nonconductive coatings (such as paint, lacquer, and enamel) on equipment to be grounded or bonded shall be removed from threads and other contact surfaces to ensure good electrical continuity or shall be connected by means of fittings designed so as to make such removal unnecessary. + +## Part II. System Grounding + +### 250.20 Alternating-Current Systems to Be Grounded. + +Alternating-current systems shall be grounded as provided for in 250.20(A), (B), (C), or (D). Other systems shall be permitted to be grounded. If such systems are grounded, they shall comply with the applicable provisions of this article. + +> [!info] Informational Note: +> An example of a system permitted to be grounded is a corner-grounded delta transformer connection. See 250.26(4) for conductor to be grounded. + +#### 250.20(A) Alternating-Current Systems of Less Than 50 Volts. + +Alternating-current systems of less than 50 volts shall be grounded under any of the following conditions: + +* (1) Where supplied by transformers, if the transformer supply system exceeds 150 volts to ground + +* (2) Where supplied by transformers, if the transformer supply system is ungrounded + +* (3) Where installed outside as overhead conductors + +#### 250.20(B) Alternating-Current Systems of 50 Volts to 1000 Volts. + +Alternating-current systems of 50 volts to 1000 volts that supply premises wiring and premises wiring systems shall be grounded under any of the following conditions: + +* (1) Where the system can be grounded so that the maximum voltage to ground on the ungrounded conductors does not exceed 150 volts + +* (2) Where the system is 3-phase, 4-wire, wye connected in which the neutral conductor is used as a circuit conductor + +* (3) Where the system is 3-phase, 4-wire, delta connected in which the midpoint of one phase winding is used as a circuit conductor + +> [!info] Informational Note: +> According to Annex O of NFPA 70E-2018, Standard for Electrical Safety in the Workplace, high impedance grounding is an effective tool to reduce arc flash hazards. + +#### 250.20(C) Alternating-Current Systems of over 1000 Volts. + +Alternating-current systems supplying mobile or portable equipment shall be grounded as specified in 250.188. Where supplying other than mobile or portable equipment, such systems shall be permitted to be grounded. + +#### 250.20(D) Impedance Grounded Neutral Systems. + +Impedance grounded neutral systems shall be grounded in accordance with 250.36 or 250.187. + +### 250.21 Alternating-Current Systems of 50 Volts to 1000 Volts Not Required to Be Grounded. + +#### 250.21(A) General. + +The following ac systems of 50 volts to 1000 volts shall be permitted to be grounded but shall not be required to be grounded: + +* (1) Electrical systems used exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like + +* (2) Separately derived systems used exclusively for rectifiers that supply only adjustable-speed industrial drives + +* (3) Separately derived systems supplied by transformers that have a primary voltage rating of 1000 volts or less if all the following conditions are met: + * a. The system is used exclusively for control circuits. + * b. The conditions of maintenance and supervision ensure that only qualified persons service the installation. + * c. Continuity of control power is required. + +* (4) Other systems that are not required to be grounded in accordance with the requirements of 250.20(B) + +#### 250.21(B) Ground Detectors. + +Ground detectors shall be installed in accordance with 250.21(B)(1) and (B)(2). + +* (1) Ungrounded ac systems as permitted in 250.21(A)(1) through (A)(4) operating at not less than 120 volts and at 1000 volts or less shall have ground detectors installed on the system. + +* (2) The ground detection sensing equipment shall be connected as close as practicable to where the system receives its supply. + +#### 250.21(C) Marking. + +Ungrounded systems shall be legibly marked "Caution: Ungrounded System Operating --- \_\_\_\_\_Volts Between Conductors" at the source or first disconnecting means of the system. The marking shall be of sufficient durability to withstand the environment involved. + +### 250.22 Circuits Not to Be Grounded. + +The following circuits shall not be grounded: + +* (1) Circuits for electric cranes operating over combustible fibers in Class III locations, as provided in 503.155 + +* (2) Circuits in health care facilities as provided in 517.61 and 517.160 + +* (3) Circuits for equipment within electrolytic cell line working zones as provided in Article 668 + +* (4) Secondary circuits of lighting systems as provided in 411.6(A) + +* (5) Secondary circuits of lighting systems as provided in 680.23(A)(2) + +* (6) Class 2 load side circuits for suspended ceiling low-voltage power grid distribution systems as provided in 393.60(B) + +### 250.24 Grounding of Service-Supplied Alternating-Current Systems. + +#### 250.24(A) System Grounding Connections. + +A premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor at each service, in accordance with 250.24(A)(1) through (A) (5). + +##### 250.24(A)(1) General. + +The grounding electrode conductor connection shall be made at any accessible point from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral to, including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. + +> [!info] Informational Note: +> See definitions of Service Conductors, Overhead; Service Conductors, Underground; Service Drop; and Service + +Lateral in Article 100. + +##### 250.24(A)(2) Outdoor Transformer. + +Where the transformer supplying the service is located outside the building, at least one additional grounding connection shall be made from the grounded service conductor to a grounding electrode, either at the transformer or elsewhere outside the building. + +> [!important] Exception: +> The additional grounding electrode conductor connection shall not be made on high-impedance grounded neutral systems. + +The system shall meet the requirements of 250.36. + +##### 250.24(A)(3) Dual-Fed Services. + +For services that are dual fed (double ended) in a common enclosure or grouped together in separate enclosures and employing a secondary tie, a single grounding electrode conductor connection to the tie point of the grounded conductor(s) from each power source shall be permitted. + +##### 250.24(A)(4) Main Bonding Jumper as Wire or Busbar. + +Where the main bonding jumper specified in 250.28 is a wire or busbar and is installed from the grounded conductor terminal bar or bus to the equipment grounding terminal bar or bus in the service equipment, the grounding electrode conductor shall be permitted to be connected to the equipment grounding terminal, bar, or bus to which the main bonding jumper is connected. + +##### 250.24(A)(5) Load-Side Grounding Connections. + +A grounded conductor shall not be connected to normally non-current-carrying metal parts of equipment, to equipment grounding conductor(s), or be reconnected to ground on the load side of the service disconnecting means except as otherwise permitted in this article. + +> [!info] Informational Note: +> See 250.30 for separately derived systems, 250.32 for connections at separate buildings or structures, and 250.142 for use of the grounded circuit conductor for grounding equipment. + +#### 250.24(B) Main Bonding Jumper. + +For a grounded system, an unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor within the enclosure for each service disconnect in accordance with 250.28. + +> [!important] Exception No. 1: +> Where more than one service disconnecting means is located in an assembly listed for use as service equipment, an unspliced main bonding jumper shall bond the grounded conductor(s) to the assembly enclosure. + +> [!important] Exception No. 2: +> Impedance grounded neutral systems shall be permitted to be connected as provided in 250.36 and 250.187. + +#### 250.24(C) Grounded Conductor Brought to Service Equipment. + +Where an ac system operating at 1000 volts or less is grounded at any point, the grounded conductor(s) shall be routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with 250.24(C)(1) through (C)(4). + +> [!important] Exception: +> Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the grounded conductor(s) to the assembly common grounded conductor(s) terminal or bus. The assembly shall include a main bonding jumper for connecting the grounded conductor(s) to the assembly enclosure. + +##### 250.24(C)(1) Sizing for a Single Raceway or Cable. + +The grounded conductor shall not be smaller than specified in Table 250.102(C)(1). + +##### 250.24(C)(2) Parallel Conductors in Two or More Raceways or Cables. + +If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or cables, the grounded conductor shall also be installed in parallel. The size of the grounded conductor in each raceway or cable shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or cable, as indicated in 250.24(C) (1) , but not smaller than 1/0 AWG. + +> [!info] Informational Note: +> See 310.10(G) for grounded conductors connected in parallel. + +##### 250.24(C)(3) Delta-Connected Service. + +The grounded conductor of a 3-phase, 3-wire delta service shall have an ampacity not less than that of the ungrounded conductors. + +##### 250.24(C)(4) High Impedance. + +The grounded conductor on a high-impedance grounded neutral system shall be grounded in accordance with 250.36. + +#### 250.24(D) Grounding Electrode Conductor. + +A grounding electrode conductor shall be used to connect the equipment grounding conductors, the service-equipment enclosures, and, where the system is grounded, the grounded service conductor to the grounding electrode(s) required by Part III of this article. + +This conductor shall be sized in accordance with 250.66. + +High-impedance grounded neutral system connections shall be made as covered in 250.36. + +#### 250.24(E) Ungrounded System Grounding Connections. + +A premises wiring system that is supplied by an ac service that is ungrounded shall have, at each service, a grounding electrode conductor connected to the grounding electrode(s) required by Part III of this article. The grounding electrode conductor shall be connected to a metal enclosure of the service conductors at any accessible point from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral to the service disconnecting means. + +### 250.25 Grounding Systems Permitted to Be Connected on the Supply Side of the Disconnect. + +The grounding of systems connected on the supply side of the service disconnect, as permitted in 230.82, that are in enclosures separate from the service equipment enclosure shall comply with 250.25(A) or (B). + +#### 250.25(A) Grounded System. + +If the utility supply system is grounded, the grounding of systems permitted to be connected on the supply side of the service disconnect and are installed in one or more separate enclosures from the service equipment enclosure shall comply with the requirements of 250.24(A) through (D). + +#### 250.25(B) Ungrounded Systems. + +If the utility supply system is ungrounded, the grounding of systems permitted to be connected on the supply side of the service disconnect and are installed in one or more separate enclosures from the service equipment enclosure shall comply with the requirements of 250.24(E). + +### 250.26 Conductor to Be Grounded --- Alternating-Current Systems. + +For grounded ac premises wiring systems, the conductor to be grounded shall be as specified in the following: + +* (1) Single-phase, 2-wire --- one conductor + +* (2) Single-phase, 3-wire --- the neutral conductor + +* (3) Multiphase systems having one wire common to all phases --- the neutral conductor + +* (4) Multiphase systems where one phase is grounded --- that phase conductor + +* (5) Multiphase systems in which one phase is used as in (2) --- the neutral conductor + +### 250.28 Main Bonding Jumper and System Bonding Jumper. + +For a grounded system, main bonding jumpers and system bonding jumpers shall be installed as follows: + +#### 250.28(A) Material. + +Main bonding jumpers and system bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A main bonding jumper and a system bonding jumper shall be a wire, bus, screw, or similar suitable conductor. + +#### 250.28(B) Construction. + +Where a main bonding jumper or a system bonding jumper is a screw only, the screw shall be identified with a green finish that shall be visible with the screw installed. + +#### 250.28(C) Attachment. + +Main bonding jumpers and system bonding jumpers shall be connected in the manner specified in 250.8. + +#### 250.28(D) Size. + +Main bonding jumpers and system bonding jumpers shall be sized in accordance with 250.28(D)(1) through (D) (3). + +##### 250.28(D)(1) General. + +Main bonding jumpers and system bonding jumpers shall not be smaller than specified in Table 250.102(C) (1). + +##### 250.28(D)(2) Main Bonding Jumper for Service with More Than One Enclosure. + +If a service consists of more than a single enclosure as permitted in 230.71(B), the main bonding jumper for each enclosure shall be sized in accordance with 250.28(D)(1) based on the largest ungrounded service conductor serving that enclosure. + +##### 250.28(D)(3) Separately Derived System with More Than One Enclosure. + +Where a separately derived system supplies more than a single enclosure, the system bonding jumper for each enclosure shall be sized in accordance with 250.28(D)(1) based on the largest ungrounded feeder conductor serving that enclosure, or a single system bonding jumper shall be installed at the source and sized in accordance with 250.28(D)(1) based on the equivalent size of the largest supply conductor determined by the largest sum of the areas of the corresponding conductors of each set. + +### 250.30 Grounding Separately Derived Alternating-Current Systems. + +In addition to complying with 250.30(A) for grounded systems, or as provided in 250.30(B) for ungrounded systems, separately derived systems shall comply with 250.20, 250.21, 250.22, or 250.26, as applicable. Multiple power sources of the same type that are connected in parallel to form one system that supplies premises wiring shall be considered as a single separately derived system and shall be installed in accordance with 250.30. + +> [!info] Informational Note No. 1: +> An alternate ac power source, such as an on-site generator, is not a separately derived system if the grounded conductor is solidly interconnected to a service-supplied system grounded conductor. An example of such a situation is where alternate source transfer equipment does not include a switching action in the grounded conductor and allows it to remain solidly connected to the service-supplied grounded conductor when the alternate source is operational and supplying the load served. + +> [!info] Informational Note No. 2: +> See 445.13 for the minimum size of conductors that carry fault current. + +#### 250.30(A) Grounded Systems. + +A separately derived ac system that is grounded shall comply with 250.30(A)(1) through (A)(8). Except as otherwise permitted in this article, a grounded conductor shall not be connected to normally non-current-carrying metal parts of equipment, be connected to equipment grounding conductors, or be reconnected to ground on the load side of the system bonding jumper. + +> [!info] Informational Note: +> See 250.32 for connections at separate buildings or structures and 250.142 for use of the grounded circuit conductor for grounding equipment. + +> [!important] Exception: +> Impedance grounded neutral system grounding connections shall be made as specified in 250.36 or 250.187, as applicable. + +##### 250.30(A)(1) System Bonding Jumper. + +An unspliced system bonding jumper shall comply with 250.28(A) through (D). This connection shall be made at any single point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices, in accordance with 250.30(A)(1)(a) or +(A)(1)(b). The system bonding jumper shall remain within the enclosure where it originates. If the source is located outside the building or structure supplied, a system bonding jumper shall be installed at the grounding electrode connection in compliance with 250.30(C). + +> [!important] Exception No. 1: +> For systems installed in accordance with 450.6, a single system bonding jumper connection to the tie point of the grounded circuit conductors from each power source shall be permitted. + +> [!important] Exception No. 2: +> If a building or structure is supplied by a feeder from an outdoor separately derived system, a system bonding jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a parallel path for the grounded conductor. If a grounded conductor is used in this manner, it shall not be smaller than the size specified for the system bonding jumper but shall not be required to be larger than the ungrounded conductor(s). For the purposes of this exception, connection through the earth shall not be considered as providing a parallel path. + +> [!important] Exception No. 3: +> The size of the system bonding jumper for a system that supplies a Class 1, Class 2, or Class 3 circuit, and is derived from a transformer rated not more than 1000 volt-amperes, shall not be smaller than the derived ungrounded conductors and shall not be smaller than 14 AWG copper or 12 AWG aluminum. + +* (a) Installed at the Source. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper and the normally non-current-carrying metal enclosure. + +* (b) Installed at the First Disconnecting Means. The system bonding jumper shall connect the grounded conductor to the supply-side bonding jumper, the disconnecting means enclosure, and the equipment grounding conductor(s). + +> [!important] Exception: +> Separately derived systems consisting of multiple sources of the same type that are connected in parallel shall be permitted to have the system bonding jumper installed at the paralleling switchgear, switchboard, or other paralleling connection point instead of at the disconnecting means located at each separate source. + +##### 250.30(A)(2) Supply-Side Bonding Jumper. + +If the source of a separately derived system and the first disconnecting means are located in separate enclosures, a supply-side bonding jumper shall be installed with the circuit conductors from the source enclosure to the first disconnecting means enclosure. A supply-side bonding jumper shall not be required to be larger than the derived ungrounded conductors. The supply-side bonding jumper shall be permitted to be of nonflexible metal raceway type or of the wire or bus type as follows: + +* (1) A supply-side bonding jumper of the wire type shall comply with 250.102(C), based on the size of the derived ungrounded conductors. + +* (2) A supply-side bonding jumper of the bus type shall have a cross-sectional area not smaller than a supply-side bonding jumper of the wire type as determined in 250.102(C). + +> [!important] Exception: +> A supply-side bonding jumper shall not be required between enclosures for installations made in compliance with 250.30(A) +(1), Exception No. 2. + +##### 250.30(A)(3) Grounded Conductor. + +If a grounded conductor is installed and the system bonding jumper connection is not located at the source, 250.30(A)(3)(a) through (A) +(3)(d) shall apply. The grounded conductor shall not be required to be larger than the derived ungrounded conductors. + +* (a) Sizing for a Single Raceway. The grounded conductor shall not be smaller than specified in Table 250.102(C)(1). + +* (b) Parallel Conductors in Two or More Raceways. If the ungrounded conductors are installed in parallel in two or more raceways, the grounded conductor shall also be installed in parallel. The size of the grounded conductor in each raceway shall be based on the total circular mil area of the parallel derived ungrounded conductors in the raceway as indicated in 250.30(A)(3)(a), but not smaller than 1/0 AWG. + +> [!info] Informational Note: +> See 310.10(G) for grounded conductors connected in parallel. + +* (c) Delta-Connected System. The grounded conductor of a 3-phase, 3-wire delta system shall have an ampacity not less than that of the ungrounded conductors. + +* (d) Impedance Grounded System. The grounded conductor of an impedance grounded neutral system shall be installed in accordance with 250.36 or 250.187, as applicable. + +##### 250.30(A)(4) Grounding Electrode. + +The building or structure grounding electrode system shall be used as the grounding electrode for the separately derived system. If located outdoors, the grounding electrode shall be in accordance with 250.30(C). + +> [!important] Exception: +> If a separately derived system originates in equipment that is listed and identified as suitable for use as service equipment, the grounding electrode used for the service or feeder equipment shall be permitted to be used as the grounding electrode for the separately derived system. + +> [!info] Informational Note No. 1: +> See 250.104(D) for bonding requirements for interior metal water piping in the area served by separately derived systems. + +> [!info] Informational Note No. 2: +> See 250.50 and 250.58 for requirements for bonding all electrodes together if located at the same building or structure. + +##### 250.30(A)(5) Grounding Electrode Conductor, Single Separately Derived System. + +A grounding electrode conductor for a single separately derived system shall be sized in accordance with 250.66 for the derived ungrounded conductors. It shall be used to connect the grounded conductor of the derived system to the grounding electrode in accordance with 250.30(A)(4), or as permitted in 250.68(C)(1) and (C)(2). This connection shall be made at the same point on the separately derived system where the system bonding jumper is connected. + +> [!important] Exception No. 1: +> If the system bonding jumper specified in 250.30(A) (1) is a wire or busbar, it shall be permitted to connect the grounding electrode conductor to the equipment grounding terminal, bar, or bus if the equipment grounding terminal, bar, or bus is of sufficient size for the separately derived system. + +> [!important] Exception No. 2: +> If the source of a separately derived system is located within equipment listed and identified as suitable for use as service equipment, the grounding electrode conductor from the service or feeder equipment to the grounding electrode shall be permitted as the grounding electrode conductor for the separately derived system, if the grounding electrode conductor is of sufficient size for the separately derived system. If the equipment grounding bus internal to the equipment is not smaller than the required grounding electrode conductor for the separately derived system, the grounding electrode connection for the separately derived system shall be permitted to be made to the bus. + +> [!important] Exception No. 3: +> A grounding electrode conductor shall not be required for a system that supplies a Class 1, Class 2, or Class 3 circuit and is derived from a transformer rated not more than 1000 volt-amperes, provided the grounded conductor is bonded to the transformer frame or enclosure by a jumper sized in accordance with 250.30(A)(1), Exception No. 3, and the transformer frame or enclosure is grounded by one of the means specified in 250.134. + +##### 250.30(A)(6) Grounding Electrode Conductor, Multiple Separately Derived Systems. + +A common grounding electrode conductor for multiple separately derived systems shall be permitted. If installed, the common grounding electrode conductor shall be used to connect the grounded conductor of each separately derived system to the grounding electrode as specified in 250.30(A)(4). A grounding electrode conductor tap shall then be installed from each separately derived system to the common grounding electrode conductor. Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode conductor. This connection shall be made at the same point on the separately derived system where the system bonding jumper is connected. + +> [!important] Exception No. 1: +> If the system bonding jumper specified in 250.30(A) (1) is a wire or busbar, it shall be permitted to connect the grounding electrode conductor tap to the equipment grounding terminal, bar, or bus, provided the equipment grounding terminal, bar, or bus is of sufficient size for the separately derived system. + +> [!important] Exception No. 2: +> A grounding electrode conductor shall not be required for a system that supplies a Class 1, Class 2, or Class 3 circuit and is derived from a transformer rated not more than 1000 volt-amperes, provided the system grounded conductor is bonded to the transformer frame or enclosure by a jumper sized in accordance with 250.30(A)(1), Exception No. 3, and the transformer frame or enclosure is grounded by one of the means specified in 250.134. + +> [!important] Exception No. 3: +> If the source of a separately derived system is located within equipment listed and identified as suitable for use as service equipment, the grounding electrode conductor from the service or feeder equipment to the grounding electrode shall be permitted as the grounding electrode conductor for the separately derived system, if the grounding electrode conductor is of sufficient size for the separately derived system. If the equipment grounding bus internal to the equipment is not smaller than the required grounding electrode conductor for the separately derived system, the grounding electrode connection for the separately derived system shall be permitted to be made to the bus. + +* (a) Common Grounding Electrode Conductor. The common grounding electrode conductor shall be permitted to be one of the following: + +* (1) A conductor of the wire type not smaller than 3/0 AWG copper or 250 kcmil aluminum + +* (2) A metal water pipe that complies with 250.68(C)(1) + +* (3) The metal structural frame of the building or structure that complies with 250.68(C)(2) or is connected to the grounding electrode system by a conductor not smaller than 3/0 AWG copper or 250 kcmil aluminum + +* (b) Tap Conductor Size. Each tap conductor shall be sized in accordance with 250.66 based on the derived ungrounded conductors of the separately derived system it serves. + +> [!important] Exception to (a)(1) and (b): +> If the only electrodes that are present are of the types in 250.66(A), (B), or (C), the size of the common grounding electrode conductor shall not be required to be larger than the largest conductor required by 250.66(A), (B), or (C) for the type of electrode that is present. + +* (c) Connections. All tap connections to the common grounding electrode conductor shall be made at an accessible location by one of the following methods: + +* (1) A connector listed as grounding and bonding equipment. + +* (2) Listed connections to aluminum or copper busbars not smaller than 6 mm thick × 50 mm wide (1⁄4 in. thick × 2 in. wide) and of sufficient length to accommodate the number of terminations necessary for the installation. If aluminum busbars are used, the installation shall also comply with 250.64(A). + +* (3) The exothermic welding process. + +Tap conductors shall be connected to the common grounding electrode conductor in such a manner that the common grounding electrode conductor remains without a splice or joint. + +##### 250.30(A)(7) Installation. + +The installation of all grounding electrode conductors shall comply with 250.64(A), (B), (C), and (E). + +##### 250.30(A)(8) Bonding. + +Structural steel and metal piping shall be connected to the grounded conductor of a separately derived system in accordance with +250.104(D). + +#### 250.30(B) Ungrounded Systems. + +The equipment of an ungrounded separately derived system shall be grounded and bonded as specified in 250.30(B)(1) through (B)(3). + +##### 250.30(B)(1) Grounding Electrode Conductor. + +A grounding electrode conductor, sized in accordance with 250.66 for the largest derived ungrounded conductor(s) or set of derived ungrounded conductors, shall be used to connect the metal enclosures of the derived system to the grounding electrode as specified in +250.30(A)(5) or (A)(6), as applicable. This connection shall be made at any point on the separately derived system from the source to the first system disconnecting means. If the source is located outside the building or structure supplied, a grounding electrode connection shall be made in compliance with 250.30(C). + +##### 250.30(B)(2) Grounding Electrode. + +Except as permitted by 250.34 for portable and vehicle-mounted generators, the grounding electrode shall comply with 250.30(A)(4). + +##### 250.30(B)(3) Bonding Path and Conductor. + +A supply-side bonding jumper shall be installed from the source of a separately derived system to the first disconnecting means in compliance with 250.30(A)(2). + +#### 250.30(C) Outdoor Source. + +If the source of the separately derived system is located outside the building or structure supplied, a grounding electrode connection shall be made at the source location to one or more grounding electrodes in compliance with 250.50. In addition, the installation shall comply with 250.30(A) for grounded systems or with 250.30(B) for ungrounded systems. + +> [!important] Exception: +> The grounding electrode conductor connection for impedance grounded neutral systems shall comply with 250.36 or 250.187, as awpplicable. + +### 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). + +#### 250.32(A) Grounding Electrode. + +A building(s) or structure(s) supplied by a feeder(s) or branch circuit(s) shall have a grounding electrode system and grounding electrode conductor installed in accordance with Part III of Article 250. Where there is no existing grounding electrode, the grounding electrode(s) required in 250.50 shall be installed. + +> [!important] Exception: +> A grounding electrode shall not be required where only a single branch circuit, including a multiwire branch circuit, supplies the building or structure and the branch circuit includes an equipment grounding conductor for grounding the normally non-currentcarrying metal parts of equipment. + +#### 250.32(B) Grounded Systems. + +##### 250.32(B)(1) Supplied by a Feeder or Branch Circuit. + +An equipment grounding conductor, as described in 250.118, shall be run with the supply conductors and be connected to the building or structure disconnecting means and to the grounding electrode(s). The equipment grounding conductor shall be used for grounding or bonding of equipment, structures, or frames required to be grounded or bonded. The equipment grounding conductor shall be sized in accordance with 250.122. Any installed grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrode(s). + +> [!important] Exception No. 1: +> For installations made in compliance with previous editions of this Code that permitted such connection, the grounded conductor run with the supply to the building or structure shall be permitted to serve as the ground-fault return path if all of the following requirements continue to be met: + +* (1) An equipment grounding conductor is not run with the supply to the building or structure. + +* (2) There are no continuous metallic paths bonded to the grounding system in each building or structure involved. + +* (3) Ground-fault protection of equipment has not been installed on the supply side of the feeder(s). + +If the grounded conductor is used for grounding in accordance with the provision of this exception, the size of the grounded conductor shall not be smaller than the larger of either of the following: + +* (1) That required by 220.61 + +* (2) That required by 250.122 + +> [!important] Exception No. 2: +> If system bonding jumpers are installed in accordance with 250.30(A)(1), Exception No. 2, the feeder grounded circuit conductor at the building or structure served shall be connected to the equipment grounding conductors, grounding electrode conductor, and the enclosure for the first disconnecting means. + +##### 250.32(B)(2) Supplied by Separately Derived System. + +* (a) With Overcurrent Protection. If overcurrent protection is provided where the conductors originate, the installation shall comply with 250.32(B)(1). + +* (b) Without Overcurrent Protection. If overcurrent protection is not provided where the conductors originate, the installation shall comply with 250.30(A). If installed, the supply-side bonding jumper shall be connected to the building or structure disconnecting means and to the grounding electrode(s). + +#### 250.32(C) Ungrounded Systems. + +##### 250.32(C)(1) Supplied by a Feeder or Branch Circuit. + +An equipment grounding conductor, as described in 250.118, shall be installed with the supply conductors and be connected to the building or structure disconnecting means and to the grounding electrode(s). The grounding electrode(s) shall also be connected to the building or structure disconnecting means. + +##### 250.32(C)(2) Supplied by a Separately Derived System. + +* (a) With Overcurrent Protection. If overcurrent protection is provided where the conductors originate, the installation shall comply with 250.32(C)(1). + +* (b) Without Overcurrent Protection. If overcurrent protection is not provided where the conductors originate, the installation shall comply with 250.30(B). If installed, the supply-side bonding jumper shall be connected to the building or structure disconnecting means and to the grounding electrode(s). + +#### 250.32(D) Disconnecting Means Located in Separate Building or Structure on the Same Premises. + +Where one or more disconnecting means supply one or more additional buildings or structures under single management, and where these disconnecting means are located remote from those buildings or structures in accordance with 225.32, Exception No. 1 and No. 2, 700.12(D)(5), 701.12(D)(5), or 702.12, all of the following conditions shall be met: + +* (1) The connection of the grounded conductor to the grounding electrode, to normally non-current-carrying metal parts of equipment, or to the equipment grounding conductor at a separate building or structure shall not be made. + +* (2) An equipment grounding conductor for grounding and bonding any normally non-current-carrying metal parts of equipment, interior metal piping systems, and building or structural metal frames is run with the circuit conductors to a separate building or structure and connected to existing grounding electrode(s) required in Part III of this article, or, where there are no existing electrodes, the grounding electrode(s) required in Part III of this article shall be installed where a separate building or structure is supplied by more than one branch circuit. + +* (3) The connection between the equipment grounding conductor and the grounding electrode at a separate building or structure shall be made in a junction box, panelboard, or similar enclosure located immediately inside or outside the separate building or structure. + +#### 250.32(E) Grounding Electrode Conductor. + +The size of the grounding electrode conductor to the grounding electrode(s) shall not be smaller than given in 250.66, based on the largest ungrounded supply conductor. The installation shall comply with Part III of this article. + +### 250.34 Portable, Vehicle-Mounted, and Trailer-Mounted Generators. + +#### 250.34(A) Portable Generators. + +The frame of a portable generator shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by the generator under both of the following conditions: + +* (1) The generator supplies only equipment mounted on the generator, cord-and-plug-connected equipment through receptacles mounted on the generator, or both. + +* (2) The normally non-current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are connected to the generator frame. + +#### 250.34(B) Vehicle-Mounted and Trailer-Mounted Generators. + +The frame of a vehicle or trailer shall not be required to be connected to a grounding electrode as defined in 250.52 for a system supplied by a generator located on this vehicle or trailer under all of the following conditions: + +* (1) The frame of the generator is bonded to the vehicle or trailer frame. + +* (2) The generator supplies only equipment located on the vehicle or trailer; cord-and-plug-connected equipment through receptacles mounted on the vehicle; or both equipment located on the vehicle or trailer and cord-and-plug-connected equipment through receptacles mounted on the vehicle, trailer, or on the generator. + +* (3) The normally non-current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are connected to the generator frame. + +#### 250.34(C) Grounded Conductor Bonding. + +A system conductor that is required to be grounded by 250.26 shall be connected to the generator frame where the generator is a component of a separately derived system. + +> [!info] Informational Note: +> For grounding portable generators supplying fixed wiring systems, see 250.30. + +### 250.35 Permanently Installed Generators. + +A conductor that provides an effective ground-fault current path shall be installed with the supply conductors from a permanently installed generator(s) to the first disconnecting mean(s) in accordance with 250.35(A) or (B). + +#### 250.35(A) Separately Derived System. + +If the generator is installed as a separately derived system, the requirements in 250.30 shall apply. + +#### 250.35(B) Nonseparately Derived System. + +If the generator is installed as a nonseparately derived system, and overcurrent protection is not integral with the generator assembly, a supply-side bonding jumper shall be installed between the generator equipment grounding terminal and the equipment grounding terminal, bar, or bus of the disconnecting mean(s). It shall be sized in accordance with 250.102(C) based on the size of the conductors supplied by the generator. + +### 250.36 High-Impedance Grounded Neutral Systems. + +High-impedance grounded neutral systems in which a grounding impedance, usually a resistor, limits the ground-fault current to a low value shall be permitted for 3-phase ac systems of 480 volts to 1000 volts if all the following conditions are met: + +* (1) The conditions of maintenance and supervision ensure that only qualified persons service the installation. + +* (2) Ground detectors are installed on the system. + +* (3) Line-to-neutral loads are not served. + +High-impedance grounded neutral systems shall comply with 250.36(A) through (G). + +> [!info] Informational Note: +> According to Annex O of NFPA 70E-2018, Standard for Electrical Safety in the Workplace, high-impedance grounding is an effective tool to reduce arc flash hazards. + +#### 250.36(A) Location. + +The grounding impedance shall be installed between the grounding electrode conductor and the system neutral point. If a neutral point is not available, the grounding impedance shall be installed between the grounding electrode conductor and the neutral point derived from a grounding transformer. + +#### 250.36(B) Conductor Insulation and Ampacity. + +The grounded system conductor from the neutral point of the transformer or generator to its connection point to the grounding impedance shall be fully insulated. + +The grounded system conductor shall have an ampacity of not less than the maximum current rating of the grounding impedance but in no case shall the grounded system conductor be smaller than 8 AWG copper or 6 AWG aluminum or copper-clad aluminum. + +#### 250.36(C) System Grounding Connection. + +The system shall not be connected to ground except through the grounding impedance. + +> [!info] Informational Note: +> The impedance is normally selected to limit the ground-fault current to a value slightly greater than or equal to the capacitive charging current of the system. This value of impedance will also limit transient overvoltages to safe values. For guidance, refer to criteria for limiting transient overvoltages in ANSI/IEEE 142-2007, Recommended Practice for Grounding of Industrial and Commercial Power Systems. + +#### 250.36(D) Conductor Routing. + +The conductor connecting the neutral point of the transformer or generator to the grounding impedance shall be permitted to be installed in a separate raceway from the ungrounded conductors. It shall not be required to run this conductor with the phase conductors to the first system disconnecting means or overcurrent device. + +#### 250.36(E) Equipment Bonding Jumper. + +The equipment bonding jumper (the connection between the equipment grounding conductors and the grounding impedance) shall be an unspliced conductor run from the first system disconnecting means or overcurrent device to the grounded side of the grounding impedance. + +#### 250.36(F) Grounding Electrode Conductor Connection Location. + +For services or separately derived systems, the grounding electrode conductor shall be connected at any point from the grounded side of the grounding impedance to the equipment grounding connection at the service equipment or the first system disconnecting means of a separately derived system. + +#### 250.36(G) Equipment Bonding Jumper Size. + +The equipment bonding jumper shall be sized in accordance with (1) or (2) as follows: + +* (1) If the grounding electrode conductor connection is made at the grounding impedance, the equipment bonding jumper shall be sized in accordance with 250.66, based on the size of the service entrance conductors for a service or the derived phase conductors for a separately derived system. + +* (2) If the grounding electrode conductor is connected at the first system disconnecting means or overcurrent device, the equipment bonding jumper shall be sized the same as the neutral conductor in 250.36(B). + +## Part III. Grounding Electrode System and Grounding Electrode Conductor + +### 250.50 Grounding Electrode System. + +All grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrode system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A) (8) shall be instal led and used. + +> [!important] Exception: +> Concrete-encased electrodes of existing buildings or structures shall not be required to be part of the grounding electrode system where the steel reinforcing bars or rods are not accessible for use without disturbing the concrete. + +### 250.52 Grounding Electrodes. + +#### 250.52(A) Electrodes Permitted for Grounding. + +##### 250.52(A)(1) Metal Underground Water Pipe. + +A metal underground water pipe in direct contact with the earth for 3.0 m (10 ft) or more (including any metal well casing bonded to the pipe) and electrically continuous (or made electrically continuous by bonding around insulating joints or insulating pipe) to the points of connection of the grounding electrode conductor and the bonding conductor(s) or jumper(s), if installed. + +##### 250.52(A)(2) Metal In-ground Support Structure(s). + +One or more metal in-ground support structure(s) in direct contact with the earth vertically for 3.0 m (10 ft) or more, with or without concrete encasement. If multiple metal in-ground support structures are present at a building or a structure, it shall be permissible to bond only one into the grounding electrode system. + +> [!info] Informational Note: +> Metal in-ground support structures include, but are not limited to, pilings, casings, and other structural metal. + +##### 250.52(A)(3) Concrete-Encased Electrode. + +A concrete-encased electrode shall consist of at least 6.0 m (20 ft) of either (1) or (2): + +* (1) One or more bare or zinc galvanized or other electrically conductive coated steel reinforcing bars or rods of not less than 13 mm (1⁄2 in.) in diameter, installed in one continuous 6.0 m (20 ft) length, or if in multiple pieces connected together by the usual steel tie wires, exothermic welding, welding, or other effective means to create a 6.0 m (20 ft) or greater length; or + +* (2) Bare copper conductor not smaller than 4 AWG + +Metallic components shall be encased by at least 50 mm (2 in.) of concrete and shall be located horizontally within that portion of a concrete foundation or footing that is in direct contact with the earth or within vertical foundations or structural components or members that are in direct contact with the earth. If multiple concrete-encased electrodes are present at a building or structure, it shall be permissible to bond only one into the grounding electrode system. + +> [!info] Informational Note: +> Concrete installed with insulation, vapor barriers, films or similar items separating the concrete from the earth is not considered to be in "direct contact" with the earth. + +##### 250.52(A)(4) Ground Ring. + +A ground ring encircling the building or structure, in direct contact with the earth, consisting of at least 6.0 m (20 ft) of bare copper conductor not smaller than 2 AWG. + +##### 250.52(A)(5) Rod and Pipe Electrodes. + +Rod and pipe electrodes shall not be less than 2.44 m (8 ft) in length and shall consist of the following materials. + +* (a) Grounding electrodes of pipe or conduit shall not be smaller than metric designator 21 (trade size 3⁄4) and, where of steel, shall have the outer surface galvanized or otherwise metal-coated for corrosion protection. + +* (b) Rod-type grounding electrodes of stainless steel and copper or zinc coated steel shall be at least 15.87 mm (5⁄8 in.) in diameter, unless listed. + +##### 250.52(A)(6) Other Listed Electrodes. + +Other listed grounding electrodes shall be permitted. + +##### 250.52(A)(7) Plate Electrodes. + +Each plate electrode shall expose not less than 0.186 m (2 ft ) of surface to exterior soil. Electrodes of bare or electrically conductive coated iron or steel plates shall be at least 6.4 mm (1⁄4 in.) in thickness. Solid, uncoated electrodes of nonferrous metal shall be at least +1.5 mm (0.06 in.) in thickness. + +##### 250.52(A)(8) Other Local Metal Underground Systems or Structures. + +Other local metal underground systems or structures such as piping systems, underground tanks, and underground metal well casings that are not bonded to a metal water pipe. + +#### 250.52(B) Not Permitted for Use as Grounding Electrodes. + +The following systems and materials shall not be used as grounding electrodes: + +* (1) Metal underground gas piping systems + +* (2) Aluminum + +* (3) The structures and structural reinforcing steel described in 680.26(B)(1) and (B)(2) + +> [!info] Informational Note: +> See 250.104(B) for bonding requirements of gas piping. + +### 250.53 Grounding Electrode System Installation. + +#### 250.53(A) Rod, Pipe, and Plate Electrodes. + +Rod, pipe, and plate electrodes shall meet the requirements of 250.53(A)(1) through (A)(3). + +##### 250.53(A)(1) Below Permanent Moisture Level. + +If practicable, rod, pipe, and plate electrodes shall be embedded below permanent moisture level. Rod, pipe, and plate electrodes shall be free from nonconductive coatings such as paint or enamel. + +##### 250.53(A)(2) Supplemental Electrode Required. + +A single rod, pipe, or plate electrode shall be supplemented by an additional electrode of a type specified in 250.52(A)(2) through (A)(8). The supplemental electrode shall be permitted to be bonded to one of the following: + +* (1) Rod, pipe, or plate electrode + +* (2) Grounding electrode conductor + +* (3) Grounded service-entrance conductor + +* (4) Nonflexible grounded service raceway + +* (5) Any grounded service enclosure + +> [!important] Exception: +> If a single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required. + +##### 250.53(A)(3) Supplemental Electrode. + +If multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall not be less than 1.8 m (6 ft) apart. + +> [!info] Informational Note: +> The paralleling efficiency of rods is increased by spacing them twice the length of the longest rod. + +##### 250.53(A)(4) Rod and Pipe Electrodes. + +The electrode shall be installed such that at least 2.44 m (8 ft) of length is in contact with the soil. It shall be driven to a depth of not less than 2.44 m (8 ft) except that, where rock bottom is encountered, the electrode shall be driven at an oblique angle not to exceed 45 degrees from the vertical or, where rock bottom is encountered at an angle up to 45 degrees, the electrode shall be permitted to be buried in a trench that is at least 750 mm (30 in.) deep. The upper end of the electrode shall be flush with or below ground level unless the aboveground end and the grounding electrode conductor attachment are protected against physical damage as specified in 250.10. + +##### 250.53(A)(5) Plate Electrode. + +Plate electrodes shall be installed not less than 750 mm (30 in.) below the surface of the earth. + +#### 250.53(B) Electrode Spacing. + +Where more than one of the electrodes of the type specified in 250.52(A)(5) or (A)(7) are used, each electrode of one grounding system +(including that used for strike termination devices) shall not be less than 1.83 m (6 ft) from any other electrode of another grounding system. Two or more grounding electrodes that are bonded together shall be considered a single grounding electrode system. + +#### 250.53(C) Bonding Jumper. + +The bonding jumper(s) used to connect the grounding electrodes together to form the grounding electrode system shall be installed in accordance with 250.64(A), (B), and (E), shall be sized in accordance with 250.66, and shall be connected in the manner specified in +250.70. Rebar shall not be used as a conductor to interconnect the electrodes of grounding electrode systems. + +#### 250.53(D) Metal Underground Water Pipe. + +If used as a grounding electrode, metal underground water pipe shall meet the requirements of 250.53(D)(1) and (D)(2). + +##### 250.53(D)(1) Continuity. + +Continuity of the grounding path or the bonding connection to interior piping shall not rely on water meters or filtering devices and similar equipment. + +##### 250.53(D)(2) Supplemental Electrode Required. + +A metal underground water pipe shall be supplemented by an additional electrode of a type specified in 250.52(A)(2) through (A)(8). If the supplemental electrode is of the rod, pipe, or plate type, it shall comply with 