vault backup: 2025-12-04 17:06:30

This commit is contained in:
2025-12-04 17:06:30 -05:00
parent a538caab43
commit 8c9e0e0b6b
42 changed files with 878 additions and 243 deletions
+9 -9
View File
@@ -37,11 +37,11 @@ for a [[ibc-construction-types#5-Over-1 Construction|podium]] construction.
> * Concealed: NM/SER
> * Exposed to Structure: PVC OH
<!--
%%
This needs reworking.
I know PVC is preferable to MC in the case of feeders, subfeeds, and possibly home runs,
but I think they swap for branch.
-->
%%
## Standard Indoor Wiring Methods
@@ -50,9 +50,8 @@ NM/SER < PVC in Slab < MC < EMT-SS < EMT-Comp
### NM/SER Overhead
Nonmetallic-sheathed cables are combustible,
so not permissible in Non-Combustible (Type I, II) constructions.
See [[ibc-construction-types]] for more info.
so not permissible in Type [[ibc-construction-types#Type I Fire Resistive Non-Combustible|I]],
[[ibc-construction-types#Type II Non-Combustible|II]] constructions.
#### Concealment
@@ -81,8 +80,8 @@ See [[pdi-breakdowns#Garage]] for more info.
#### Slab Thickness
Conduits may not be routed through slabs of thickness
less than 3 times the outer diameter of the conduit.
Conduits may only be routed through slabs of thickness
at least 3 times the outer diameter of the conduit.
| Conduit Size | Minimum Slab Thickness (in) |
| ------------:| ---------------------------:|
@@ -133,8 +132,8 @@ _Market Type = Assisted Living:_ MC-AP may be required.
Cable type wiring methods (MC, NM, SE)
may only be used where they will be concealed from view.
Exception:
Temporary provisions for unfinished spaces (e.g. core and shell retail)
> [!important] Exception:
> Temporary provisions for unfinished spaces (e.g. core and shell retail)
#### Multi-Circuit Homeruns
@@ -145,6 +144,7 @@ Temporary provisions for unfinished spaces (e.g. core and shell retail)
### EMT Overhead
Set-screw fittings are [[best-practice]]
Set-screw fittings may not be acceptable.
> [!info]