@@ -37,11 +37,11 @@ for a [[ibc-construction-types#5-Over-1 Construction|podium]] construction.
|
||||
> * Concealed: NM/SER
|
||||
> * Exposed to Structure: PVC OH
|
||||
|
||||
<!--
|
||||
%%
|
||||
This needs reworking.
|
||||
I know PVC is preferable to MC in the case of feeders, subfeeds, and possibly home runs,
|
||||
but I think they swap for branch.
|
||||
-->
|
||||
%%
|
||||
|
||||
## Standard Indoor Wiring Methods
|
||||
|
||||
@@ -50,9 +50,8 @@ NM/SER < PVC in Slab < MC < EMT-SS < EMT-Comp
|
||||
### NM/SER Overhead
|
||||
|
||||
Nonmetallic-sheathed cables are combustible,
|
||||
so not permissible in Non-Combustible (Type I, II) constructions.
|
||||
|
||||
See [[ibc-construction-types]] for more info.
|
||||
so not permissible in Type [[ibc-construction-types#Type I Fire Resistive Non-Combustible|I]],
|
||||
[[ibc-construction-types#Type II Non-Combustible|II]] constructions.
|
||||
|
||||
#### Concealment
|
||||
|
||||
@@ -81,8 +80,8 @@ See [[pdi-breakdowns#Garage]] for more info.
|
||||
|
||||
#### Slab Thickness
|
||||
|
||||
Conduits may not be routed through slabs of thickness
|
||||
less than 3 times the outer diameter of the conduit.
|
||||
Conduits may only be routed through slabs of thickness
|
||||
at least 3 times the outer diameter of the conduit.
|
||||
|
||||
| Conduit Size | Minimum Slab Thickness (in) |
|
||||
| ------------:| ---------------------------:|
|
||||
@@ -133,8 +132,8 @@ _Market Type = Assisted Living:_ MC-AP may be required.
|
||||
Cable type wiring methods (MC, NM, SE)
|
||||
may only be used where they will be concealed from view.
|
||||
|
||||
Exception:
|
||||
Temporary provisions for unfinished spaces (e.g. core and shell retail)
|
||||
> [!important] Exception:
|
||||
> Temporary provisions for unfinished spaces (e.g. core and shell retail)
|
||||
|
||||
#### Multi-Circuit Homeruns
|
||||
|
||||
@@ -145,6 +144,7 @@ Temporary provisions for unfinished spaces (e.g. core and shell retail)
|
||||
|
||||
### EMT Overhead
|
||||
|
||||
Set-screw fittings are [[best-practice]]
|
||||
Set-screw fittings may not be acceptable.
|
||||
|
||||
> [!info]
|
||||
|
||||