# NEC Article 210 Branch Circuits
|
||||
|
||||
## Part I. General Provisions
|
||||
|
||||
### 210.1 Scope.
|
||||
|
||||
This article provides the general requirements for branch circuits.
|
||||
|
||||
<!-- TODO: TEXT OMITTED -->
|
||||
|
||||
### 210.11 Branch Circuits Required.
|
||||
|
||||
Branch circuits for lighting and for appliances,
|
||||
including motor-operated appliances,
|
||||
shall be provided to supply the loads calculated in accordance with 220.10.
|
||||
In addition, branch circuits shall be provided for specific loads not covered by 220.10
|
||||
where required elsewhere in this Code
|
||||
and for dwelling unit loads as specified in 210.11(C).
|
||||
|
||||
#### 210.11(A) Number of Branch Circuits.
|
||||
|
||||
The minimum number of branch circuits
|
||||
shall be determined from the total calculated load
|
||||
and the size or rating of the circuits used.
|
||||
In all installations, the number of circuits
|
||||
shall be sufficient to supply the load served.
|
||||
In no case shall the load on any circuit exceed the maximum specified by 220.18.
|
||||
|
||||
#### 210.11(B) Load Evenly Proportioned Among Branch Circuits.
|
||||
|
||||
Where the load is calculated on the basis of volt-amperes per square meter or per square foot,
|
||||
the wiring system up to and including the branch-circuit panelboard(s)
|
||||
shall be provided to serve not less than the calculated load.
|
||||
This load shall be evenly proportioned
|
||||
among multioutlet branch circuits within the panelboard(s).
|
||||
Branch-circuit overcurrent devices and circuits
|
||||
shall be required to be installed only to serve the connected load.
|
||||
|
||||
#### 210.11(C) Dwelling Units.
|
||||
|
||||
##### 210.11(C)(1) Small-Appliance Branch Circuits.
|
||||
|
||||
In addition to the number of branch circuits required by other parts of this section,
|
||||
two or more 20-ampere small-appliance branch circuits shall be provided
|
||||
for all receptacle outlets specified by 210.52(B).
|
||||
|
||||
##### 210.11(C)(2) Laundry Branch Circuits.
|
||||
|
||||
In addition to the number of branch circuits required by other parts of this section,
|
||||
at least one additional 20-ampere branch circuit shall be provided
|
||||
to supply the laundry receptacle outlet(s) required by 210.52(F).
|
||||
This circuit shall have no other outlets.
|
||||
|
||||
##### 210.11(C)(3) Bathroom Branch Circuits.
|
||||
|
||||
In addition to the number of branch circuits required by other parts of this section,
|
||||
one or more 120-volt, 20-ampere branch circuit shall be provided
|
||||
to supply bathroom(s) receptacle outlet(s) required by 210.52(D)
|
||||
and any countertop and similar work surface receptacle outlets.
|
||||
Such circuits shall have no other outlets.
|
||||
|
||||
Exception:
|
||||
Where the 20-ampere circuit supplies a single bathroom,
|
||||
outlets for other equipment within the same bathroom
|
||||
shall be permitted to be supplied in accordance with 210.23(A)(1) and (A)(2).
|
||||
|
||||
##### 210.11(C)(4) Garage Branch Circuits.
|
||||
|
||||
In addition to the number of branch circuits required by other parts of this section,
|
||||
at least one 120-volt, 20-ampere branch circuit shall be installed
|
||||
to supply receptacle outlets required by 210.52(G)(1)
|
||||
for attached garages and in detached garages with electric power.
|
||||
This circuit shall have no other outlets.
|
||||
|
||||
Exception:
|
||||
This circuit shall be permitted to supply
|
||||
readily accessible outdoor receptacle outlets.
|
||||
|
||||
<!-- TODO: TEXT OMITTED -->
|
||||
|
||||
## Part II. Branch-Circuit Ratings
|
||||
|
||||
### 210.18 Rating.
|
||||
|
||||
Branch circuits recognized by this article
|
||||
shall be rated in accordance with the maximum permitted ampere rating
|
||||
or setting of the overcurrent device.
|
||||
The rating for other than individual branch circuits
|
||||
shall be 15, 20, 30, 40, and 50 amperes.
|
||||
Where conductors of higher ampacity are used for any reason,
|
||||
the ampere rating or setting of the specified overcurrent device
|
||||
shall determine the circuit rating.