250.53(A). The supplemental electrode shall be bonded to one of the following: + +* (1) Grounding electrode conductor + +* (2) Grounded service-entrance conductor + +* (3) Nonflexible grounded service raceway + +* (4) Any grounded service enclosure + +* (5) As provided by 250.32(B) + +> [!important] Exception: +> The supplemental electrode shall be permitted to be bonded to the interior metal water piping as specified in 250.68(C)(1). + +#### 250.53(E) Supplemental Electrode Bonding Connection Size. + +Where the supplemental electrode is a rod, pipe, or plate electrode, that portion of the bonding jumper that is the sole connection to the supplemental grounding electrode shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire. + +#### 250.53(F) Ground Ring. + +The ground ring shall be installed not less than 750 mm (30 in.) below the surface of the earth. + +### 250.54 Auxiliary Grounding Electrodes. + +One or more grounding electrodes shall be permitted to be connected to the equipment grounding conductors specified in 250.118 and shall not be required to comply with the electrode bonding requirements of 250.50 or 250.53(C) or the resistance requirements of 250.53(A)(2) Exception, but the earth shall not be used as an effective ground-fault current path as specified in 250.4(A)(5) and 250.4(B)(4). + +### 250.58 Common Grounding Electrode. + +Where an ac system is connected to a grounding electrode in or at a building or structure, the same electrode shall be used to ground conductor enclosures and equipment in or on that building or structure. Where separate services, feeders, or branch circuits supply a building and are required to be connected to a grounding electrode(s), the same grounding electrode(s) shall be used. + +Two or more grounding electrodes that are bonded together shall be considered as a single grounding electrode system in this sense. + +### 250.60 Use of Strike Termination Devices. + +Conductors and driven pipes, rods, or plate electrodes used for grounding strike termination devices shall not be used in lieu of the grounding electrodes required by 250.50 for grounding wiring systems and equipment. This provision shall not prohibit the required bonding together of grounding electrodes of different systems. + +> [!info] Informational Note No. 1: +> See 250.106 for the bonding requirement of the lightning protection system components to the building or structure grounding electrode system. + +> [!info] Informational Note No. 2: +> Bonding together of all separate grounding electrodes will limit voltage differences between them and between their associated wiring systems. + +### 250.62 Grounding Electrode Conductor Material. + +The grounding electrode conductor shall be of copper, aluminum, copper-clad aluminum, or the items as permitted in 250.68(C). The material selected shall be resistant to any corrosive condition existing at the installation or shall be protected against corrosion. + +Conductors of the wire type shall be solid or stranded, insulated, covered, or bare. + +### 250.64 Grounding Electrode Conductor Installation. + +Grounding electrode conductors at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system shall be installed as specified in 250.64(A) through (F). + +#### 250.64(A) Aluminum or Copper-Clad Aluminum Conductors. + +Grounding electrode conductors of bare, covered, or insulated aluminum or copper-clad aluminum shall comply with the following: + +* (1) Bare or covered conductors without an extruded polymeric covering shall not be installed where subject to corrosive conditions or be installed in direct contact with concrete. + +* (2) Terminations made within outdoor enclosures that are listed and identified for the environment shall be permitted within 450 mm (18 in.) of the bottom of the enclosure. + +* (3) Aluminum or copper-clad aluminum conductors external to buildings or equipment enclosures shall not be terminated within 450 mm (18 in.) of the earth. + +#### 250.64(B) Securing and Protection Against Physical Damage. + +Where exposed, a grounding electrode conductor or its enclosure shall be securely fastened to the surface on which it is carried. + +Grounding electrode conductors shall be permitted to be installed on or through framing members. + +##### 250.64(B)(1) Not Exposed to Physical Damage. + +A 6 AWG or larger copper or aluminum grounding electrode conductor not exposed to physical damage shall be permitted to be run along the surface of the building construction without metal covering or protection. + +##### 250.64(B)(2) Exposed to Physical Damage. + +A 6 AWG or larger copper or aluminum grounding electrode conductor exposed to physical damage shall be protected in rigid metal conduit (RMC), intermediate metal conduit (IMC), Schedule 80 rigid polyvinyl chloride conduit (PVC), reinforced thermosetting resin conduit Type XW (RTRC-XW), electrical metallic tubing (EMT), or cable armor. + +##### 250.64(B)(3) Smaller Than 6 AWG. + +Grounding electrode conductors smaller than 6 AWG shall be protected in RMC, IMC, Schedule 80 PVC, RTRC-XW, EMT, or cable armor. + +##### 250.64(B)(4) In Contact with the Earth. + +Grounding electrode conductors and grounding electrode bonding jumpers in contact with the earth shall not be required to comply with +300.5, but shall be buried or otherwise protected if subject to physical damage. + +#### 250.64(C) Continuous. + +Except as provided in 250.30(A)(5) and (A) (6), 250.30(B)(1), and 250.68(C), grounding electrode conductor(s) shall be installed in one continuous length without a splice or joint. If necessary, splices or connections shall be made as permitted in (1) through (4): + +* (1) Splicing of the wire-type grounding electrode conductor shall be permitted only by irreversible compression-type connectors listed as grounding and bonding equipment or by the exothermic welding process. + +* (2) Sections of busbars shall be permitted to be connected together to form a grounding electrode conductor. + +* (3) Bolted, riveted, or welded connections of structural metal frames of buildings or structures. + +* (4) Threaded, welded, brazed, soldered or bolted-flange connections of metal water piping. + +#### 250.64(D) Building or Structure with Multiple Disconnecting Means in Separate Enclosures. + +If a building or structure is supplied by a service or feeder with two or more disconnecting means in separate enclosures, the grounding electrode connections shall be made in accordance with 250.64(D)(1), 250.64(D)(2), or 250.64(D)(3). + +##### 250.64(D)(1) Common Grounding Electrode Conductor and Taps. + +A common grounding electrode conductor and grounding electrode conductor taps shall be installed. The common grounding electrode conductor shall be sized in accordance with 250.66, based on the sum of the circular mil area of the largest ungrounded conductor(s) of each set of conductors that supplies the disconnecting means. If the service-entrance conductors connect directly to the overhead service conductors, service drop, underground service conductors, or service lateral, the common grounding electrode conductor shall be sized in accordance with Table 250.66, note 1. + +A grounding electrode conductor tap shall extend to the inside of each disconnecting means enclosure. The grounding electrode conductor taps shall be sized in accordance with 250.66 for the largest service-entrance or feeder conductor serving the individual enclosure. The tap conductors shall be connected to the common grounding electrode conductor by one of the following methods in such a manner that the common grounding electrode conductor remains without a splice or joint: + +* (1) Exothermic welding. + +* (2) Connectors listed as grounding and bonding equipment. + +* (3) Connections to an aluminum or copper busbar not less than 6 mm thick × 50 mm wide (1⁄4 in. thick × 2 in. wide) and of sufficient length to accommodate the number of terminations necessary for the installation. The busbar shall be securely fastened and shall be installed in an accessible location. Connections shall be made by a listed connector or by the exothermic welding process. If aluminum busbars are used, the installation shall comply with 250.64(A). + +##### 250.64(D)(2) Individual Grounding Electrode Conductors. + +A grounding electrode conductor shall be connected between the grounding electrode system and one or more of the following, as applicable: + +* (1) Grounded conductor in each service equipment disconnecting means enclosure + +* (2) Equipment grounding conductor installed with the feeder + +* (3) Supply-side bonding jumper + +Each grounding electrode conductor shall be sized in accordance with 250.66 based on the service-entrance or feeder conductor(s) supplying the individual disconnecting means. + +##### 250.64(D)(3) Common Location. + +A grounding electrode conductor shall be connected in a wireway or other accessible enclosure on the supply side of the disconnecting means to one or more of the following, as applicable: + +* (1) Grounded service conductor(s) + +* (2) Equipment grounding conductor installed with the feeder + +* (3) Supply-side bonding jumper + +The connection shall be made with exothermic welding or a connector listed as grounding and bonding equipment. The grounding electrode conductor shall be sized in accordance with 250.66 based on the service-entrance or feeder conductor(s) at the common location where the connection is made. + +#### 250.64(E) Raceways and Enclosures for Grounding Electrode Conductors. + +##### 250.64(E)(1) General. + +Ferrous metal raceways, enclosures, and cable armor for grounding electrode conductors shall be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode and shall be securely fastened to the ground clamp or fitting. Ferrous metal raceways, enclosures, and cable armor shall be bonded at each end of the raceway or enclosure to the grounding electrode or grounding electrode conductor to create an electrically parallel path. Nonferrous metal raceways, enclosures, and cable armor shall not be required to be electrically continuous. + +##### 250.64(E)(2) Methods. + +Bonding shall be in compliance with 250.92(B) and ensured by one of the methods in 250.92(B)(2) through (B)(4). + +##### 250.64(E)(3) Size. + +The bonding jumper for a grounding electrode conductor(s), raceway(s), enclosure(s), or cable armor shall be the same size as, or larger than, the largest enclosed grounding electrode conductor. + +##### 250.64(E)(4) Wiring Methods. + +If a raceway is used as protection for a grounding electrode conductor, the installation shall comply with the requirements of the appropriate raceway article. + +#### 250.64(F) Installation to Electrode(s). + +Grounding electrode conductor(s) and bonding jumpers interconnecting grounding electrodes shall be installed in accordance with (1), (2), or (3). The grounding electrode conductor shall be sized for the largest grounding electrode conductor required among all the electrodes connected to it. + +* (1) The grounding electrode conductor shall be permitted to be run to any convenient grounding electrode available in the grounding electrode system where the other electrode(s), if any, is connected by bonding jumpers that are installed in accordance with 250.53(C). + +* (2) Grounding electrode conductor(s) shall be permitted to be run to one or more grounding electrode(s) individually. + +* (3) Bonding jumper(s) from grounding electrode(s) shall be permitted to be connected to an aluminum or copper busbar not less than 6 mm thick × 50 mm wide (1⁄4 in. thick × 2 in wide.) and of sufficient length to accommodate the number of terminations necessary for the installation. The busbar shall be securely fastened and shall be installed in an accessible location. + +Connections shall be made by a listed connector or by the exothermic welding process. The grounding electrode conductor shall be permitted to be run to the busbar. Where aluminum busbars are used, the installation shall comply with 250.64(A). + +### 250.66 Size of Alternating-Current Grounding Electrode Conductor. + +The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). + +Table 250.66 Grounding Electrode Conductor for Alternating-Current Systems + +%% TODO %% + +Notes: + +1. If multiple sets of service-entrance conductors connect directly to a service drop, set of overhead service conductors, set of underground service conductors, or service lateral, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. + +2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. + +3. See installation restrictions in 250.64. + +#### 250.66(A) Connections to a Rod, Pipe, or Plate Electrode(s). + +If the grounding electrode conductor or bonding jumper connected to a single or multiple rod, pipe, or plate electrode(s), or any combination thereof, as described in 250.52(A)(5) or (A)(7), does not extend on to other types of electrodes that require a larger size conductor, the grounding electrode conductor shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire. + +#### 250.66(B) Connections to Concrete-Encased Electrodes. + +If the grounding electrode conductor or bonding jumper connected to a single or multiple concrete-encased electrode(s), as described in 250.52(A)(3), does not extend on to other types of electrodes that require a larger size of conductor, the grounding electrode conductor shall not be required to be larger than 4 AWG copper wire. + +#### 250.66(C) Connections to Ground Rings. + +If the grounding electrode conductor or bonding jumper connected to a ground ring, as described in 250.52(A)(4), does not extend on to other types of electrodes that require a larger size of conductor, the grounding electrode conductor shall not be required to be larger than the conductor used for the ground ring. + +### 250.68 Grounding Electrode Conductor and Bonding Jumper Connection to Grounding Electrodes. + +The connection of a grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system and associated bonding jumper(s) shall be made as specified 250.68(A) through (C). + +#### 250.68(A) Accessibility. + +All mechanical elements used to terminate a grounding electrode conductor or bonding jumper to a grounding electrode shall be accessible. + +> [!important] Exception No. 1: +> An encased or buried connection to a concrete-encased, driven, or buried grounding electrode shall not be required to be accessible. + +> [!important] Exception No. 2: +> Exothermic or irreversible compression connections used at terminations, together with the mechanical means used to attach such terminations to fireproofed structural metal whether or not the mechanical means is reversible, shall not be required to be accessible. + +#### 250.68(B) Effective Grounding Path. + +The connection of a grounding electrode conductor or bonding jumper to a grounding electrode shall be made in a manner that will ensure an effective grounding path. Where necessary to ensure the grounding path for a metal piping system used as a grounding electrode, bonding shall be provided around insulated joints and around any equipment likely to be disconnected for repairs or replacement. Bonding jumpers shall be of sufficient length to permit removal of such equipment while retaining the integrity of the grounding path. + +#### 250.68(C) Grounding Electrode Conductor Connections. + +Grounding electrode conductors and bonding jumpers shall be permitted to be connected at the following locations and used to extend the connection to an electrode(s): + +* (1) Interior metal water piping that is electrically continuous with a metal underground water pipe electrode and is located not more than 1.52 m (5 ft) from the point of entrance to the building shall be permitted to extend the connection to an electrode(s). + +Interior metal water piping located more than 1.52 m (5 ft) from the point of entrance to the building shall not be used as a conductor to interconnect electrodes of the grounding electrode system. + +> [!important] Exception: +> In industrial, commercial, and institutional buildings or structures, if conditions of maintenance and supervision ensure that only qualified persons service the installation, interior metal water piping located more than 1.52 m (5 ft) from the point of entrance to the building shall be permitted as a bonding conductor to interconnect electrodes that are part of the grounding electrode system, or as a grounding electrode conductor, if the entire length, other than short sections passing perpendicularly through walls, floors, or ceilings, of the interior metal water pipe that is being used for the conductor is exposed. + +* (2) The metal structural frame of a building shall be permitted to be used as a conductor to interconnect electrodes that are part of the grounding electrode system, or as a grounding electrode conductor. Hold-down bolts securing the structural steel column that are connected to a concrete-encased electrode complying with 250.52(A)(3) and located in the support footing or foundation shall be permitted to connect the metal structural frame of a building or structure to the concrete encased grounding electrode. The hold-down bolts shall be connected to the concrete-encased electrode by welding, exothermic welding, the usual steel tie wires, or other approved means. + +* (3) A rebar-type concrete-encased electrode installed in accordance with 250.52(A)(3) with an additional rebar section extended from its location within the concrete foundation or footing to an accessible location that is not subject to corrosion shall be permitted for connection of grounding electrode conductors and bonding jumpers in accordance with the following: + + * a. The additional rebar section shall be continuous with the grounding electrode rebar or shall be connected to the grounding electrode rebar and connected together by the usual steel tie wires, exothermic welding, welding, or other effective means. + + * b. The rebar extension shall not be exposed to contact with the earth without corrosion protection. + + * c. Rebar shall not be used as a conductor to interconnect the electrodes of grounding electrode systems. + +### 250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes. + +The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means. Connections depending on solder shall not be used. Ground clamps shall be listed for the materials of the grounding electrode and the grounding electrode conductor and, where used on pipe, rod, or other buried electrodes, shall also be listed for direct soil burial or concrete encasement. Not more than one conductor shall be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors. One of the following methods shall be used: + +* (1) A pipe fitting, pipe plug, or other approved device screwed into a pipe or pipe fitting + +* (2) A listed bolted clamp of cast bronze or brass, or plain or malleable iron + +* (3) For indoor communications purposes only, a listed sheet metal strap-type ground clamp having a rigid metal base that seats on the electrode and having a strap of such material and dimensions that it is not likely to stretch during or after installation + +* (4) An equally substantial approved means + +## Part IV. Enclosure, Raceway, and Service Cable Connections + +### 250.80 Service Raceways and Enclosures. + +Metal enclosures and raceways for service conductors and equipment shall be connected to the grounded system conductor if the electrical system is grounded or to the grounding electrode conductor for electrical systems that are not grounded. + +> [!important] Exception: +> Metal components that are installed in a run of underground nonmetallic raceway(s) and are isolated from possible contact by a minimum cover of 450 mm (18 in.) to all parts of the metal components shall not be required to be connected to the grounded system conductor, supply side bonding jumper, or grounding electrode conductor. + +### 250.84 Underground Service Cable or Raceway. + +#### 250.84(A) Underground Service Cable. + +The sheath or armor of a continuous underground metal-sheathed or armored service cable system that is connected to the grounded system conductor on the supply side shall not be required to be connected to the grounded system conductor at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal raceway or piping. + +#### 250.84(B) Underground Service Raceway Containing Cable. + +An underground metal service raceway that contains a metal-sheathed or armored cable connected to the grounded system conductor shall not be required to be connected to the grounded system conductor at the building or structure. The sheath or armor shall be permitted to be insulated from the interior metal raceway or piping. + +### 250.86 Other Conductor Enclosures and Raceways. + +Except as permitted by 250.112(I), metal enclosures and raceways for other than service conductors shall be connected to the equipment grounding conductor. + +> [!important] Exception No. 1: +> Metal enclosures and raceways for conductors added to existing installations of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable shall not be required to be connected to the equipment grounding conductor where these enclosures or wiring methods comply with (1) through (4) as follows: + +* (1) Do not provide an equipment ground + +* (2) Are in runs of less than 7.5 m (25 ft) + +* (3) Are free from probable contact with ground, grounded metal, metal lath, or other conductive material + +* (4) Are guarded against contact by persons + +> [!important] Exception No. 2: +> Short sections of metal enclosures or raceways used to provide support or protection of cable assemblies from physical damage shall not be required to be connected to the equipment grounding conductor. + +> [!important] Exception No. 3: +> Metal components shall not be required to be connected to the equipment grounding conductor or supply-side bonding jumper where either of the following conditions exist: +> +> * (1) The metal components are installed in a run of nonmetallic raceway(s) and isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the metal components. +> +> * (2) The metal components are part of an installation of nonmetallic raceway(s) and are isolated from possible contact to any part of the metal components by being encased in not less than 50 mm (2 in.) of concrete. + +## Part V. Bonding + +### 250.90 General. + +Bonding shall be provided where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed. + +### 250.92 Services. + +#### 250.92(A) Bonding of Equipment for Services. + +The normally non-current-carrying metal parts of equipment indicated in 250.92(A)(1) and (A)(2) shall be bonded together. + +* (1) All raceways, cable trays, cablebus framework, auxiliary gutters, or service cable armor or sheath that enclose, contain, or support service conductors, except as permitted in 250.80 + +* (2) All enclosures containing service conductors, including meter fittings, boxes, or the like, interposed in the service raceway or armor + +#### 250.92(B) Method of Bonding at the Service. + +Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s). + +Electrical continuity at service equipment, service raceways, and service conductor enclosures shall be ensured by one of the following methods: + +* (1) Bonding equipment to the grounded service conductor in a manner provided in 250.8 + +* (2) Connections using threaded couplings or listed threaded hubs on enclosures if made up wrenchtight + +* (3) Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables + +* (4) Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers + +### 250.94 Bonding for Communication Systems. + +Communications system bonding terminations shall be connected in accordance with 250.94(A) or (B). + +#### 250.94(A) The Intersystem Bonding Termination Device. + +An intersystem bonding termination (IBT) for connecting intersystem bonding conductors shall be provided external to enclosures at the service equipment or metering equipment enclosure and at the disconnecting means for any additional buildings or structures. If an IBT is used, it shall comply with the following: + +* (1) Be accessible for connection and inspection. + +* (2) Consist of a set of terminals with the capacity for connection of not less than three intersystem bonding conductors. + +* (3) Not interfere with opening the enclosure for a service, building or structure disconnecting means, or metering equipment. + +* (4) At the service equipment, be securely mounted and electrically connected to an enclosure for the service equipment, to the meter enclosure, or to an exposed nonflexible metallic service raceway, or be mounted at one of these enclosures and be connected to the enclosure or to the grounding electrode conductor with a minimum 6 AWG copper conductor. + +* (5) At the disconnecting means for a building or structure, be securely mounted and electrically connected to the metallic enclosure for the building or structure disconnecting means, or be mounted at the disconnecting means and be connected to the metallic enclosure or to the grounding electrode