vault backup: 2025-10-07 16:32:57
This commit is contained in:
+69
-21
@@ -9,14 +9,18 @@ tags:
|
||||
---
|
||||
# Conductor Sizing
|
||||
|
||||
Conductors are sized to be suitable for the load,
|
||||
overcurrent protection is sized to protect the conductors.
|
||||
|
||||
## "The 80% Rule"
|
||||
|
||||
"The 80% Rule" is a rule of thumb
|
||||
referring to a common convention of several articles
|
||||
including:
|
||||
|
||||
- [[nfpa-70_article-210_branch-circuits#210.19(A)(1) General.]]
|
||||
- [[nfpa-70_article-215_feeders#215.2(A)(1) General.]]
|
||||
* [[nfpa-70_210_branch-circuits#210.19(A)(1) General.]]
|
||||
* [[nfpa-70_215_feeders#215.2(A)(1) General.]]
|
||||
* [[nfpa-70_430_motors#430.22 Single Motor.]]
|
||||
|
||||
which paraphrased states:
|
||||
|
||||
@@ -45,17 +49,26 @@ $$
|
||||
$$
|
||||
|
||||
but the 180VA per yoke load specified in
|
||||
[[nfpa-70_article-220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]]
|
||||
[[nfpa-70_220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]]
|
||||
is specifically for calculating service and feeder sizing.
|
||||
|
||||
Per [[nfpa-70_article-210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]]
|
||||
Per [[nfpa-70_210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]]
|
||||
a receptacle branch circuit's load
|
||||
is the load of the equipment intended to be served by it.
|
||||
|
||||
Where general-use receptacles are provided
|
||||
without specific equipment in mind,
|
||||
circuits will be engineered at the minimum load.
|
||||
If a receptacle circuit's load is a whole multiple of 180VA
|
||||
there's a good chance that's the number of devices,
|
||||
or at least was at some point in the design.
|
||||
|
||||
## Feeders
|
||||
|
||||
> [!cite] 250.122 Size of Equipment Grounding Conductors
|
||||
> **(A) General.** Copper, aluminum, or copper-clad aluminum
|
||||
> [!cite] NEC Article 250 (emphasis added)
|
||||
> ### 250.122 Size of Equipment Grounding Conductors
|
||||
> #### (A) General.
|
||||
> Copper, aluminum, or copper-clad aluminum
|
||||
> equipment grounding conductors of the wire type
|
||||
> shall not be smaller than shown in Table 250.122,
|
||||
> but in no case shall they be required to be larger
|
||||
@@ -73,8 +86,10 @@ are in contradiction to this idea.
|
||||
|
||||
Given a minimum ampacity, find all valid configurations.
|
||||
|
||||
> [!cite] 310.10(H) Conductors in Parallel.
|
||||
> **(1) General.** Aluminum, copper-clad aluminum, or copper conductors,
|
||||
> [!cite] NEC Article 310 (emphasis added)
|
||||
> #### 310.10(H) Conductors in Parallel.
|
||||
> ##### (1) General.
|
||||
> Aluminum, copper-clad aluminum, or copper conductors,
|
||||
> for each phase, polarity, neutral, or grounded circuit
|
||||
> shall be permitted to be connected in parallel
|
||||
> (electrically joined at both ends)
|
||||
@@ -101,31 +116,64 @@ either for spec requirements or conduit fill considerations.
|
||||
## Voltage Drop
|
||||
|
||||
$$
|
||||
V_d = \frac{ I \times R \times L \times M }{ P }
|
||||
V_d = I \times R \times L \times M
|
||||
$$
|
||||
|
||||
where
|
||||
- $V_d$ = Voltage Drop in volts ($V$)
|
||||
- $I$ = Current in Amperes ($A$)
|
||||
- $R$ = Linear resistance in ohms per foot ($\Omega\text{ft}^{-1}$)
|
||||
- $L$ = Length of wire one way in feet ($\text{ft}$)
|
||||
- $M$ = Multiplier
|
||||
- $2$ for 1-phase
|
||||
- $\sqrt{3}$ for 3-phase
|
||||
- $P$ = Number of parallel runs
|
||||
* $V_d$ = Voltage Drop in volts ($V$)
|
||||
* $I$ = Current in Amperes ($A$)
|
||||
* $R$ = Feeder linear resistance in ohms per foot ($VA^{-1}\text{ft}^{-1}$)
|
||||
* $L$ = Length of wire one way in feet ($\text{ft}$)
|
||||
* $M$ = Multiplier
|
||||
* $2$ for 1-phase
|
||||
* $\sqrt{3}$ for 3-phase
|
||||
|
||||
It is often more useful to know the maximum length
|
||||
a certain wiring configuration is suitable for.
|
||||
|
||||
$$
|
||||
L = \frac{ V_d }{ I \times M } \times \frac{ P }{ R }
|
||||
L = \frac{ V_d }{ I \times M } \times \frac{1}{R}
|
||||
$$
|
||||
|
||||
- $L$ = Max length of wire one way in feet ($\text{ft}$)
|
||||
- $\frac{ V_d }{ I \times M }$ = Max circuit resistance in ohms ($\Omega$)
|
||||
- $\frac{ P }{ R }$ = ??? in feet per ohm ($\text{ft}\Omega^{-1}$)
|
||||
* $L$ = Max length of wire one way in feet ($\text{ft}$)
|
||||
* $\frac{ V_d }{ I \times M }$ = Max circuit resistance in ohms ($VA^{-1}$)
|
||||
|
||||
> [!info] Ohm's Law
|
||||
>
|
||||
> $$
|
||||
> V = I \times R, \quad R = \frac{ V }{ I }, \quad I = \frac{ V }{ R }
|
||||
> $$
|
||||
|
||||
> [!important]
|
||||
> "Current" is not the OCPD rating,
|
||||
> but the actual load.
|
||||
|
||||
## Transformers
|
||||
|
||||
$$
|
||||
I = \frac{S}{ \sqrt{3} \times V \times E }
|
||||
$$
|
||||
|
||||
* $I$ = nameplate current rating
|
||||
* $S$ = nameplate kVA rating
|
||||
* $V$ = feeder voltage
|
||||
* $E$ = efficiency
|
||||
|
||||
## Parallel Runs
|
||||
|
||||
$$
|
||||
\frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots
|
||||
$$
|
||||
|
||||
where $R_1 = R_n$:
|
||||
|
||||
$$
|
||||
\begin{align*}
|
||||
\frac{1}{R_{\text{eq}}} &= P \times \left(\frac{1}{R_1}\right) \\
|
||||
&= \frac{P}{R_1} \\
|
||||
R_{\text{eq}} &= \frac{R_1}{P}
|
||||
\end{align*}
|
||||
$$
|
||||
|
||||
where
|
||||
* $P$ = Number of parallel runs
|
||||
|
||||
Reference in New Issue
Block a user