|
||||
|
||||
> [!important] Exception:
|
||||
> Multioutlet branch circuits greater than 50 amperes
|
||||
> shall be permitted to supply nonlighting outlet loads on industrial premises
|
||||
> where conditions of maintenance and supervision ensure
|
||||
> that only qualified persons service the equipment.
|
||||
|
||||
### 210.19 Conductors -- Minimum Ampacity and Size.
|
||||
|
||||
<!-- TODO: TEXT OMITTED -->
|
||||
|
||||
#### 210.19(A) Branch Circuits Not More Than 600 Volts.
|
||||
|
||||
##### 210.19(A)(1) General.
|
||||
|
||||
Branch-circuit conductors shall have an ampacity
|
||||
not less than the larger of 210.19(A)(1)(a) or (A)(1)(b)
|
||||
and comply with
|
||||
[[nfpa-70_110_requirements-for-electrical-installations#110.14(C) Temperature Limitations.|110.14(C)]]
|
||||
for equipment terminations.
|
||||
|
||||
* (a) Where a branch circuit supplies continuous loads
|
||||
or any combination of continuous and noncontinuous loads,
|
||||
the minimum branch-circuit conductor size
|
||||
shall have an ampacity not less than the noncontinuous load
|
||||
plus 125 percent of the continuous load in accordance with
|
||||
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts – 2000 Volts.|310.14]].
|
||||
|
||||
* (b) The minimum branch-circuit conductor size
|
||||
shall have an ampacity not less than the maximum load to be served
|
||||
after the application of any adjustment
|
||||
or correction factors in accordance with
|
||||
[[nfpa-70_310_conductors_for_general_wiring#310.15 Ampacity Tables.|310.15]].
|
||||
|
||||
##### 210.19(A)(2) Branch Circuits with More than One Receptacle.
|
||||
|
||||
Conductors of branch circuits supplying more than one receptacle
|
||||
for cord-and-plug-connected portable loads
|
||||
shall have an ampacity of not less than the rating of the branch circuit.
|
||||
|
||||
<!-- TODO: TEXT OMITTED -->
|
||||
|
||||
### 210.21 Outlet Devices.
|
||||
|
||||
Outlet devices shall have an ampere rating
|
||||
that is not less than the load to be served
|
||||
and shall comply with 210.21(A) and (B).
|
||||
|
||||
#### 210.21(A) Lampholders.
|
||||
|
||||
Where connected to a branch circuit having a rating in excess of 20 amperes, lampholders
|
||||
shall be of the heavy-duty type. A heavy-duty lampholder
|
||||
shall have a rating of not less than 660 watts if of the admedium type,
|
||||
or not less than 750 watts if of any other type.
|
||||
|
||||
#### 210.21(B) Receptacles.
|
||||
|
||||
##### 210.21(B)(1) Single Receptacle on an Individual Branch Circuit.
|
||||
|
||||
A single receptacle installed on an individual branch circuit
|
||||
shall have an ampere rating
|
||||
not less than that of the branch circuit.
|
||||
|
||||
> [!important] Exception No. 1:
|
||||
> A receptacle installed in accordance with 430.81(B).
|
||||
|
||||
> [!important] Exception No. 2:
|
||||
> A receptacle installed exclusively for the use of a cord-and-plug-connected arc welder
|
||||
> shall be permitted to have an ampere rating
|
||||
> not less than the minimum branch-circuit conductor ampacity
|
||||
> determined by 630.11(A) for arc welders.
|
||||
|
||||
> [!info] Informational Note:
|
||||
> See the definition of receptacle in Article 100.
|
||||
|
||||
##### 210.21(B)(2) Total Cord-and-Plug-Connected Load.
|
||||
|
||||
Where connected to a branch circuit supplying two or more receptacles or outlets,
|
||||
a receptacle shall not supply a total cord-and-plug-connected load
|
||||
in excess of the maximum specified in Table 210.21(B)(2).
|
||||
|
||||
##### Table 210.21(B)(2) Maximum Cord-and-Plug-Connected Load to Receptacle
|
||||
|
||||
| Circuit Rating (Amperes) | Receptacle Rating (Amperes) | Maximum Load (Amperes) |
|
||||
| ------------------------ | --------------------------- | ---------------------- |
|
||||
| 15 or 20 | 15 | 12 |
|
||||
| 20 | 20 | 16 |
|
||||
| 30 | 30 | 24 |
|
||||
|
||||
##### 210.21(B)(3) Receptacle Ratings.
|
||||
|
||||
Where connected to a branch circuit supplying two or more receptacles or outlets,
|
||||
receptacle ratings shall conform to the values listed in Table 210.21(B)(3),
|
||||
or, where rated higher than 50 amperes,
|
||||
the receptacle rating shall not be less than the branch-circuit rating.