conductor with a minimum 6 AWG copper conductor. + +* (6) The terminals shall be listed as grounding and bonding equipment. + +> [!important] Exception: +> In existing buildings or structures where any of the intersystem bonding and grounding electrode conductors required by 770.100(B)(2), 800.100(B)(2), 810.21(F)(2), 820.100, and 830.100 exist, installation of the intersystem bonding termination is not required. An accessible means external to enclosures for connecting intersystem bonding and grounding electrode conductors shall be permitted at the service equipment and at the disconnecting means for any additional buildings or structures by at least one of the following means: + +* (1) Exposed nonflexible metallic raceways + +* (2) An exposed grounding electrode conductor + +* (3) Approved means for the external connection of a copper or other corrosion-resistant bonding or grounding electrode conductor to the grounded raceway or equipment + +> [!info] Informational Note No. 1: +> A 6 AWG copper conductor with one end bonded to the grounded nonflexible metallic raceway or equipment and with 150 mm (6 in.) or more of the other end made accessible on the outside wall is an example of the approved means covered in 250.94, Exception item (3). + +> [!info] Informational Note No. 2: +> See 770.100, 800.100, 810.21, 820.100, and 830.100 for intersystem bonding and grounding requirements for conductive optical fiber cables, communications circuits, radio and television equipment, CATV circuits and network-powered broadband communications systems, respectively. + +#### 250.94(B) Other Means. + +Connections to an aluminum or copper busbar not less than 6 mm thick × 50 mm wide (1⁄4 in. thick × 2 in. wide) and of sufficient length to accommodate at least three terminations for communication systems in addition to other connections. The busbar shall be securely fastened and shall be installed in an accessible location. Connections shall be made by a listed connector. If aluminum busbars are used, the installation shall also comply with 250.64(A). + +> [!important] Exception to (A) and (B): +> Means for connecting intersystem bonding conductors are not required where communications systems are not likely to be used. + +> [!info] Informational Note: +> The use of an IBT can reduce electrical noise on communication systems. + +### 250.96 Bonding Other Enclosures. + +#### 250.96(A) General. + +Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and other metal non-current-carrying parts that are to serve as equipment grounding conductors, with or without the use of supplementary equipment grounding conductors, shall be bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them. Any nonconductive paint, enamel, or similar coating shall be removed at threads, contact points, and contact surfaces or shall be connected by means of fittings designed so as to make such removal unnecessary. + +#### 250.96(B) Isolated Grounding Circuits. + +Where installed for the reduction of electromagnetic interference on the grounding circuit, an equipment enclosure supplied by a branch circuit shall be permitted to be isolated from a raceway containing circuits supplying only that equipment by one or more listed nonmetallic raceway fittings located at the point of attachment of the raceway to the equipment enclosure. The metal raceway shall comply with this article and shall be supplemented by an internal insulated equipment grounding conductor installed in accordance with + +#### 250.146(D) to ground the equipment enclosure. + +> [!info] Informational Note: +> Use of an isolated equipment grounding conductor does not relieve the requirement for grounding the raceway system. + +### 250.97 Bonding for Over 250 Volts. + +For circuits of over 250 volts to ground, the electrical continuity of metal raceways and cables with metal sheaths that contain any conductor other than service conductors shall be ensured by one or more of the methods specified for services in 250.92(B), except for +(B)(1). + +> [!important] Exception: +> Where oversized, concentric, or eccentric knockouts are not encountered, or where a box or enclosure with concentric or eccentric knockouts is listed to provide a reliable bonding connection, the following methods shall be permitted: + +* (1) Threadless couplings and connectors for cables with metal sheaths + +* (2) Two locknuts, on rigid metal conduit or intermediate metal conduit, one inside and one outside of boxes and cabinets + +* (3) Fittings with shoulders that seat firmly against the box or cabinet, such as electrical metallic tubing connectors, flexible metal conduit connectors, and cable connectors, with one locknut on the inside of boxes and cabinets + +* (4) Listed fittings + +### 250.98 Bonding Loosely Jointed Metal Raceways. + +Expansion, expansion-deflection, or deflection fittings and telescoping sections of metal raceways shall be made electrically continuous by equipment bonding jumpers or other means. + +### 250.100 Bonding in Hazardous (Classified) Locations. + +Regardless of the voltage of the electrical system, the electrical continuity of non-current-carrying metal parts of equipment, raceways, and other enclosures in any hazardous (classified) location, as defined in 500.5, 505.5, and 506.5, shall be ensured by any of the bonding methods specified in 250.92(B)(2) through (B)(4). One or more of these bonding methods shall be used whether or not equipment grounding conductors of the wire type are installed. + +> [!info] Informational Note: +> See 501.30, 502.30, 503.30, 505.25, or 506.25 for specific bonding requirements. + +### 250.102 Grounded Conductor, Bonding Conductors, and Jumpers. + +#### 250.102(A) Material. + +Bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A bonding jumper shall be a wire, bus, screw, or similar suitable conductor. + +#### 250.102(B) Attachment. + +Bonding jumpers shall be attached in the manner specified in 250.8 for circuits and equipment and in 250.70 for grounding electrodes. + +#### 250.102(C) Size --- Supply-Side Bonding Jumper. + +##### 250.102(C)(1) Size for Supply Conductors in a Single Raceway or Cable. + +The supply-side bonding jumper shall not be smaller than specified in Table 250.102(C)(1). + +##### 250.102(C)(2) Size for Parallel Conductor Installations in Two or More Raceways or Cables. + +Where the ungrounded supply conductors are paralleled in two or more raceways or cables, and an individual supply-side bonding jumper is used for bonding these raceways or cables, the size of the supply-side bonding jumper for each raceway or cable shall be selected from Table 250.102(C)(1) based on the size of the ungrounded supply conductors in each raceway or cable. A single supplyside bonding jumper installed for bonding two or more raceways or cables shall be sized in accordance with 250.102(C)(1). + +> [!info] Informational Note No. 1: +> The term supply conductors includes ungrounded conductors that do not have overcurrent protection on their supply side and terminate at service equipment or the first disconnecting means of a separately derived system. + +> [!info] Informational Note No. 2: +> See Chapter 9, Table 8, for the circular mil area of conductors 18 AWG through 4/0 AWG. + +Table 250.102(C)(1) Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and SupplySide + +%% TODO %% + +Notes: + +1. If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor or bonding jumper shall have an area not less than 12 1⁄2 percent of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors. The grounded conductor or bonding jumper shall not be required to be larger than the largest ungrounded conductor or set of ungrounded conductors. + +2. If the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum and if the ungrounded supply conductors and the bonding jumper are of different materials (copper, aluminum, or copper-clad aluminum), the minimum size of the grounded conductor or bonding jumper shall be based on the assumed use of ungrounded supply conductors of the same material as the grounded conductor or bonding jumper and will have an ampacity equivalent to that of the installed ungrounded supply conductors. + +3. If multiple sets of service-entrance conductors are used as permitted in 230.40, Exception No. 2, or if multiple sets of ungrounded supply conductors are installed for a separately derived system, the equivalent size of the largest ungrounded supply conductor(s) shall be determined by the largest sum of the areas of the corresponding conductors of each set. + +4. If there are no service-entrance conductors, the supply conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. + +\*For the purposes of applying this table and its notes, the term bonding jumper refers to main bonding jumpers, system bonding jumpers, and supply-side bonding jumpers. + +#### 250.102(D) Size --- Equipment Bonding Jumper on Load Side of an Overcurrent Device. + +The equipment bonding jumper on the load side of an overcurrent device(s) shall be sized in accordance with 250.122. + +A single common continuous equipment bonding jumper shall be permitted to connect two or more raceways or cables if the bonding jumper is sized in accordance with 250.122 for the largest overcurrent device supplying circuits therein. + +#### 250.102(E) Installation. + +Bonding jumpers or conductors and equipment bonding jumpers shall be permitted to be installed inside or outside of a raceway or an enclosure. + +##### 250.102(E)(1) Inside a Raceway or an Enclosure. + +If installed inside a raceway, equipment bonding jumpers and bonding jumpers or conductors shall comply with the requirements of + +### 250.119 and 250.148. + +##### 250.102(E)(2) Outside a Raceway or an Enclosure. + +If installed on the outside, the length of the bonding jumper or conductor or equipment bonding jumper shall not exceed 1.8 m (6 ft) and shall be routed with the raceway or enclosure. + +> [!important] Exception: +> An equipment bonding jumper or supply-side bonding jumper longer than 1.8 m (6 ft) shall be permitted at outside pole locations for the purpose of bonding or grounding isolated sections of metal raceways or elbows installed in exposed risers of metal conduit or other metal raceway, and for bonding grounding electrodes, and shall not be required to be routed with a raceway or enclosure. + +##### 250.102(E)(3) Protection. + +Bonding jumpers or conductors and equipment bonding jumpers shall be installed in accordance with 250.64(A) and (B). + +### 250.104 Bonding of Piping Systems and Exposed Structural Metal. + +#### 250.104(A) Metal Water Piping. + +The metal water piping system shall be bonded as required in 250.104(A)(1), (A)(2), or (A)(3). + +##### 250.104(A)(1) General. + +Metal water piping system(s) installed in or attached to a building or structure shall be bonded to any of the following: + +* (1) Service equipment enclosure + +* (2) Grounded conductor at the service + +* (3) Grounding electrode conductor, if of sufficient size + +* (4) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size + +The bonding jumper(s) shall be installed in accordance with 250.64(A), 250.64(B), and 250.64(E). The points of attachment of the bonding jumper(s) shall be accessible. The bonding jumper(s) shall be sized in accordance with Table 250.102(C)(1) except that it shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum and except as permitted in 250.104(A)(2) and 250.104(A) (3). + +##### 250.104(A)(2) Buildings of Multiple Occupancy. + +In buildings of multiple occupancy where the metal water piping system(s) installed in or attached to a building or structure for the individual occupancies is metallically isolated from all other occupancies by use of nonmetallic water piping, the metal water piping system(s) for each occupancy shall be permitted to be bonded to the equipment grounding terminal of the switchgear, switchboard, or panelboard enclosure (other than service equipment) supplying that occupancy. The bonding jumper shall be sized in accordance with +250.102(D). + +##### 250.104(A)(3) Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). + +The metal water piping system(s) installed in or attached to a building or structure shall be bonded to any of the following: + +* (1) Building or structure disconnecting means enclosure where located at the building or structure + +* (2) Equipment grounding conductor run with the supply conductors + +* (3) One or more grounding electrodes used + +The bonding jumper(s) shall be sized in accordance with 250.102(D). The bonding jumper shall not be required to be larger than the largest ungrounded feeder or branch-circuit conductor supplying the building or structure. + +#### 250.104(B) Other Metal Piping. + +If installed in or attached to a building or structure, a metal piping system(s), including gas piping, that is likely to become energized shall be bonded to any of the following: + +* (1) Equipment grounding conductor for the circuit that is likely to energize the piping system + +* (2) Service equipment enclosure + +* (3) Grounded conductor at the service + +* (4) Grounding electrode conductor, if of sufficient size + +* (5) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size + +The bonding conductor(s) or jumper(s) shall be sized in accordance with Table 250.122, and equipment grounding conductors shall be sized in accordance with Table 250.122 using the rating of the circuit that is likely to energize the piping system(s). The points of attachment of the bonding jumper(s) shall be accessible. + +> [!info] Informational Note No. 1: +> Bonding all piping and metal air ducts within the premises will provide additional safety. + +> [!info] Informational Note No. 2: +> Additional information for gas piping systems can be found in NFPA 54-2018, National Fuel Gas Code, and NFPA 780-2017, Standard for the Installation of Lightning Protection Systems. + +#### 250.104(C) Structural Metal. + +Exposed structural metal that is interconnected to form a metal building frame, is not intentionally grounded or bonded, and is likely to become energized shall be bonded to any of the following: + +* (1) Service equipment enclosure + +* (2) Grounded conductor at the service + +* (3) Disconnecting means for buildings or structures supplied by a feeder or branch circuit + +* (4) Grounding electrode conductor, if of sufficient size + +* (5) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size + +The bonding conductor(s) or jumper(s) shall be sized in accordance with Table 250.102(C)(1), except that it shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum, and installed in accordance with 250.64(A), 250.64(B), and 250.64(E). The points of attachment of the bonding jumper(s) shall be accessible unless installed in compliance with 250.68(A) Exception No. 2. + +#### 250.104(D) Separately Derived Systems. + +Metal water piping systems and structural metal that is interconnected to form a building frame shall be bonded to separately derived systems in accordance with 250.104(D)(1) through 250.104(D)(3). + +##### 250.104(D)(1) Metal Water Piping System(s). + +The grounded conductor of each separately derived system shall be bonded to the nearest available point of the metal water piping system(s) in the area served by each separately derived system. This connection shall be made at the same point on the separately derived system where the grounding electrode conductor is connected. Each bonding jumper shall be sized in accordance with Table +250.102(C)(1) based on the largest ungrounded conductor of the separately derived system except that it shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum. + +> [!important] Exception No. 1: +> A separate bonding jumper to the metal water piping system shall not be required if the metal water piping system is used as the grounding electrode for the separately derived system and the water piping system is in the area served. + +> [!important] Exception No. 2: +> A separate water piping bonding jumper shall not be required if the metal frame of a building or structure is used as the grounding electrode for a separately derived system and is bonded to the metal water piping in the area served by the separately derived system. + +##### 250.104(D)(2) Structural Metal. + +If exposed structural metal that is interconnected to form the building frame exists in the area served by the separately derived system, it shall be bonded to the grounded conductor of each separately derived system. This connection shall be made at the same point on the separately derived system where the grounding electrode conductor is connected. Each bonding jumper shall be sized in accordance with Table 250.102(C)(1) based on the largest ungrounded conductor of the separately derived system except that it shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum. + +> [!important] Exception No. 1: +> A separate bonding jumper to the building structural metal shall not be required if the metal frame of a building or structure is used as the grounding electrode for the separately derived system. + +> [!important] Exception No. 2: +> A separate bonding jumper to the building structural metal shall not be required if the water piping of a building or structure is used as the grounding electrode for a separately derived system and is bonded to the building structural metal in the area served by the separately derived system. + +##### 250.104(D)(3) Common Grounding Electrode Conductor. + +If a common grounding electrode conductor is installed for multiple separately derived systems as permitted by 250.30(A)(6), and exposed structural metal that is interconnected to form the building frame or interior metal piping exists in the area served by the separately derived system, the metal piping and the structural metal member shall be bonded to the common grounding electrode conductor in the area served by the separately derived system. + +> [!important] Exception: +> A separate bonding jumper from each derived system to metal water piping and to structural metal members shall not be required if the metal water piping and the structural metal members in the area served by the separately derived system are bonded to the common grounding electrode conductor. + +### 250.106 Lightning Protection Systems. + +The lightning protection system ground terminals shall be bonded to the building or structure grounding electrode system. + +> [!info] Informational Note No. 1: +> See 250.60 for use of strike termination devices. For further information, see NFPA 780-2017, Standard for the Installation of Lightning Protection Systems, which contains detailed information on grounding, bonding, and sideflash distance from lightning protection systems. + +> [!info] Informational Note No. 2: +> Metal raceways, enclosures, frames, and other non-current-carrying metal parts of electrical equipment installed on a building equipped with a lightning protection system may require bonding or spacing from the lightning protection conductors in accordance with NFPA 780-2017, Standard for the Installation of Lightning Protection Systems. + +## Part VI. Equipment Grounding and Equipment Grounding Conductors + +### 250.109 Metal Enclosures. + +Metal enclosures shall be permitted to be used to connect bonding jumpers or equipment grounding conductors, or both, together to become a part of an effective ground-fault current path. Metal covers and metal fittings attached to these metal enclosures shall be considered as being connected to bonding jumpers or equipment grounding conductors, or both. + +### 250.110 Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods. + +Exposed, normally non-current-carrying metal parts of fixed equipment supplied by or enclosing conductors or components that are likely to become energized shall be connected to an equipment grounding conductor under any of the following conditions: + +* (1) Where within 2.5 m (8 ft) vertically or 1.5 m (5 ft) horizontally of ground or grounded metal objects and subject to contact by persons + +* (2) Where located in a wet or damp location and not isolated + +* (3) Where in electrical contact with metal + +* (4) Where in a hazardous (classified) location as covered by Articles 500 through 517 + +* (5) Where supplied by a wiring method that provides an equipment grounding conductor, except as permitted by 250.86, Exception No. 2, for short sections of metal enclosures + +* (6) Where equipment operates with any terminal at over 150 volts to ground + +> [!important] Exception No. 1: +> If exempted by special permission, the metal frame of electrically heated appliances that have the frame permanently and effectively insulated from ground shall not be required to be grounded. + +> [!important] Exception No. 2: +> Distribution apparatus, such as transformer and capacitor cases, mounted on wooden poles at a height exceeding +2.5 m (8 ft) above ground or grade level shall not be required to be grounded. + +> [!important] Exception No. 3: +> Listed equipment protected by a system of double insulation, or its equivalent, shall not be required to be connected to the equipment grounding conductor. Where such a system is employed, the equipment shall be distinctively marked. + +### 250.112 Specific Equipment Fastened in Place (Fixed) or Connected by Permanent Wiring Methods. + +Except as permitted in 250.112(F) and (I), exposed, normally non-current-carrying metal parts of equipment described in 250.112(A) through (K), and normally non-current-carrying metal parts of equipment and enclosures described in 250.112(L) and (M), shall be connected to an equipment grounding conductor, regardless of voltage. + +#### 250.112(A) Switchgear and Switchboard Frames and Structures. + +Switchgear or switchboard frames and structures supporting switching equipment, except frames of 2-wire dc switchgear or switchboards where effectively insulated from ground. + +#### 250.112(B) Pipe Organs. + +Generator and motor frames in an electrically operated pipe organ, unless effectively insulated from ground and the motor driving it. + +#### 250.112(C) Motor Frames. + +Motor frames, as provided by 430.242. + +#### 250.112(D) Enclosures for Motor Controllers. + +Enclosures for motor controllers unless attached to ungrounded portable equipment. + +#### 250.112(E) Elevators and Cranes. + +Electrical equipment for elevators and cranes. + +#### 250.112(F) Garages, Theaters, and Motion Picture Studios. + +Electrical equipment in commercial garages, theaters, and motion picture studios, except pendant lampholders supplied by circuits not over 150 volts to ground. + +#### 250.112(G) Electric Signs. + +Electric signs, outline lighting, and associated equipment as provided in 600.7. + +#### 250.112(H) Motion Picture Projection Equipment. + +Motion picture projection equipment. + +#### 250.112(I) Remote-Control, Signaling, and Fire Alarm Circuits. + +Equipment supplied by Class 1 circuits shall be grounded unless operating at less than 50 volts. Equipment supplied by Class 1 power-limited circuits, by Class 2 and Class 3 remote-control and signaling circuits, and by fire alarm circuits shall be grounded where system grounding is required by Part II or Part VIII of this article. + +#### 250.112(J) Luminaires. + +Luminaires as provided in Part V of Article 410. + +#### 250.112(K) Skid-Mounted Equipment. + +Permanently mounted electrical equipment and skids shall be connected to the equipment grounding conductor. Wire-type equipment grounding conductors shall be sized as required by 250.122. + +#### 250.112(L) Motor-Operated Water Pumps. + +Motor-operated water pumps, including the submersible type. + +#### 250.112(M) Metal Well Casings. + +Where a submersible pump is used in a metal well casing, the well casing shall be connected to the pump circuit equipment grounding conductor. + +### 250.114 Equipment Connected by Cord and Plug. + +Exposed, normally non-current-carrying metal parts of cord-and-plug-connected equipment shall be connected to the equipment grounding conductor under any of the following conditions: + +> [!important] Exception: +> Listed tools, listed appliances, and listed equipment covered in 250.114(2) through (4) shall not be required to be connected to an equipment grounding conductor where protected by a system of double insulation or its equivalent. Double insulated equipment shall be distinctively marked. + +* (1) In hazardous (classified) locations (see Articles 500 through 517) + +* (2) Where operated at over 150 volts to ground + +> [!important] Exception No. 1 to (2): +> Motors, where guarded, shall not be required to be connected to an equipment grounding conductor. + +> [!important] Exception No. 2 to (2): +> Metal frames of electrically heated appliances, exempted by special permission, shall not be required to be connected to an equipment grounding conductor, in which case the frames shall be permanently and effectively insulated from ground. + +* (3) In residential occupancies: + * a. Refrigerators, freezers, and air conditioners + * b. Clothes-washing, clothes-drying, and dish-washing machines; ranges; kitchen waste disposers; information technology equipment; sump pumps; and electrical aquarium equipment + * c. Hand-held motor-operated tools, stationary and fixed motor-operated tools, and light industrial motor-operated tools + * d. Motor-operated appliances of the following types: hedge clippers, lawn mowers, snow blowers, and wet scrubbers + * e. Portable handlamps and portable luminaires + +* (4) In other than residential occupancies: + * a. Refrigerators, freezers, and air conditioners + * b. Clothes-washing, clothes-drying, and dish-washing machines; information technology equipment; sump pumps; and electrical aquarium equipment + * c. Hand-held motor-operated tools, stationary and fixed motor-operated tools, and light industrial motor-operated tools + * d. Motor-operated appliances of the following types: hedge clippers, lawn mowers, snow blowers, and wet scrubbers + * e. Portable handlamps and portable luminaires + * f. Cord-and-plug-connected appliances used in damp or wet locations or by persons standing on the ground, standing on metal floors, or working inside of metal tanks or boilers + * g. Tools likely to be used in wet or conductive locations + +> [!important] Exception: +> Tools and portable handlamps and portable luminaires likely to be used in wet or conductive locations shall not be required to be connected to an equipment grounding conductor where supplied through an isolating transformer with an ungrounded secondary of not over 50 volts. + +### 250.116 Nonelectrical Equipment. + +The metal parts of the following nonelectrical equipment described in this section shall be connected to the equipment grounding conductor: + +* (1) Frames and tracks of electrically operated cranes and hoists + +* (2) Frames of nonelectrically driven elevator cars to which electrical conductors are attached + +* (3) Hand-operated metal shifting ropes or cables of electric elevators + +> [!info] Informational Note: +> Where extensive metal in or on buildings or structures may become energized and is subject to personal contact, adequate bonding and grounding will provide additional safety. + +### 250.118 Types of Equipment Grounding Conductors. + +The equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following: + +* (1) A copper, aluminum, or copper-clad aluminum conductor. This conductor shall be solid or stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape. + +* (2) Rigid metal conduit. + +* (3) Intermediate metal conduit. + +* (4) Electrical metallic tubing. + +* (5) Listed flexible metal conduit meeting all the following conditions: + * a. The conduit is terminated in listed fittings. + * b. The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less. + * c. The size of the conduit does not exceed metric designator 35 (trade size 11⁄4). + * d. The combined length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same effective ground-fault current path does not exceed 1.8 m (6 ft). + * e. If used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation, a wire-type equipment grounding conductor shall be installed. + +* (6) Listed liquidtight flexible metal conduit meeting all the following conditions: + * a. The conduit is terminated in listed fittings. + * b. For metric designators 12 through 16 (trade sizes 3⁄8 through 1⁄2), the circuit conductors contained in the conduit are protected by overcurrent devices rated at 20 amperes or less. + * c. For metric designators 21 through 35 (trade sizes 3⁄4 through 11⁄4), the circuit conductors contained in the conduit are protected by overcurrent devices rated not more than 60 amperes and there is no flexible metal conduit, flexible metallic tubing, or liquidtight flexible metal conduit in metric designators 12 through 16 (trade sizes 3⁄8 through 1⁄2) in the effective ground-fault current path. + * d. The combined length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same effective ground-fault current path does not exceed 1.8 m (6 ft). + * e. If used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation, a wire-type equipment grounding conductor shall be installed. + +* (7) Flexible metallic tubing where the tubing is terminated in listed fittings and meeting the following conditions: + * a. The circuit conductors contained in the tubing are protected by overcurrent devices rated at 20 amperes or less. + * b. The combined length of flexible metal conduit, flexible metallic tubing, and liquidtight flexible metal conduit in the same effective ground-fault current path does not exceed 1.8 m (6 ft). + +* (8) Armor of Type AC cable as provided in 320.108. + +* (9) The copper sheath of mineral-insulated, metal-sheathed cable Type MI. + +* (10) Type MC cable that provides an effective ground-fault current path in accordance with one or more of the following: + * a. It contains an insulated or uninsulated equipment grounding conductor in compliance with 250.118(1). + * b. The combined metallic sheath and uninsulated equipment grounding/bonding conductor of interlocked metal tape--type MC cable that is listed and identified as an equipment grounding conductor + * c. The metallic sheath or the combined metallic sheath and equipment grounding conductors of the smooth or corrugated tube-type MC cable that is listed and identified as an equipment grounding conductor + +* (11) Cable trays as permitted in 392.10 and 392.60. + +* (12) Cablebus framework as permitted in 370.60(1). + +* (13) Other listed electrically continuous metal raceways and listed auxiliary gutters. + +* (14) Surface metal raceways listed for grounding. + +> [!info] Informational Note: +> For a definition of effective ground-fault current path, see Article 100. + +### 250.119 Identification of Equipment Grounding Conductors. + +Unless required elsewhere in this Code, equipment grounding conductors shall be permitted to be bare, covered, or insulated. + +Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green or green with one or more yellow stripes except as permitted in this section. Conductors with insulation or individual covering that is green, green with one or more yellow stripes, or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors. + +> [!important] Exception No. 1: +> Power-limited Class 2 or Class 3 cables, power-limited fire alarm cables, or communications cables containing only circuits operating at less than 50 volts ac or 60 volts dc where connected to equipment not required to be grounded shall be permitted to use a conductor with green insulation or green with one or more yellow stripes for other than equipment grounding purposes. + +> [!important] Exception No. 2: +> Flexible cords having an integral insulation and jacket without an equipment grounding conductor shall be permitted to have a continuous outer finish that is green. + +> [!info] Informational Note: +> An example of a flexible cord with integral-type insulation is Type SPT-2, 2 conductor. + +> [!important] Exception No. 3: +> Conductors with green insulation shall be permitted to be used as ungrounded signal conductors where installed between the output terminations of traffic signal control and traffic signal indicating heads. Signaling circuits installed in accordance with this exception shall include an equipment grounding conductor in accordance with 250.118. Wire-type equipment grounding conductors shall be bare or have insulation or covering that is green with one or more yellow stripes. + +#### 250.119(A) Conductors 4 AWG and Larger. + +Equipment grounding conductors 4 AWG and larger shall comply with 250.119(A)(1) and (A)(2). + +* (1) An insulated or covered conductor 4 AWG and larger shall be permitted, at the time of installation, to be permanently identified as an equipment grounding conductor at each end and at every point where the conductor is accessible. + +> [!important] Exception: +> Conductors 4 AWG and larger shall not be required to be marked in conduit bodies that contain no splices or unused hubs. + +* (2) Identification shall encircle the conductor and shall be accomplished by one of the following: + * a. Stripping the insulation or covering from the entire exposed length + * b. Coloring the insulation or covering green at the termination + * c. Marking the insulation or covering with green tape or green adhesive labels at the termination + +#### 250.119(B) Multiconductor Cable. + +One or more insulated conductors in a multiconductor cable, at the time of installation, shall be permitted to be permanently identified as equipment grounding conductors at each end and at every point where the conductors are accessible by one of the following means: + +* (1) Stripping the insulation from the entire exposed length. + +* (2) Coloring the exposed insulation green. + +* (3) Marking the exposed insulation with green tape or green adhesive labels. Identification shall encircle the conductor. + +#### 250.119(C) Flexible Cord. + +Equipment grounding conductors in flexible cords shall be insulated and shall have a continuous outer finish that is either green or green with one or more yellow stripes. + +### 250.120 Equipment Grounding Conductor Installation. + +An equipment grounding conductor shall be installed in accordance with 250.120(A), (B), and (C). + +#### 250.120(A) Raceway, Cable Trays, Cable Armor, Cablebus, or Cable Sheaths. + +Where it consists of a raceway, cable tray, cable armor, cablebus framework, or cable sheath or where it is a wire within a raceway or cable, it shall be installed in accordance with the applicable provisions in this Code using fittings for joints and terminations approved for use with the type raceway or cable used. All connections, joints, and fittings shall be made tight using suitable tools. + +> [!info] Informational Note: +> See the UL guide information on FHIT systems for equipment grounding conductors installed in a raceway that are part of an electrical circuit protective system or a fire-rated cable listed to maintain circuit integrity. + +#### 250.120(B) Aluminum and Copper-Clad Aluminum Conductors. + +Equipment grounding conductors of bare, covered, or insulated aluminum or copper-clad aluminum shall comply with the following: + +* (1) Unless part of a suitable Chapter 3 cable wiring method, bare or covered conductors shall not be installed where subject to corrosive conditions or be installed in direct contact with concrete, masonry, or the earth. + +* (2) Terminations made within outdoor enclosures that are listed and identified for the environment shall be permitted within 450 mm (18 in.) of the bottom of the enclosure. + +* (3) Aluminum or copper-clad aluminum conductors external to buildings or enclosures shall not be terminated within 450 mm (18 in.) of the earth, unless terminated within a listed wire connector system. + +#### 250.120(C) Equipment Grounding Conductors Smaller Than 6 AWG. + +Where not routed with circuit conductors as permitted in 250.130(C) and 250.134(A) Exception No. 2, equipment grounding conductors smaller than 6 AWG shall be protected from physical damage by an identified raceway or cable armor unless installed within hollow spaces of the framing members of buildings or structures and where not subject to physical damage. + +### 250.121 Restricted Use of Equipment Grounding Conductors. + +#### 250.121(A) Grounding Electrode Conductor. + +An equipment grounding conductor shall not be used as a grounding electrode conductor. + +> [!important] Exception: +> A wire-type equipment grounding conductor installed in compliance with 250.6(A) and the applicable requirements for both the equipment grounding conductor and the grounding electrode conductor in Parts II, III, and VI of this article shall be permitted to serve as both an equipment grounding conductor and a grounding electrode conductor. + +#### 250.121(B) Metal Frame of Building or Structure. + +The structural metal frame of a building or structure shall not be used as an equipment grounding conductor. + +### 250.122 Size of Equipment Grounding Conductors. + +#### 250.122(A) General. + +Copper, aluminum, or copper-clad aluminum equipment grounding conductors of the wire type shall not be smaller than shown in Table +250.122. The equipment grounding conductor shall not be required to be larger than the circuit conductors supplying the equipment. If a cable tray, a raceway, or a cable armor or sheath is used as the equipment grounding conductor, as provided in 250.118 and +250.134(1), it shall comply with 250.4(A)(5) or (B)(4). + +Equipment grounding conductors shall be permitted to be sectioned within a multiconductor cable, provided the combined circular mil area complies with Table 250.122. + +#### 250.122(B) Increased in Size. + +If ungrounded conductors are increased in size for any reason other than as required in 310.15(B) or 310.15(C), wire-type equipment grounding conductors, if installed, shall be increased in size proportionately to the increase in circular mil area of the ungrounded conductors. + +> [!important] Exception: +> Equipment grounding conductors shall be permitted to be sized by a qualified person to provide an effective ground fault current path in accordance with 250.4(A)(5) or (B)(4). + +#### 250.122(C) Multiple Circuits. + +A single equipment grounding conductor shall be permitted to be installed for multiple circuits that are installed in the same raceway, cable, trench, or cable tray. It shall be sized from Table 250.122 for the largest overcurrent device protecting circuit conductors in the raceway, cable, trench, or cable tray. Equipment grounding conductors instal led in cable trays shall meet the minimum requirements of +392.10(B)(1)(c). + +#### 250.122(D) Motor Circuits. + +Equipment grounding conductors for motor circuits shall be sized in accordance with 250.122(D)(1) or (D)(2). + +##### 250.122(D)(1) General. + +The equipment grounding conductor size shall not be smaller than determined by 250.122(A)based on the rating of the branch-circuit short-circuit and ground-fault protective device. + +##### 250.122(D)(2) Instantaneous-Trip Circuit Breaker and Motor Short-Circuit Protector. + +If the overcurrent device is an instantaneous-trip circuit breaker or a motor short-circuit protector, the equipment grounding conductor shall be sized not smaller than that given by 250.122(A) using the maximum permitted rating of a dual element time-delay fuse selected for branch-circuit short-circuit and ground-fault protection in accordance with 430.52(C)(1), Exception No. 1. + +#### 250.122(E) Flexible Cord and Fixture Wire. + +The equipment grounding conductor in a flexible cord with the largest circuit conductor 10 AWG or smaller, and the equipment grounding conductor used with fixture wires of any size in accordance with 240.5, shall not be smaller than 18 AWG copper and shall not be smaller than the circuit conductors. The equipment grounding conductor in a flexible cord with a circuit conductor larger than +10 AWG shall be sized in accordance with Table 250.122. + +#### 250.122(F) Conductors in Parallel. + +For circuits of parallel conductors as permitted in 310.10(G), the equipment grounding conductor shall be installed in accordance with + +##### 250.122(F)(1) or (F) (2). + +##### 250.122(F)(1) Conductor Installations in Raceways, Auxiliary Gutters, or Cable Trays. + +* (a) Single Raceway or Cable Tray, Auxiliary Gutter, or Cable Tray. If circuit conductors are connected in parallel in the same raceway, auxiliary gutter, or cable tray, a single wire-type conductor shall be permitted as the equipment grounding conductor. + +The wire-type equipment grounding conductor shall be sized in accordance with 250.122, based on the overcurrent protective device for the feeder or branch circuit. + +* (b) Multiple Raceways. If conductors are installed in multiple raceways and are connected in parallel, a wire-type equipment grounding conductor, if used, shall be installed in each raceway and shall be connected in parallel. The equipment grounding conductor installed in each raceway shall be sized in accordance with 250.122 based on the rating of the overcurrent protective device for the feeder or branch circuit. + +* (c) Wire-Type Equipment Grounding Conductors in Cable Trays. Wire-type equipment grounding conductors installed in cable trays shall meet the minimum requirements of 392.10(B) (1)(c). + +* (d) Metal Raceways, Auxiliary Gutters, or Cable Trays. Metal raceways or auxiliary gutters in accordance with 250.118 or cable trays complying with 392.60(B) shall be permitted as the equipment grounding conductor. + +##### 250.122(F)(2) Multiconductor Cables. + +* (a) Except as provided in 250.122(F)(2)(c) for raceway or cable tray installations, the equipment grounding conductor in each multiconductor cable shall be sized in accordance with 250.122 based on the overcurrent protective device for the feeder or branch circuit. + +* (b) If circuit conductors of multiconductor cables are connected in parallel, the equipment grounding conductor(s) in each cable shall be connected in parallel. + +* (c) If multiconductor cables are paralleled in the same raceway, auxiliary gutter, or cable tray, a single equipment grounding conductor that is sized in accordance with 250.122 shall be permitted in combination with the equipment grounding conductors provided within the multiconductor cables and shall all be connected together. + +* (d) Equipment grounding conductors installed in cable trays shall meet the minimum requirements of 392.10(B) (1) (c). Cable trays complying with 392.60(B), metal raceways in accordance with 250.118, or auxiliary gutters shall be permitted as the equipment grounding conductor. + +#### 250.122(G) Feeder Taps. + +Equipment grounding conductors installed with feeder taps shall not be smaller than shown in Table 250.122 based on the rating of the overcurrent device ahead of the feeder on the supply side ahead of the tap but shall not be required to be larger than the tap conductors. + +%% TODO %% + +Note: Where necessary to comply with 250.4(A)(5) or (B)(4), the equipment grounding conductor shall be sized larger than given in this table. + +\*See installation restrictions in 250.120. + +### 250.124 Equipment Grounding Conductor Continuity. + +#### 250.124(A) Separable Connections. + +Separable connections such as those provided in drawout equipment or attachment plugs and mating connectors and receptacles shall provide for first-make, last-break of the equipment grounding conductor. First-make, last-break shall not be required where interlocked equipment, plugs, receptacles, and connectors preclude energization without grounding continuity. + +#### 250.124(B) Switches. + +No automatic cutout or switch shall be placed in the equipment grounding conductor of a premises wiring system unless the opening of the cutout or switch disconnects all sources of energy. + +### 250.126 Identification of Wiring Device Terminals. + +The terminal for the connection of the equipment grounding conductor shall be identified by one of the following: + +* (1) A green, not readily removable terminal screw with a hexagonal head. + +* (2) A green, hexagonal, not readily removable terminal nut. + +* (3) A green pressure wire connector. If the terminal for the equipment grounding conductor is not visible, the conductor entrance hole shall be marked with the word green or ground, the letters G or GR, a grounding symbol, or otherwise identified by a distinctive green color. If the terminal for the equipment grounding conductor is readily removable, the area adjacent to the terminal shall be similarly marked. + +> [!info] Informational Note: +> See Informational Note Figure 250.126. + +> [!info] Informational Note Figure 250.126 One Example of a Symbol Used to Identify the Grounding Termination Point for an Equipment Grounding Conductor. + +## Part VII. Methods of Equipment Grounding Conductor Connections + +### 250.130 Equipment Grounding Conductor Connections. + +Equipment grounding conductor connections at the source of separately derived systems shall be made in accordance with 250.30(A) (1). Equipment grounding conductor connections at service equipment shall be made as indicated in 250.130(A) or (B). For replacement of non-grounding-type receptacles with grounding-type receptacles and for branch-circuit extensions only in existing installations that do not have an equipment grounding conductor in the branch circuit, connections shall be permitted as indicated in +250.130(C). + +#### 250.130(A) For Grounded Systems. + +The connection shall be made by bonding the equipment grounding conductor to the grounded service conductor and the grounding electrode conductor. + +#### 250.130(B) For Ungrounded Systems. + +The connection shall be made by bonding the equipment grounding conductor to the grounding electrode conductor. + +#### 250.130(C) Nongrounding Receptacle Replacement or Branch Circuit Extensions. + +The equipment grounding conductor of a grounding-type receptacle or a branch-circuit extension shall be permitted to be connected to any of the following: + +* (1) Any accessible point on the grounding electrode system as described in 250.50 + +* (2) Any accessible point on the grounding electrode conductor + +* (3) The equipment grounding terminal bar within the enclosure where the branch circuit for the receptacle or branch circuit originates + +* (4) An equipment grounding conductor that is part of another branch circuit that originates from the enclosure where the branch circuit for the receptacle or branch circuit originates + +* (5) For grounded systems, the grounded service conductor within the service equipment enclosure + +* (6) For ungrounded systems, the grounding terminal bar within the service equipment enclosure + +> [!info] Informational Note: +> See 406.4(D) for the use of a ground-fault circuit-interrupting type of receptacle. + +### 250.132 Short Sections of Raceway. + +Isolated sections of metal raceway or cable armor, if required to be connected to an equipment grounding conductor, shall be connected in accordance with 250.134. + +### 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed). + +Unless connected to the grounded circuit conductor as permitted by 250.32, 250.140, and 250.142, non-current-carrying metal parts of equipment, raceways, and other enclosures, if grounded, shall be connected to an equipment grounding conductor by one of the following methods: + +* (1) By connecting to any of the equipment grounding conductors permitted by 250.118(2) through (14) + +* (2) By connecting to an equipment grounding conductor of the wire type that is contained within the same raceway, contained within the same cable, or otherwise run with the circuit conductors + +> [!important] Exception No. 1: +> As provided in 250.130(C), the equipment grounding conductor shall be permitted to be run separately from the circuit conductors. + +> [!important] Exception No. 2: +> For dc circuits, the equipment grounding conductor shall be permitted to be run separately from the circuit conductors + +> [!info] Informational Note No. 1: +> See 250.102 and 250.168 for equipment bonding jumper requirements. + +> [!info] Informational Note No. 2: +> See 400.10 for use of flexible cords and flexible cables for fixed equipment. + +### 250.136 Equipment Secured to Grounded Metal Supports. + +Electrical equipment secured to and in electrical contact with a metal rack or structure provided for its support shall be permitted to be considered as being connected to an equipment grounding conductor if the metal rack or structure is connected to an equipment grounding conductor by one of the means indicated in 250.134. + +### 250.138 Cord-and-Plug-Connected Equipment. + +non-current-carrying metal parts of cord-and-plug-connected equipment, if required to be connected to an equipment grounding conductor, shall be connected by one of the methods in 250.138(A) or (B). + +#### 250.138(A) By Means of an Equipment Grounding Conductor. + +By means of an equipment grounding conductor run with the power supply conductors in a cable assembly or flexible cord properly terminated in a grounding-type attachment plug with one fixed grounding contact. + +> [!important] Exception: +> The grounding contacting pole of grounding-type plug-in ground-fault circuit interrupters shall be permitted to be of the movable, self-restoring type on circuits operating at not over 150 volts between any two conductors or over 150 volts between any conductor and ground. + +#### 250.138(B) By Means of a Separate Flexible Wire or Strap. + +By means of a separate flexible wire or strap, insulated or bare, connected to an equipment grounding conductor, and protected as well as practicable against physical damage, where part of equipment. + +### 250.140 Frames of Ranges and Clothes Dryers. + +Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes that are part of the circuit for these appliances shall be connected to the equipment grounding conductor in the manner specified by 250.134 or +250.138. + +> [!important] Exception: +> For existing branch-circuit installations only where an equipment grounding conductor is not present in the outlet or junction box, the frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes that are part of the circuit for these appliances shall be permitted to be connected to the grounded circuit conductor if all the following conditions are met. + +* (1) The supply circuit is 120/240-volt, single-phase, 3-wire; or 208Y/120-volt derived from a 3-phase, 4-wire, wye-connected system. + +* (2) The grounded conductor is not smaller than 10 AWG copper or 8 AWG aluminum. + +* (3) The grounded conductor is insulated, or the grounded conductor is uninsulated and part of a Type SE service-entrance cable and the branch circuit originates at the service equipment. + +* (4) Grounding contacts of receptacles furnished as part of the equipment are bonded to the equipment. + +### 250.142 Use of Grounded Circuit Conductor for Grounding Equipment. + +#### 250.142(A) Supply-Side Equipment. + +A grounded circuit conductor shall be permitted to be connected to non-current-carrying metal parts of equipment, raceways, and other enclosures at any of the following locations: + +* (1) On the supply side or within the enclosure of the ac service disconnecting means + +* (2) On the supply side or within the enclosure of the main disconnecting means for separate buildings as provided in 250.32(B)(1) Exception No. 1 + +* (3) On the supply side or within the enclosure of the main disconnecting means or overcurrent devices of a separately derived system where permitted by 250.30(A)(1) + +#### 250.142(B) Load-Side Equipment. + +Except as permitted in 250.30(A) (1), 250.32(B)(1), Exception No. 1, and Part X of Article 250, a grounded circuit conductor shall not be connected to non-current-carrying metal parts of equipment on the load side of the service disconnecting means or on the load side of a separately derived system disconnecting means or the overcurrent devices for a separately derived system not having a main disconnecting means. + +> [!important] Exception No. 1: +> The frames of ranges, wall-mounted ovens, counter-mounted cooking units, and clothes dryers under the conditions permitted for existing installations by 250.140 shall be permitted to be connected to the grounded circuit conductor. + +> [!important] Exception No. 2: +> It shall be permissible to connect meter enclosures to the grounded circuit conductor on the load side of the service disconnect if all of the following conditions apply: + +* (1) Ground-fault protection of equipment is not installed. + +* (2) All meter enclosures are located immediately adjacent to the service disconnecting means. + +* (3) The size of the grounded circuit conductor is not smaller than the size specified in Table 250.122 for equipment grounding conductors. + +> [!important] Exception No. 3: +> Electrode-type boilers operating at over 1000 volts shall be grounded as required in 490.72(E)(1) and 490.74. + +### 250.144 Multiple Circuit Connections. + +Where equipment is grounded and is supplied by separate connection to more than one circuit or grounded premises wiring system, an equipment grounding conductor termination shall be provided for each such connection as specified in 250.134 and 250.138. + +### 250.146 Connecting Receptacle Grounding Terminal to an Equipment Grounding Conductor. + +An equipment bonding jumper shall be used to connect the grounding terminal of a grounding-type receptacle to a metal box that is connected to an equipment grounding conductor, except as permitted in 250.146(A) through (D). The equipment bonding jumper shall be sized in accordance with Table 250.122. + +#### 250.146(A) Surface-Mounted Box. + +If a metal box is mounted on the surface, the direct metal-to-metal contact between the device yoke or strap to the box shall be permitted to provide the required effective ground fault current path. At least one of the insulating washers shall be removed from receptacles that do not have a contact yoke or device to ensure direct metal-to-metal contact. Direct metal-to-metal contact for providing continuity applies to cover-mounted receptacles if the box and cover combination are listed as providing satisfactory continuity between the box and the receptacle. A listed exposed work cover shall be permitted to be the grounding and bonding means under both of the following conditions: + +* (1) The device is attached to the cover with at least two fasteners that are permanent (such as a rivet) or have a thread locking or screw or nut locking means + +* (2) The cover mounting holes are located on a flat non-raised portion of the cover + +#### 250.146(B) Contact Devices or Yokes. + +Contact devices or yokes designed and listed as self-grounding shall be permitted in conjunction with the supporting screws to establish equipment bonding between the device yoke and flush-type boxes. + +#### 250.146(C) Floor Boxes. + +Floor boxes designed for and listed as providing satisfactory continuity between the box and the device shall be permitted. + +#### 250.146(D) Isolated Ground Receptacles. + +Where installed for the reduction of electromagnetic interference on the equipment grounding conductor, a receptacle in which the grounding terminal is purposely insulated from the receptacle mounting means shall be permitted. The receptacle grounding terminal shall be connected to an insulated equipment grounding conductor run with the circuit conductors. This equipment grounding conductor shall be permitted to pass through one or more panelboards without a connection to the panelboard grounding terminal bar as permitted in 408.40, Exception, so as to terminate within the same building or structure directly at an equipment grounding conductor terminal of the applicable derived system or service. Where installed in accordance with this section, this equipment grounding conductor shall also be permitted to pass through boxes, wireways, or other enclosures without being connected to such enclosures. + +> [!info] Informational Note: +> Use of an isolated equipment grounding conductor does not relieve the requirement for connecting the raceway system and outlet box to an equipment grounding conductor. + +### 250.148 Continuity of Equipment Grounding Conductors and Attachment in Boxes. + +If circuit conductors are spliced within a box or terminated on equipment within or supported by a box, all wire-type equipment grounding conductor(s) associated with any of those circuit conductors shall be connected within the box or to the box in accordance with 250.8 and 250.148(A) through (D). + +> [!important] Exception: +> The equipment grounding conductor permitted in 250.146(D) shall not be required to be connected to the other equipment grounding conductors or to the box. + +#### 250.148(A) Connections and Splices. + +Connections and splices shall be made in accordance with 110.14(B) except that insulation shall not be required. + +#### 250.148(B) Equipment Grounding Conductor Continuity. + +The arrangement of grounding connections shall be such that the disconnection or the removal of a luminaire, receptacle, or other device fed from the box does not interrupt the electrical continuity of the equipment grounding conductor(s) providing an effective ground-fault current path. + +#### 250.148(C) Metal Boxes. + +A connection used for no other purpose shall be made between the metal box and the equipment grounding conductor(s) in accordance with 250.8. + +#### 250.148(D) Nonmetallic Boxes. + +One or more equipment grounding conductors brought into a nonmetallic outlet box shall be arranged such that a connection can be made to any fitting or device in that box requiring connection to an equipment grounding conductor. + +## Part VIII. Direct-Current Systems + +### 250.160 General. + +Direct-current systems shall comply with Part VIII and other sections of Article 250 not specifically intended for ac systems. + +### 250.162 Direct-Current Circuits and Systems to Be Grounded. + +Direct-current circuits and systems shall be grounded as provided for in 250.162(A) and (B). + +#### 250.162(A) Two-Wire, Direct-Current Systems. + +A 2-wire, dc system supplying premises wiring and operating at greater than 60 volts but not greater than 300 volts shall be grounded. + +> [!important] Exception No. 1: +> A system equipped with a ground detector and supplying only industrial equipment in limited areas shall not be required to be grounded where installed adjacent to or integral with the source of supply. + +> [!important] Exception No. 2: +> A rectifier-derived dc system supplied from an ac system complying with 250.20 shall not be required to be grounded. + +> [!important] Exception No. 3: +> Direct-current fire alarm circuits having a maximum current of 0.030 ampere as specified in Article 760, Part III, shall not be required to be grounded. + +#### 250.162(B) Three-Wire, Direct-Current Systems. + +The neutral conductor of all 3-wire, dc systems supplying premises wiring shall be grounded. + +### 250.164 Point of Connection for Direct-Current Systems. + +#### 250.164(A) Off-Premises Source. + +Direct-current systems to be grounded and supplied from an off-premises source shall have the grounding connection made at one or more supply stations. A grounding connection shall not be made at individual services or at any point on the premises wiring. + +#### 250.164(B) On-Premises Source. + +Where the dc system source is located on the premises, a grounding connection shall be made at one of the following: + +* (1) The source + +* (2) The first system disconnection means or overcurrent device + +* (3) By other means that accomplish equivalent system protection and that utilize equipment listed and identified for the use + +### 250.166 Size of the Direct-Current Grounding Electrode Conductor. + +The size of the grounding electrode conductor for a dc system shall be as specified in 250.166(A) and (B), except as permitted by +250.166(C) through (E). The grounding electrode conductor for a dc system shall meet the sizing requirements in this section but shall not be required to be larger than 3/0 copper or 250 kcmil aluminum. + +#### 250.166(A) Not Smaller Than the Neutral Conductor. + +Where the dc system consists of a 3-wire balancer set or a balancer winding with overcurrent protection as provided in 445.12(D), the grounding electrode conductor shall not be smaller than the neutral conductor and not smaller than 8 AWG copper or 6 AWG aluminum. + +#### 250.166(B) Not Smaller Than the Largest Conductor. + +Where the dc system is other than as in 250.166(A), the grounding electrode conductor shall not be smaller than the largest conductor supplied by the system, and not smaller than 8 AWG copper or 6 AWG aluminum. + +#### 250.166(C) Connected to Rod, Pipe, or Plate Electrodes. + +Where connected to rod, pipe, or plate electrodes as in 250.52(A)(5) or (A)(7), that portion of the grounding electrode conductor that is the sole connection to the grounding electrode shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire. + +#### 250.166(D) Connected to a Concrete-Encased Electrode. + +Where connected to a concrete-encased electrode as in 250.52(A)(3), that portion of the grounding electrode conductor that is the sole connection to the grounding electrode shall not be required to be larger than 4 AWG copper wire. + +#### 250.166(E) Connected to a Ground Ring. + +Where connected to a ground ring as in 250.52(A)(4), that portion of the grounding electrode conductor that is the sole connection to the grounding electrode shall not be required to be larger than the conductor used for the ground ring. + +### 250.167 Direct-Current Ground-Fault Detection. + +#### 250.167(A) Ungrounded Systems. + +Ground-fault detection systems shall be required for ungrounded systems. + +#### 250.167(B) Grounded Systems. + +Ground-fault detection shall be permitted for grounded systems. + +#### 250.167(C) Marking. + +Direct-current systems shall be legibly marked to indicate the grounding type at the dc source or the first disconnecting means of the system. The marking shall be of sufficient durability to withstand the environment involved. + +> [!info] Informational Note: +> NFPA 70E-2018, Standard for Electrical Safety in the Workplace, identifies four dc grounding types in detail. + +### 250.168 Direct-Current System Bonding Jumper. + +For direct-current systems that are to be grounded, an unspliced bonding jumper shall be used to connect the equipment grounding conductor(s) to the grounded conductor at the source or to the first system disconnecting means where the system is grounded. The size of the bonding jumper shall not be smaller than the system grounding electrode conductor specified in 250.166 and shall comply with 250.28(A), (B), and (C). + +### 250.169 Ungrounded Direct-Current Separately Derived Systems. + +Except as otherwise permitted in 250.34 for portable and vehicle-mounted generators, an ungrounded dc separately derived system supplied from a stand-alone power source (such as an engine--generator set) shall have a grounding electrode conductor connected to an electrode that complies with Part III of this article to provide for grounding of metal enclosures, raceways, cables, and exposed non-current-carrying metal parts of equipment. The grounding electrode conductor connection shall be to the metal enclosure at any point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices. + +The size of the grounding electrode conductor shall be in accordance with 250.166. + +## Part IX. Instruments, Meters, and Relays + +### 250.170 Instrument Transformer Circuits. + +Secondary circuits of current and potential instrument transformers shall be grounded where the primary windings are connected to circuits of 300 volts or more to ground and, where installed on or in switchgear and on switchboards, shall be grounded irrespective of voltage. + +> [!important] Exception No. 1: +> Circuits where the primary windings are connected to circuits of 1000 volts or less with no live parts or wiring exposed or accessible to other than qualified persons. + +> [!important] Exception No. 2: +> Current transformer secondaries connected in a three-phase delta configuration shall not be required to be grounded. + +### 250.172 Instrument Transformer Cases. + +Cases or frames of instrument transformers shall be connected to the equipment grounding conductor where accessible to other than qualified persons. + +> [!important] Exception: +> Cases or frames of current transformers, the primaries of which are not over 150 volts to ground and that are used exclusively to supply current to meters. + +### 250.174 Cases of Instruments, Meters, and Relays Operating at 1000 Volts or Less. + +Instruments, meters, and relays operating with windings or working parts at 1000 volts or less shall be connected to the equipment grounding conductor as specified in 250.174(A), (B), or (C). + +#### 250.174(A) Not on Switchgear or Switchboards. + +Instruments, meters, and relays not located on switchgear or switchboards operating with windings or working parts at 300 volts or more to ground, and accessible to other than qualified persons, shall have the cases and other exposed metal parts connected to the equipment grounding conductor. + +#### 250.174(B) On Switchgear or Dead-Front Switchboards. + +Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchgear or switchboards having no live parts on the front of the panels shall have the cases connected to the equipment grounding conductor. + +#### 250.174(C) On Live-Front Switchboards. + +Instruments, meters, and relays (whether operated from current and potential transformers or connected directly in the circuit) on switchboards having exposed live parts on the front of panels shall not have their cases connected to the equipment grounding conductor. Mats of insulating rubber or other suitable floor insulation shall be provided for the operator where the voltage to ground exceeds 150 volts. + +### 250.176 Cases of Instruments, Meters, and Relays --- Operating at Over 1000 Volts. + +Where instruments, meters, and relays have current-carrying parts of over 1000 volts to ground, they shall be isolated by elevation or protected by suitable barriers, grounded metal, or insulating covers or guards. Their cases shall not be connected to the equipment grounding conductor. + +> [!important] Exception: +> Cases of electrostatic ground detectors shall be permitted to be connected to an equipment grounding conductor if the internal ground segments of the instrument are connected to the instrument case and grounded and the ground detector is isolated by elevation. + +### 250.178 Instrument Equipment Grounding Conductor. + +The equipment grounding conductor for secondary circuits of instrument transformers and for instrument cases shall not be smaller than 12 AWG copper or 10 AWG aluminum. Cases of instrument transformers, instruments, meters, and relays that are mounted directly on grounded metal surfaces of enclosures or grounded metal of switchgear or switchboard panels shall be considered to be grounded, and no additional equipment grounding conductor shall be required. + +## Part X. Grounding of Systems and Circuits of over 1000 Volts + +### 250.180 General. + +If systems over 1000 volts are grounded, they shall comply with all applicable requirements of 250.1 through 250.178 and with 250.182 through 250.194, which supplement and modify the preceding sections. + +### 250.182 Derived Neutral Systems. + +A system neutral point derived from a grounding transformer shall be permitted to be used for grounding systems over 1 kV. + +### 250.184 Solidly Grounded Neutral Systems. + +Solidly grounded neutral systems shall be permitted to be either single point grounded or multigrounded neutral. + +#### 250.184(A) Neutral Conductor. + +##### 250.184(A)(1) Insulation Level. + +The minimum insulation level for neutral conductors of solidly grounded systems shall be 600 volts. + +> [!important] Exception No. 1: +> For multigrounded neutral systems as permitted in 250.184(C), bare copper conductors shall be permitted to be used for the neutral conductor of the following: + +* (1) Service-entrance conductors + +* (2) Service laterals or underground service conductors + +* (3) Direct-buried portions of feeders + +> [!important] Exception No. 2: +> Bare conductors shall be permitted for the neutral conductor of overhead portions installed outdoors. + +> [!important] Exception No. 3: +> The grounded neutral conductor shall be permitted to be a bare conductor if isolated from phase conductors and protected from physical damage. + +> [!info] Informational Note: +> See 225.4 for conductor covering where within 3.0 m (10 ft) of any building or other structure. + +##### 250.184(A)(2) Ampacity. + +The neutral conductor shall be of sufficient ampacity for the load imposed on the conductor but not less than 331⁄3 percent of the ampacity of the phase conductors. + +> [!important] Exception: +> In industrial and commercial premises under engineering supervision, it shall be permissible to size the ampacity of the neutral conductor to not less than 20 percent of the ampacity of the phase conductor. + +#### 250.184(B) Single-Point Grounded Neutral System. + +Where a single-point grounded neutral system is used, the following shall apply: + +* (1) A single-point grounded neutral system shall be permitted to be supplied from (a) or (b): + * a. A separately derived system + * b. A multigrounded neutral system with an equipment grounding conductor connected to the multigrounded neutral conductor at the source of the single-point grounded neutral system + +* (2) A grounding electrode shall be provided for the system. + +* (3) A grounding electrode conductor shall connect the grounding electrode to the system neutral conductor. + +* (4) A bonding jumper shall connect the equipment grounding conductor to the grounding electrode conductor. + +* (5) An equipment grounding conductor shall be provided to each building, structure, and equipment enclosure. + +* (6) A neutral conductor shall only be required where phase-to-neutral loads are supplied. + +* (7) The neutral conductor, where provided, shall be insulated and isolated from earth except at one location. + +* (8) An equipment grounding conductor shall be run with the phase conductors and shall comply with (a), (b), and (c): + * a. Shall not carry continuous load + * b. May be bare or insulated + * c. Shall have sufficient ampacity for fault current duty + +#### 250.184(C) Multigrounded Neutral Systems. + +Where a multigrounded neutral system is used, the following shall apply: + +* (1) The neutral conductor of a solidly grounded neutral system shall be permitted to be grounded at more than one point. Grounding shall be permitted at one or more of the following locations: + * a. Transformers supplying conductors to a building or other structure + * b. Underground circuits where the neutral conductor is exposed + * c. Overhead circuits installed outdoors + +* (2) The multigrounded neutral conductor shall be grounded at each transformer and at other additional locations by connection to a grounding electrode. + +* (3) At least one grounding electrode shall be installed and connected to the multigrounded neutral conductor every 400 m (1300 ft). + +* (4) The maximum distance between any two adjacent electrodes shall not be more than 400 m (1300 ft). + +* (5) In a multigrounded shielded cable system, the shielding shall be grounded at each cable joint that is exposed to personnel contact. + +> [!important] Exception: +> In a multipoint grounded system, a grounding electrode shall not be required to bond the neutral conductor in an uninterrupted conductor exceeding 400 m (1300 ft) if the only purpose for removing the cable jacket is for bonding the neutral conductor to a grounding electrode. + +### 250.186 Grounding Service-Supplied Alternating-Current Systems. + +#### 250.186(A) Systems with a Grounded Conductor at the Service Point. + +Where an ac system is grounded at any point and is provided with a grounded conductor at the service point, a grounded conductor(s) shall be installed and routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means's enclosure. The grounded conductor(s) shall be installed in accordance with 250.186(A)(1) through (A) (4). The size of the solidly grounded circuit conductor(s) shall be the larger of that determined by 250.184 or 250.186(A)(1) or (A)(2). + +> [!important] Exception: +> Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the grounded conductor(s) to the assembly common grounded conductor(s) terminal or bus. The assembly shall include a main bonding jumper for connecting the grounded conductor(s) to the assembly enclosure. + +##### 250.186(A)(1) Sizing for a Single Raceway or Overhead Conductor. + +The grounded conductor shall not be smaller than the required grounding electrode conductor specified in Table 250.102(C)(1) but shall not be required to be larger than the largest ungrounded service-entrance conductor(s). + +##### 250.186(A)(2) Parallel Conductors in Two or More Raceways or Overhead Conductors. + +If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or as overhead parallel conductors, the grounded conductors shall also be installed in parallel. The size of the grounded conductor in each raceway or overhead shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or overhead, as indicated in 250.186(A)(1), but not smaller than 1/0 AWG. + +> [!info] Informational Note: +> See 310.10(G) for grounded conductors connected in parallel. + +##### 250.186(A)(3) Delta-Connected Service. + +The grounded conductor of a 3-phase, 3-wire delta service shall have an ampacity not less than that of the ungrounded conductors. + +##### 250.186(A)(4) Impedance Grounded Neutral Systems. + +Impedance grounded neutral systems shall be installed in accordance with 250.187. + +#### 250.186(B) Systems Without a Grounded Conductor at the Service Point. + +Where an ac system is grounded at any point and is not provided with a grounded conductor at the service point, a supply-side bonding jumper shall be installed and routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means equipment grounding conductor terminal or bus. The supply-side bonding jumper shall be installed in accordance with 250.186(B)(1) through (B)(3). + +> [!important] Exception: +> Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the supply-side bonding jumper to the assembly common equipment grounding terminal or bus. + +##### 250.186(B)(1) Sizing for a Single Raceway or Overhead Conductor. + +The supply-side bonding jumper shall not be smaller than the required grounding electrode conductor specified in Table 250.102(C)(1) but shall not be required to be larger than the largest ungrounded service-entrance conductor(s). + +##### 250.186(B)(2) Parallel Conductors in Two or More Raceways or Overhead Conductors. + +If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or overhead conductors, the supplyside bonding jumper shall also be installed in parallel. The size of the supply-side bonding jumper in each raceway or overhead shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or overhead, as indicated in 250.186(A)(1), but not smaller than 1/0 AWG. + +##### 250.186(B)(3) Impedance Grounded Neutral Systems. + +Impedance grounded neutral systems shall be installed in accordance with 250.187. + +### 250.187 Impedance Grounded Systems. + +Impedance grounded systems in which a grounding impedance, usually a resistor, limits the ground-fault current shall be permitted where all of the following conditions are met: + +* (1) The conditions of maintenance and supervision ensure that only qualified persons service the installation. + +* (2) Ground detectors are installed on the system. + +* (3) Line-to-neutral loads are not served. + +Impedance grounded systems shall comply with 250.187(A) through (D). + +#### 250.187(A) Location. + +The grounding impedance shall be inserted in the grounding electrode conductor between the grounding electrode of the supply system and the neutral point of the supply transformer or generator. + +#### 250.187(B) Insulated. + +The grounded conductor shall be insulated for the maximum neutral voltage. + +> [!info] Informational Note: +> The maximum neutral voltage in a 3-phase wye system is 57.7 percent of the phase-to-phase voltage. + +#### 250.187(C) Grounded System Conductor Connection. + +The system grounded conductor shall not be connected to ground, except through the grounding impedance. + +#### 250.187(D) Equipment Grounding Conductors. + +Equipment grounding conductors shall be permitted to be bare and shall be electrically connected to the ground bus and grounding electrode conductor. + +### 250.188 Grounding of Systems Supplying Portable or Mobile Equipment. + +Systems supplying portable or mobile equipment over 1000 volts, other than substations installed on a temporary basis, shall comply with 250.188(A) through (F). + +#### 250.188(A) Portable or Mobile Equipment. + +Portable or mobile equipment over 1000 volts shall be supplied from a system having its neutral conductor grounded through an impedance. Where a delta-connected system over 1000 volts is used to supply portable or mobile equipment, a system neutral point and associated neutral conductor shall be derived. + +#### 250.188(B) Exposed non-Current-Carrying Metal Parts. + +Exposed non-current-carrying metal parts of portable or mobile equipment shall be connected by an equipment grounding conductor to the point at which the system neutral impedance is grounded. + +#### 250.188(C) Ground-Fault Current. + +The voltage developed between the portable or mobile equipment frame and ground by the flow of maximum ground-fault current shall not exceed 100 volts. + +#### 250.188(D) Ground-Fault Detection and Relaying. + +Ground-fault detection and relaying shall be provided to automatically de-energize any component of a system over 1000 volts that has developed a ground fault. The continuity of the equipment grounding conductor shall be continuously monitored so as to automatically de-energize the circuit of the system over 1000 volts to the portable or mobile equipment upon loss of continuity of the equipment grounding conductor. + +#### 250.188(E) Isolation. + +The grounding electrode to which the portable or mobile equipment system neutral impedance is connected shall be isolated from and separated in the ground by at least 6.0 m (20 ft) from any other system or equipment grounding electrode, and there shall be no direct connection between the grounding electrodes, such as buried pipe and fence, and so forth. + +#### 250.188(F) Trailing Cable and Couplers. + +Trailing cable and couplers of systems over 1000 volts for interconnection of portable or mobile equipment shall meet the requirements of Part III of Article 400 for cables and 490.55 for couplers. + +### 250.190 Grounding of Equipment. + +#### 250.190(A) Equipment Grounding. + +All non-current-carrying metal parts of fixed, portable, and mobile equipment and associated fences, housings, enclosures, and supporting structures shall be grounded. + +> [!important] Exception: +> Where isolated from ground and located such that any person in contact with ground cannot contact such metal parts when the equipment is energized, the metal parts shall not be required to be grounded. + +> [!info] Informational Note: +> See 250.110, Exception No. 2, for pole-mounted distribution apparatus. + +#### 250.190(B) Grounding Electrode Conductor. + +If a grounding electrode conductor connects non-current-carrying metal parts to ground, the grounding electrode conductor shall be sized in accordance with Table 250.66, based on the size of the largest ungrounded service, feeder, or branch-circuit conductors supplying the equipment. The grounding electrode conductor shall not be smaller than 6 AWG copper or 4 AWG aluminum. + +#### 250.190(C) Equipment Grounding Conductor. + +Equipment grounding conductors shall comply with 250.190(C)(1) through (C)(3). + +##### 250.190(C)(1) General. + +Equipment grounding conductors that are not an integral part of a cable assembly shall not be smaller than 6 AWG copper or 4 AWG aluminum. + +##### 250.190(C)(2) Shielded Cables. + +The metallic insulation shield encircling the current carrying conductors shall be permitted to be used as an equipment grounding conductor, if it is rated for clearing time of ground-fault current protective device operation without damaging the metallic shield. The metallic tape insulation shield and drain wire insulation shield shall not be used as an equipment grounding conductor for solidly grounded systems. + +##### 250.190(C)(3) Sizing. + +Equipment grounding conductors shall be sized in accordance with Table 250.122 based on the current rating of the fuse or the overcurrent setting of the protective relay. + +> [!info] Informational Note: +> The overcurrent rating for a circuit breaker is the combination of the current transformer ratio and the current pickup setting of the protective relay. + +### 250.191 Grounding System at Alternating-Current Substations. + +For ac substations, the grounding system shall be in accordance with Part III of Article 250. + +> [!info] Informational Note: +> For further information on outdoor ac substation grounding, see IEEE 80-2013, IEEE Guide for Safety in AC + +Substation Grounding. + +### 250.194 Grounding and Bonding of Fences and Other Metal Structures. + +Metallic fences enclosing, and other metal structures in or surrounding, a substation with exposed electrical conductors and equipment shall be grounded and bonded to limit step, touch, and transfer voltages. + +#### 250.194(A) Metal Fences. + +Where metal fences are located within 5 m (16 ft) of the exposed electrical conductors or equipment, the fence shall be bonded to the grounding electrode system with wire-type bonding jumpers as follows: + +* (1) Bonding jumpers shall be installed at each fence corner and at maximum 50 m (160 ft) intervals along the fence. + +* (2) Where bare overhead conductors cross the fence, bonding jumpers shall be installed on each side of the crossing. + +* (3) Gates shall be bonded to the gate support post, and each gate support post shall be bonded to the grounding electrode system. + +* (4) Any gate or other opening in the fence shall be bonded across the opening by a buried bonding jumper. + +* (5) The grounding grid or grounding electrode systems shall be extended to cover the swing of all gates. + +* (6) The barbed wire strands above the fence shall be bonded to the grounding electrode system. + +Alternate designs performed under engineering supervision shall be permitted for grounding or bonding of metal fences. + +> [!info] Informational Note No. 1: +> A nonconducting fence or section may provide isolation for transfer of voltage to other areas. + +> [!info] Informational Note No. 2: +> See IEEE 80-2013, IEEE Guide for Safety In AC Substation Grounding, for design and installation of fence grounding. + +#### 250.194(B) Metal Structures. + +All exposed conductive metal structures, including guy wires within 2.5 m (8 ft) vertically or 5 m (16 ft) horizontally of exposed conductors or equipment and subject to contact by persons, shall be bonded to the grounding electrode systems in the area. diff --git a/nfpa-70_300_general-requirements.md b/nfpa-70_300_general-requirements.md index 9ac62f7..48fa1ac 100644 --- a/nfpa-70_300_general-requirements.md +++ b/nfpa-70_300_general-requirements.md @@ -53,7 +53,7 @@ Metric designators and trade sizes for conduit, tubing, and associated fittings #### 300.19(A) Spacing Intervals -- Maximum. -Conductors in vertical raceways shall be supported +Conductors in vertical [[nfpa-70_100_definitions#Raceway.|raceways]] shall be supported if the vertical rise exceeds the values in Table 300.19(A). At least one support method shall be provided for each conductor at the top of the vertical raceway or as close to the top as practical. diff --git a/nfpa-70_450_transformers.md b/nfpa-70_450_transformers.md index 9af6248..019da8b 100644 --- a/nfpa-70_450_transformers.md +++ b/nfpa-70_450_transformers.md @@ -6,7 +6,7 @@ tags: - authorship/other - destiny/uncertain - exclude-from-word-count - - status/incomplete + - status/draft - topic/construction/electrical - type/media title: Article 450 Transformers and Transformer Vaults (Including Secondary Ties) @@ -19,45 +19,550 @@ title: Article 450 Transformers and Transformer Vaults (Including Secondary Ties This article covers the installation of all transformers. -Exception No. 1: -Current transformers. +> [!important] Exception No. 1: +> Current transformers. -Exception No. 2: -Dry-type transformers -that constitute a component part of other apparatus -and comply with the requirements for such apparatus. +> [!important] Exception No. 2: +> Dry-type transformers that constitute a component part of other apparatus and comply with the requirements for such apparatus. -Exception No. 3: -Transformers that are an integral part -of an X-ray, high-frequency, or electrostatic-coating apparatus. +> [!important] Exception No. 3: +> Transformers that are an integral part of an X-ray, high-frequency, or electrostatic-coating apparatus. -Exception No. 4: -Transformers used with Class 2 and Class 3 circuits -that comply with Article 725. +> [!important] Exception No. 4: +> Transformers used with Class 2 and Class 3 circuits that comply with Article 725. -Exception No. 5: -Transformers for sign and outline lighting -that comply with Article 600. +> [!important] Exception No. 5: +> Transformers for sign and outline lighting that comply with Article 600. -Exception No. 6: -Transformers for electric-discharge lighting -that comply with Article 410. +> [!important] Exception No. 6: +> Transformers for electric-discharge lighting that comply with Article 410. -Exception No. 7: -Transformers used for power-limited fire alarm circuits -that comply with Part III of Article 760. +> [!important] Exception No. 7: +> Transformers used for power-limited fire alarm circuits that comply with Part III of Article 760. -Exception No. 8: -Transformers used for research, development, or testing, -where effective arrangements are provided -to safeguard persons from contacting energized parts. +> [!important] Exception No. 8: +> Transformers used for research, development, or testing, where effective arrangements are provided to safeguard persons from contacting energized parts. -This article covers the installation of transformers -dedicated to supplying power to a fire pump installation -as modified by Article 695. +This article covers the installation of transformers dedicated to supplying power to a fire pump installation as modified by Article 695. -This article also covers the installation of transformers -in hazardous (classified) locations -as modified by Articles 501 through 504. +This article also covers the installation of transformers in hazardous (classified) locations as modified by Articles 501 through 504. - +### 450.2 Definition. + +The definitions in this section shall apply only within this article. + +Transformer. + +An individual transformer, single or polyphase, identified by a single nameplate, unless otherwise indicated in this article. + +### 450.3 Overcurrent Protection. + +Overcurrent protection of transformers shall comply with 450.3(A), (B), or (C). As used in this section, the word transformer shall mean a transformer or polyphase bank of two or more single-phase transformers operating as a unit. + +> [!info] Informational Note No. 1: +> See 240.4, 240.21, 240.100, and 240.101 for overcurrent protection of conductors. + +> [!info] Informational Note No. 2: +> Nonlinear loads can increase heat in a transformer without operating its overcurrent protective device. + +#### 450.3(A) Transformers Over 1000 Volts, Nominal. + +Overcurrent protection shall be provided in accordance with Table 450.3(A). + +#### 450.3(B) Transformers 1000 Volts, Nominal, or Less. + +Overcurrent protection shall be provided in accordance with Table 450.3(B). + +> [!important] Exception: +> Where the transformer is installed as a motor control circuit transformer in accordance with 430.72(C)(1) through (C)(5). + +Table 450.3(A) Maximum Rating or Setting of Overcurrent Protection for Transformers Over 1000 Volts +(as a Percentage of Transformer-Rated Current) + +%% TODO %% + +Notes: +1. Where the required fuse rating or circuit breaker setting does not correspond to a standard rating or setting, a higher rating or setting that does not exceed the following shall be permitted: + * a. The next higher standard rating or setting for fuses and circuit breakers 1000 volts and below, or + * b. The next higher commercially available rating or setting for fuses and circuit breakers above 1000 volts. + +1. Where secondary overcurrent protection is required, the secondary overcurrent device shall be permitted to consist of not more than six circuit breakers or six sets of fuses grouped in one location. Where multiple overcurrent devices are utilized, the total of all the device ratings shall not exceed the allowed value of a single overcurrent device. If both circuit breakers and fuses are used as the overcurrent device, the total of the device ratings shall not exceed that allowed for fuses. + +2. A supervised location is a location where conditions of maintenance and supervision ensure that only qualified persons monitor and service the transformer installation. + +3. Electronically actuated fuses that may be set to open at a specific current shall be set in accordance with settings for circuit breakers. + +4. A transformer equipped with a coordinated thermal overload protection by the manufacturer shall be permitted to have separate secondary protection omitted. + +Table 450.3(B) Maximum Rating or Setting of Overcurrent Protection for Transformers 1000 Volts and Less (as a Percentage of Transformer-Rated Current) + +%% TODO %% + +Notes: + +1. Where 125 percent of this current does not correspond to a standard rating of a fuse or nonadjustable circuit breaker, a higher rating that does not exceed the next higher standard rating shall be permitted. + +2. Where secondary overcurrent protection is required, the secondary overcurrent device shall be permitted to consist of not more than six circuit breakers or six sets of fuses grouped in one location. Where multiple overcurrent devices are utilized, the total of all the device ratings shall not exceed the allowed value of a single overcurrent device. + +3. A transformer equipped with coordinated thermal overload protection by the manufacturer and arranged to interrupt the primary current shall be permitted to have primary overcurrent protection rated or set at a current value that is not more than six times the rated current of the transformer for transformers having not more than 6 percent impedance and not more than four times the rated current of the transformer for transformers having more than 6 percent but not more than 10 percent impedance. + +#### 450.3(C) Voltage (Potential) Transformers. + +Voltage (potential) transformers installed indoors or enclosed shall be protected with primary fuses. + +> [!info] Informational Note: +> For protection of instrument circuits including voltage transformers, see 408.52. + +### 450.4 Autotransformers 1000 Volts, Nominal, or Less. + +#### 450.4(A) Overcurrent Protection. + +Each autotransformer 1000 volts, nominal, or less shall be protected by an individual overcurrent device installed in series with each ungrounded input conductor. Such overcurrent device shall be rated or set at not more than 125 percent of the rated full-load input current of the autotransformer. Where this calculation does not correspond to a standard rating of a fuse or nonadjustable circuit breaker and the rated input current is 9 amperes or more, the next higher standard rating described in 240.6 shall be permitted. An overcurrent device shall not be installed in series with the shunt winding (the winding common to both the input and the output circuits) of the autotransformer between Points A and B as shown in Figure 450.4(A). + +> [!info] Figure 450.4(A) Autotransformer. + +> [!important] Exception: +> Where the rated input current of the autotransformer is less than 9 amperes, an overcurrent device rated or set at not more than 167 percent of the input current shall be permitted. + +#### 450.4(B) Transformer Field-Connected as an Autotransformer. + +A transformer field-connected as an autotransformer shall be identified for use at elevated voltage. + +> [!info] Informational Note: +> For information on permitted uses of autotransformers, see 210.9 and 215.11. + +### 450.5 Grounding Autotransformers. + +Grounding autotransformers covered in this section are zigzag or T-connected transformers connected to 3-phase, 3-wire ungrounded systems for the purpose of creating a 3-phase, 4-wire distribution system or providing a neutral point for grounding purposes. Such transformers shall have a continuous per-phase current rating and a continuous neutral current rating. Zigzag-connected transformers shall not be installed on the load side of any system grounding connection, including those made in accordance with 250.24(B), +250.30(A)(1), or 250.32(B), Exception No. 1. + +> [!info] Informational Note: +> The phase current in a grounding autotransformer is one-third the neutral current. + +#### 450.5(A) Three-Phase, 4-Wire System. + +A grounding autotransformer used to create a 3-phase, 4-wire distribution system from a 3-phase, 3-wire ungrounded system shall conform to 450.5(A) (1) through (A)(4). + +##### 450.5(A)(1) Connections. + +The transformer shall be directly connected to the ungrounded phase conductors and shall not be switched or provided with overcurrent protection that is independent of the main switch and common-trip overcurrent protection for the 3-phase, 4-wire system. + +##### 450.5(A)(2) Overcurrent Protection. + +An overcurrent sensing device shall be provided that will cause the main switch or common-trip overcurrent protection referred to in +450.5(A)(1) to open if the load on the autotransformer reaches or exceeds 125 percent of its continuous current per-phase or neutral rating. Delayed tripping for temporary overcurrents sensed at the autotransformer overcurrent device shall be permitted for the purpose of allowing proper operation of branch or feeder protective devices on the 4-wire system. + +##### 450.5(A)(3) Transformer Fault Sensing. + +A fault-sensing system that causes the opening of a main switch or common-trip overcurrent device for the 3-phase, 4-wire system shall be provided to guard against single-phasing or internal faults. + +> [!info] Informational Note: +> This can be accomplished by the use of two subtractive-connected donut-type current transformers installed to sense and signal when an unbalance occurs in the line current to the autotransformer of 50 percent or more of rated current. + +##### 450.5(A)(4) Rating. + +The autotransformer shall have a continuous neutral-current rating that is not less than the maximum possible neutral unbalanced load current of the 4-wire system. + +#### 450.5(B) Ground Reference for Fault Protection Devices. + +A grounding autotransformer used to make available a specified magnitude of ground-fault current for operation of a ground-responsive protective device on a 3-phase, 3-wire ungrounded system shall conform to 450.5(B)(1) and (B)(2). + +##### 450.5(B)(1) Rating. + +The autotransformer shall have a continuous neutral-current rating not less than the specified ground-fault current. + +##### 450.5(B)(2) Overcurrent Protection. + +Overcurrent protection shall comply with 450.5(B)(2)(a) and (B)(2)(b). + +* (a) Operation and Interrupting Rating. An overcurrent protective device having an interrupting rating in compliance with 110.9 and that will open simultaneously all ungrounded conductors when it operates shall be applied in the grounding autotransformer branch circuit. + +* (b) Ampere Rating. The overcurrent protection shall be rated or set at a current not exceeding 125 percent of the autotransformer continuous per-phase current rating or 42 percent of the continuous-current rating of any series-connected devices in the autotransformer neutral connection. Delayed tripping for temporary overcurrents to permit the proper operation of groundresponsive tripping devices on the main system shall be permitted but shall not exceed values that would be more than the short-time current rating of the grounding autotransformer or any series connected devices in the neutral connection thereto. + +> [!important] Exception: +> For high-impedance grounded systems covered in 250.36, where the maximum ground-fault current is designed to be not more than 10 amperes, and where the grounding autotransformer and the grounding impedance are rated for continuous duty, an overcurrent device rated not more than 20 amperes that will simultaneously open all ungrounded conductors shall be permitted to be installed on the line side of the grounding autotransformer. + +#### 450.5(C) Ground Reference for Damping Transitory Overvoltages. + +A grounding autotransformer used to limit transitory overvoltages shall be of suitable rating and connected in accordance with 450.5(A)(1). + +### 450.6 Secondary Ties. + +As used in this article, a secondary tie is a circuit operating at 1000 volts, nominal, or less between phases that connects two power sources or power supply points, such as the secondaries of two transformers. The tie shall be permitted to consist of one or more conductors per phase or neutral. Conductors connecting the secondaries of transformers in accordance with 450.7 shall not be considered secondary ties. + +As used in this section, the word transformer means a transformer or a bank of transformers operating as a unit. + +#### 450.6(A) Tie Circuits. + +Tie circuits shall be provided with overcurrent protection at each end as required in Parts I, II, and VIII of Article 240. + +Under the conditions described in 450.6(A)(1) and 450.6(A)(2), the overcurrent protection shall be permitted to be in accordance with 450.6(A)(3). + +##### 450.6(A)(1) Loads at Transformer Supply Points Only. + +Where all loads are connected at the transformer supply points at each end of the tie and overcurrent protection is not provided in accordance with Parts I, II, and VIII of Article 240, the ampacity of the tie shall not be less than 67 percent of the rated secondary current of the highest rated transformer supplying the secondary tie system. + +##### 450.6(A)(2) Loads Connected Between Transformer Supply Points. + +Where load is connected to the tie at any point between transformer supply points and overcurrent protection is not provided in accordance with Parts I, II, and VIII of Article 240, the ampacity of the tie shall not be less than 100 percent of the rated secondary current of the highest rated transformer supplying the secondary tie system. + +> [!important] Exception: +> Tie circuits comprised of multiple conductors per phase shall be permitted to be sized and protected in accordance with 450.6(A)(4). + +##### 450.6(A)(3) Tie Circuit Protection. + +Under the conditions described in 450.6(A)(1) and (A)(2), both supply ends of each ungrounded tie conductor shall be equipped with a protective device that opens at a predetermined temperature of the tie conductor under short-circuit conditions. This protection shall consist of one of the following: (1) a fusible link cable connector, terminal, or lug, commonly known as a limiter, each being of a size corresponding with that of the conductor and of construction and characteristics according to the operating voltage and the type of insulation on the tie conductors or (2) automatic circuit breakers actuated by devices having comparable time--current characteristics. + +##### 450.6(A)(4) Interconnection of Phase Conductors Between Transformer Supply Points. + +Where the tie consists of more than one conductor per phase or neutral, the conductors of each phase or neutral shall comply with +450.6(A)(4)(a) or (A)(4)(b). + +* (a) Interconnected. The conductors shall be interconnected in order to establish a load supply point, and the protective device specified in 450.6(A)(3) shall be provided in each ungrounded tie conductor at this point on both sides of the interconnection. + +The means of interconnection shall have an ampacity not less than the load to be served. + +* (b) Not Interconnected. The loads shall be connected to one or more individual conductors of a paralleled conductor tie without interconnecting the conductors of each phase or neutral and without the protection specified in 450.6(A)(3) at load connection points. Where this is done, the tie conductors of each phase or neutral shall have a combined capacity ampacity of not less than 133 percent of the rated secondary current of the highest rated transformer supplying the secondary tie system, the total load of such taps shall not exceed the rated secondary current of the highest rated transformer, and the loads shall be equally divided on each phase and on the individual conductors of each phase as far as practicable. + +##### 450.6(A)(5) Tie Circuit Control. + +Where the operating voltage exceeds 150 volts to ground, secondary ties provided with limiters shall have a switch at each end that, when open, de-energizes the associated tie conductors and limiters. The current rating of the switch shall not be less than the rated current ampacity of the conductors connected to the switch. It shall be capable of interrupting its rated current, and it shall be constructed so that it will not open under the magnetic forces resulting from short-circuit current. + +#### 450.6(B) Overcurrent Protection for Secondary Connections. + +Where secondary ties are used, an overcurrent device rated or set at not more than 250 percent of the rated secondary current of the transformers shall be provided in the secondary connections of each transformer supplying the tie system. In addition, an automatic circuit breaker actuated by a reverse-current relay set to open the circuit at not more than the rated secondary current of the transformer shall be provided in the secondary connection of each transformer. + +#### 450.6(C) Grounding. + +Where the secondary tie system is grounded, each transformer secondary supplying the tie system shall be grounded in accordance with the requirements of 250.30 for separately derived systems. + +### 450.7 Parallel Operation. + +Transformers shall be permitted to be operated in parallel and switched as a unit, provided the overcurrent protection for each transformer meets the requirements of 450.3(A) for primary and secondary protective devices over 1000 volts, or 450.3(B) for primary and secondary protective devices 1000 volts or less. + +### 450.8 Guarding. + +Transformers shall be guarded as specified in 450.8(A) through (D). + +#### 450.8(A) Mechanical Protection. + +Appropriate provisions shall be made to minimize the possibility of damage to transformers from external causes where the transformers are exposed to physical damage. + +#### 450.8(B) Case or Enclosure. + +Dry-type transformers shall be provided with a noncombustible moisture-resistant case or enclosure that provides protection against the accidental insertion of foreign objects. + +#### 450.8(C) Exposed Energized Parts. + +Switches or other equipment operating at 1000 volts, nominal, or less and serving only equipment within a transformer enclosure shall be permitted to be installed in the transformer enclosure if accessible to qualified persons only. All energized parts shall be guarded in accordance with 110.27 and 110.34. + +#### 450.8(D) Voltage Warning. + +The operating voltage of exposed live parts of transformer installations shall be indicated by signs or visible markings on the equipment or structures. + +### 450.9 Ventilation. + +The ventilation shall dispose of the transformer full-load heat losses without creating a temperature rise that is in excess of the transformer rating. + +> [!info] Informational Note No. 1: +> See IEEE C57.12.00-2015, General Requirements for Liquid-Immersed Distribution, Power, and Regulating + +Transformers, and IEEE C57.12.01-2015, General Requirements for Dry-Type Distribution and Power Transformers. + +> [!info] Informational Note No. 2: +> Additional losses occur in some transformers where nonsinusoidal currents are present, resulting in increased heat in the transformer above its rating. See IEEE C57.110-2008, Recommended Practice for Establishing Liquid-Filled and Dry-Type + +Power and Distribution Transformer Capability When Supplying Nonsinusoidal Load Currents, where transformers are utilized with nonlinear loads. + +Transformers with ventilating openings shall be installed so that the ventilating openings are not blocked by walls or other obstructions. + +The required clearances shall be clearly marked on the transformer. Transformer top surfaces that are horizontal and readily accessible shall be marked to prohibit storage. + +### 450.10 Grounding. + +#### 450.10(A) Dry-Type Transformer Enclosures. + +Where separate equipment grounding conductors and supply-side bonding jumpers are installed, a terminal bar for all grounding and bonding conductor connections shall be secured inside the transformer enclosure. The terminal bar shall be bonded to the enclosure in accordance with 250.12 and shall not be installed on or over any vented portion of the enclosure. + +> [!important] Exception: +> Where a dry-type transformer is equipped with wire-type connections (leads), the grounding and bonding connections shall be permitted to be connected together using any of the methods in 250.8 and shall be bonded to the enclosure if of metal. + +#### 450.10(B) Other Metal Parts. + +Exposed non--current-carrying metal parts of transformer installations, including fences, guards, and so forth, shall be grounded and bonded under the conditions and in the manner specified for electrical equipment and other exposed metal parts in Parts V, VI, and VII of Article 250. + +### 450.11 Marking. + +#### 450.11(A) General. + +Each transformer shall be provided with a nameplate giving the following information: + +* (1) Name of manufacturer + +* (2) Rated kilovolt-amperes + +* (3) Frequency + +* (4) Primary and secondary voltage + +* (5) Impedance of transformers 25 kVA and larger + +* (6) Required clearances for transformers with ventilating openings + +* (7) Amount and kind of insulating liquid where used + +* (8) For dry-type transformers, temperature class for the insulation system + +#### 450.11(B) Source Marking. + +A transformer shall be permitted to be supplied at the marked secondary voltage, provided that the installation is in accordance with the manufacturer's instructions. + +### 450.12 Terminal Wiring Space. + +The minimum wire-bending space at fixed, 1000-volt and below terminals of transformer line and load connections shall be as required in 312.6. Wiring space for pigtail connections shall conform to Table 314.16(B). + +### 450.13 Accessibility. + +All transformers and transformer vaults shall be readily accessible to qualified personnel for inspection and maintenance or shall meet the requirements of 450.13(A) or 450.13(B). + +#### 450.13(A) Open Installations. + +Dry-type transformers 1000 volts, nominal, or less, located in the open on walls, columns, or structures, shall not be required to be readily accessible. + +#### 450.13(B) Hollow Space Installations. + +Dry-type transformers 1000 volts, nominal, or less and not exceeding 50 kVA shall be permitted in hollow spaces of buildings not permanently closed in by structure, provided they meet the ventilation requirements of 450.9 and separation from combustible materials requirements of 450.21(A). Transformers so installed shall not be required to be readily accessible. + +### 450.14 Disconnecting Means. + +Transformers, other than Class 2 or Class 3 transformers, shall have a disconnecting means located either in sight of the transformer or in a remote location. Where located in a remote location, the disconnecting means shall be lockable open in accordance with 110.25, and its location shall be field marked on the transformer. + +## Part II. Specific Provisions Applicable to Different Types of Transformers + +### 450.21 Dry-Type Transformers Installed Indoors. + +#### 450.21(A) Not Over 1121⁄ 2 kVA. + +Dry-type transformers installed indoors and rated 1121⁄ 2 kVA or less shall have a separation of at least 300 mm (12 in.) from combustible material unless separated from the combustible material by a fire-resistant, heat-insulated barrier. + +> [!important] Exception: +> This rule shall not apply to transformers rated for 1000 volts, nominal, or less that are completely enclosed, except for ventilating openings. + +#### 450.21(B) Over 1121⁄ 2 kVA. + +Individual dry-type transformers of more than 1121⁄ 2 kVA rating shall be installed in a transformer room of fire-resistant construction having a minimum fire rating of 1 hour. + +> [!important] Exception No. 1: +> Transformers with Class 155 or higher insulation systems and separated from combustible material by a fire-resistant, heat-insulating barrier or by not less than 1.83 m (6 ft) horizontally and 3.7 m (12 ft) vertically. + +> [!important] Exception No. 2: +> Transformers with Class 155 or higher insulation systems and completely enclosed except for ventilating openings. + +> [!info] Informational Note: +> See ASTM E119-18a, Standard Test Methods for Fire Tests of Building Construction and Materials. + +#### 450.21(C) Over 35,000 Volts. + +Dry-type transformers rated over 35,000 volts shall be installed in a vault complying with Part III of this article. + +### 450.22 Dry-Type Transformers Installed Outdoors. + +Dry-type transformers installed outdoors shall have a weatherproof enclosure. + +Transformers exceeding 1121⁄ 2 kVA shall not be located within 300 mm (12 in.) of combustible materials of buildings unless the transformer has Class 155 insulation systems or higher and is completely enclosed except for ventilating openings. + +### 450.23 Less-Flammable Liquid-Insulated Transformers. + +Transformers insulated with listed less-flammable liquids that have a fire point of not less than 300°C shall be permitted to be instal led in accordance with 450.23(A) or 450.23(B). + +#### 450.23(A) Indoor Installations. + +Indoor installations shall be permitted in accordance with one of the following: + +* (1) In Type I or Type II buildings, in areas where all of the following requirements are met: + * a. The transformer is rated 35,000 volts or less. + * b. No combustible materials are stored. + * c. A liquid confinement area is provided. + * d. The installation complies with all the restrictions provided for in the listing of the liquid. + +> [!info] Informational Note: +> Such restrictions can include, but are not limited to, maximum pressure of the tank, use of a pressure relief valve, appropriate fuse types, and proper sizing of overcurrent protection. + +* (2) If an automatic fire extinguishing system and a liquid confinement area is present, provided the transformer is rated 35,000 volts or less + +* (3) If the installation complies with 450.26 + +#### 450.23(B) Outdoor Installations. + +Less-flammable liquid-filled transformers shall be permitted to be installed outdoors, attached to, adjacent to, or on the roof of buildings, if instal led in accordance with (1) or (2). + +* (1) For Type I and Type II buildings, the installation shall comply with all the restrictions provided for in the listing of the liquid. + +> [!info] Informational Note No. 1: +> Installations adjacent to combustible material, fire escapes, or door and window openings can require additional safeguards such as those listed in 450.27. + +> [!info] Informational Note No. 2: +> Such restrictions can include, but are not limited to: maximum pressure of the tank, use of a pressure relief valve, appropriate fuse types, and proper sizing of overcurrent protection. + +* (2) In accordance with 450.27. + +> [!info] Informational Note No. 1: +> As used in this section, Type I and Type II buildings refers to Type I and Type II building construction as defined in NFPA 220-2018, Standard on Types of Building Construction. Combustible materials refers to those materials not classified as noncombustible or limited-combustible as defined in NFPA 220-2018, Standard on Types of Building Construction. + +> [!info] Informational Note No. 2: +> See definition of Listed in Article 100. + +### 450.24 Nonflammable Fluid-Insulated Transformers. + +Transformers insulated with a dielectric fluid identified as nonflammable shall be permitted to be installed indoors or outdoors. Such transformers installed indoors and rated over 35,000 volts shall be installed in a vault. Such transformers installed indoors shall be furnished with a liquid confinement area and a pressure-relief vent. The transformers shall be furnished with a means for absorbing any gases generated by arcing inside the tank, or the pressure-relief vent shall be connected to a chimney or flue that will carry such gases to an environmentally safe area. + +> [!info] Informational Note: +> Safety may be increased if fire hazard analyses are performed for such transformer installations. + +For the purposes of this section, a nonflammable dielectric fluid is one that does not have a flash point or fire point and is not flammable in air. + +### 450.25 Askarel-Insulated Transformers Installed Indoors. + +Askarel-insulated transformers installed indoors and rated over 25 kVA shall be furnished with a pressure-relief vent. Where installed in a poorly ventilated place, they shall be furnished with a means for absorbing any gases generated by arcing inside the case, or the pressure-relief vent shall be connected to a chimney or flue that carries such gases outside the building. Askarel-insulated transformers rated over 35,000 volts shall be installed in a vault. + +### 450.26 Oil-Insulated Transformers Installed Indoors. + +Oil-insulated transformers installed indoors shall be installed in a vault constructed as specified in Part III of this article. + +> [!important] Exception No. 1: +> Where the total capacity does not exceed 1121⁄ 2 kVA, the vault specified in Part III of this article shall be permitted to be constructed of reinforced concrete that is not less than 100 mm (4 in.) thick. + +> [!important] Exception No. 2: +> Where the nominal voltage does not exceed 1000, a vault shall not be required if suitable arrangements are made to prevent a transformer oil fire from igniting other materials and the total capacity in one location does not exceed 10 kVA in a section of the building classified as combustible or 75 kVA where the surrounding structure is classified as fire-resistant construction. + +> [!important] Exception No. 3: +> Electric furnace transformers that have a total rating not exceeding 75 kVA shall be permitted to be installed without a vault in a building or room of fire-resistant construction, provided suitable arrangements are made to prevent a transformer oil fire from spreading to other combustible material. + +> [!important] Exception No. 4: +> A transformer that has a total rating not exceeding 75 kVA and a supply voltage of 1000 volts or less that is an integral part of charged-particle-accelerating equipment shall be permitted to be installed without a vault in a building or room of noncombustible or fire-resistant construction, provided suitable arrangements are made to prevent a transformer oil fire from spreading to other combustible material. + +> [!important] Exception No. 5: +> Transformers shall be permitted to be installed in a detached building that does not comply with Part III of this article if neither the building nor its contents present a fire hazard to any other building or property, and if the building is used only in supplying electric service and the interior is accessible only to qualified persons. + +> [!important] Exception No. 6: +> Oil-insulated transformers shall be permitted to be used without a vault in portable and mobile surface mining equipment (such as electric excavators) if each of the following conditions is met: + +* (1) Provision is made for draining leaking fluid to the ground. + +* (2) Safe egress is provided for personnel. + +* (3) A minimum 6-mm (1⁄ 4-in.) steel barrier is provided for personnel protection. + +### 450.27 Oil-Insulated Transformers Installed Outdoors. + +Combustible material, combustible buildings, and parts of buildings, fire escapes, and door and window openings shall be safeguarded from fires originating in oil-insulated transformers installed on roofs, attached to or adjacent to a building or combustible material. + +In cases where the transformer installation presents a fire hazard, one or more of the following safeguards shall be applied according to the degree of hazard involved: + +* (1) Space separations + +* (2) Fire-resistant barriers + +* (3) Automatic fire suppression systems + +* (4) Enclosures that confine the oil of a ruptured transformer tank + +Oil enclosures shall be permitted to consist of fire-resistant dikes, curbed areas or basins, or trenches filled with coarse, crushed stone. + +Oil enclosures shall be provided with trapped drains where the exposure and the quantity of oil involved are such that removal of oil is important. + +> [!info] Informational Note: +> For additional information on transformers installed on poles or structures or under ground, see ANSI/IEEE C22017, + +National Electrical Safety Code. + +### 450.28 Modification of Transformers. + +When modifications are made to a transformer in an existing installation that change the type of the transformer with respect to Part II of this article, such transformer shall be marked to show the type of insulating liquid installed, and the modified transformer installation shall comply with the applicable requirements for that type of transformer. + +## Part III. Transformer Vaults + +### 450.41 Location. + +Vaults shall be located where they can be ventilated to the outside air without using flues or ducts wherever such an arrangement is practicable. + +### 450.42 Walls, Roofs, and Floors. + +The walls and roofs of vaults shall be constructed of materials that have approved structural strength for the conditions with a minimum fire resistance of 3 hours. The floors of vaults in contact with the earth shall be of concrete that is not less than 100 mm (4 in.) thick, but, where the vault is constructed with a vacant space or other stories below it, the floor shall have approved structural strength for the load imposed thereon and a minimum fire resistance of 3 hours. For the purposes of this section, studs and wallboard construction shall not be permitted. + +> [!important] Exception: +> Where transformers are protected with automatic sprinkler, water spray, carbon dioxide, or halon, construction of 1-hour rating shall be permitted. + +> [!info] Informational Note No. 1: +> For additional information, see ASTM E119-18a, Methods for Fire Tests of Building Construction and Materials. + +> [!info] Informational Note No. 2: +> A typical 3-hour construction is 150 mm (6 in.) thick reinforced concrete. + +### 450.43 Doorways. + +Vault doorways shall be protected in accordance with 450.43(A), (B), and (C). + +#### 450.43(A) Type of Door. + +Each doorway leading into a vault from the building interior shall be provided with a tight-fitting door that has a minimum fire rating of +3 hours. The authority having jurisdiction shall be permitted to require such a door for an exterior wall opening where conditions warrant. + +> [!important] Exception: +> Where transformers are protected with automatic sprinkler, water spray, carbon dioxide, or halon, construction of 1-hour rating shall be permitted. + +> [!info] Informational Note: +> For additional information, see NFPA 80-2016, Standard for Fire Doors and Other Opening Protectives. + +#### 450.43(B) Sills. + +A door sill or curb that is of an approved height that will confine the oil from the largest transformer within the vault shall be provided, and in no case shall the height be less than 100 mm (4 in.). + +#### 450.43(C) Locks. + +Doors shall be equipped with locks, and doors shall be kept locked, with access being allowed only to qualified persons. Personnel doors shall open in the direction of egress and be equipped with listed fire exit hardware. + +### 450.45 Ventilation Openings. + +Where required by 450.9, openings for ventilation shall be provided in accordance with 450.45(A) through (F). + +#### 450.45(A) Location. + +Ventilation openings shall be located as far as possible from doors, windows, fire escapes, and combustible material. + +#### 450.45(B) Arrangement. + +A vault ventilated by natural circulation of air shall be permitted to have roughly half of the total area of openings required for ventilation in one or more openings near the floor and the remainder in one or more openings in the roof or in the sidewalls near the roof, or all of the area required for ventilation shall be permitted in one or more openings in or near the roof. + +#### 450.45(C) Size. + +For a vault ventilated by natural circulation of air to an outdoor area, the combined net area of all ventilating openings, after deducting the area occupied by screens, gratings, or louvers, shall not be less than 1900 mm (3 in.) per kVA of transformer capacity in service, and in no case shall the net area be less than 0.1 m (1 ft) for any capacity under 50 kVA. + +#### 450.45(D) Covering. + +Ventilation openings shall be covered with durable gratings, screens, or louvers, according to the treatment required in order to avoid unsafe conditions. + +#### 450.45(E) Dampers. + +All ventilation openings to the indoors shall be provided with automatic closing fire dampers that operate in response to a vault fire. + +Such dampers shall possess a standard fire rating of not less than 1 1⁄2 hours. + +> [!info] Informational Note: +> See ANSI/UL 555-2016, Standard for Fire Dampers. + +#### 450.45(F) Ducts. + +Ventilating ducts shall be constructed of fire-resistant material. + +### 450.46 Drainage. + +Where practicable, vaults containing more than 100 kVA transformer capacity shall be provided with a drain or other means that will carry off any accumulation of oil or water in the vault unless local conditions make this impracticable. The floor shall be pitched to the drain where provided. + +### 450.47 Water Pipes and Accessories. + +Any pipe or duct system foreign to the electrical installation shall not enter or pass through a transformer vault. Piping or other facilities provided for vault fire protection, or for transformer cooling, shall not be considered foreign to the electrical installation. + +### 450.48 Storage in Vaults. + +Materials shall not be stored in transformer vaults. diff --git a/nfpa-70_national-electric-code.md b/nfpa-70_national-electric-code.md index 9e8f23f..68bae21 100644 --- a/nfpa-70_national-electric-code.md +++ b/nfpa-70_national-electric-code.md @@ -31,7 +31,7 @@ title: "NFPA 70: National Electric Code" * [[nfpa-70_230|230 Services]] * [[nfpa-70_240|240 Overcurrent Protection]] * [[nfpa-70_242|242 Overvoltage Protection]] -* [[nfpa-70_250|250 Grounding and Bonding]] +* [[nfpa-70_250_grounding-and-bonding|250 Grounding and Bonding]] ## Chapter 3 Wiring Methods and Materials diff --git a/twisted-pair-cable.md b/twisted-pair-cable.md new file mode 100644 index 0000000..f44e0d3 --- /dev/null +++ b/twisted-pair-cable.md @@ -0,0 +1,35 @@ +--- +id: +aliases: [] +tags: [] +title: Twisted-Pair Cable +--- +# Twisted Pair Cable + +## Scope + +This note concerns [twisted pair cabling](https://en.wikipedia.org/wiki/Twisted_pair), +but only as relevant to electrical estimating. + +Unless noted otherwise, +_twisted pair cable_ as used in this note refers to +4-pair Category 5 and Category 6 cable constructions. + +It should be noted for accuracy +that the standards for Category 5 and Category 6 +do not exclude cables of more than 4 pairs. + +## Construction + +| Name | Bandwidth | +| ------ | --------- | +| Cat 5 | 100 MHz | +| Cat 5e | 100 MHz | +| Cat 6 | 250 MHz | +| Cat 6A | 500 MHz | + +## Connectors + +8 position 8 contact (8P8C) modular connectors +male --- "plug" +female --- "jack" or "socket" \ No newline at end of file diff --git a/voltage-drop.md b/voltage-drop.md index 0dc968d..08e7788 100644 --- a/voltage-drop.md +++ b/voltage-drop.md @@ -18,15 +18,16 @@ title: Voltage Drop ## Step 1: Effective Impedance $Z$ +The formula for effective impedance $Z$ is given by + $$ Z = R \cos(\theta) + X \sin(\theta) $$ where -* $Z$ = Effective impedance * $R$ = AC resistance * $X$ = Reactance -* $\theta$ = Power factor angle = $\arccos(PF)$ +* $\theta$ = Power factor angle = $\arccos(\text{PF})$ ### Parallel Runs @@ -85,7 +86,7 @@ $$ ### 3-Phase Loads $$ -\Delta V_{3\phi} = \sqrt{3} \times \left( I \times Z \times L ) +\Delta V_{3\phi} = \sqrt{3} ( I \times Z \times L ) $$ where