|
||||
|
||||
> [!important] Exception No. 1:
|
||||
> Receptacles installed exclusively
|
||||
> for the use of one or more cord-and-plug-connected arc welders
|
||||
> shall be permitted to have ampere ratings
|
||||
> not less than the minimum branch-circuit conductor ampacity
|
||||
> determined by 630.11(A) or (B) for arc welders.
|
||||
|
||||
> [!important] Exception No. 2:
|
||||
> The ampere rating of a receptacle
|
||||
> installed for electric discharge lighting
|
||||
> shall be permitted to be based on 410.62(C).
|
||||
|
||||
##### Table 210.21(B)(3) Receptacle Ratings for Various Size Circuits
|
||||
|
||||
| Circuit Rating (Amperes) | Receptacle Rating (Amperes) |
|
||||
| ------------------------ | --------------------------- |
|
||||
| 15 | Not over 15 |
|
||||
| 20 | 15 or 20 |
|
||||
| 30 | 30 |
|
||||
| 40 | 40 or 50 |
|
||||
| 50 | 50 |
|
||||
|
||||
##### 210.21(B)(4) Range Receptacle Rating.
|
||||
|
||||
The ampere rating of a range receptacle
|
||||
shall be permitted to be based on a single range demand load
|
||||
as specified in Table 220.55.
|
||||
|
||||
### 210.22 Permissible Loads, Individual Branch Circuits.
|
||||
|
||||
An individual branch circuit
|
||||
shall be permitted to supply any load for which it is rated,
|
||||
but in no case shall the load exceed the branch-circuit ampere rating.
|
||||
|
||||
### 210.23 Permissible Loads, Multiple-Outlet Branch Circuits.
|
||||
|
||||
In no case shall the load exceed the branch-circuit ampere rating.
|
||||
A branch circuit supplying two or more outlets or receptacles
|
||||
shall supply only the loads specified according to its size
|
||||
as specified in 210.23(A) through (D)
|
||||
and as summarized in 210.24 and Table 210.24.
|
||||
|
||||
#### 210.23(A) 15- and 20-Ampere Branch Circuits.
|
||||
|
||||
A 15- or 20-ampere branch circuit
|
||||
shall be permitted to supply lighting units
|
||||
or other utilization equipment,
|
||||
or a combination of both,
|
||||
and shall comply with 210.23(A)(1) and (A)(2).
|
||||
|
||||
> [!important] Exception:
|
||||
> The small-appliance branch circuits,
|
||||
> laundry branch circuits, and bathroom branch circuits
|
||||
> required in a dwelling unit(s) by 210.11(C)(1), (C)(2), and (C)(3)
|
||||
> shall supply only the receptacle outlets specified in that section.
|
||||
|
||||
##### 210.23(A)(1) Cord-and-Plug-Connected Equipment Not Fastened in Place.
|
||||
|
||||
The rating of any one cord-and-plug-connected utilization equipment not fastened in place
|
||||
shall not exceed 80 percent of the branch-circuit ampere rating.
|
||||
|
||||
##### 210.23(A)(2) Utilization Equipment Fastened in Place.
|
||||
|
||||
The total rating of utilization equipment fastened in place, other than luminaires,
|
||||
shall not exceed 50 percent of the branch-circuit ampere rating
|
||||
where lighting units, cord-and-plug-connected utilization equipment not fastened in place,
|
||||
or both, are also supplied.
|
||||
|
||||
#### 210.23(B) 30-Ampere Branch Circuits.
|
||||
|
||||
A 30-ampere branch circuit
|
||||
shall be permitted to supply fixed lighting units
|
||||
with heavy-duty lampholders in other than a dwelling unit(s)
|
||||
or utilization equipment in any occupancy.
|
||||
A rating of any one cord-and-plug-connected utilization equipment
|
||||
shall not exceed 80 percent of the branch-circuit ampere rating.
|
||||
|
||||
##### 210.23(C) 40and 50-Ampere Branch Circuits.
|
||||
|
||||
A 40- or 50-ampere branch circuit
|
||||
shall be permitted to supply cooking appliances
|
||||
that are fastened in place in any occupancy.
|
||||
In other than dwelling units,
|
||||
such circuits shall be permitted to supply
|
||||
fixed lighting units with heavy-duty lampholders,
|
||||
infrared heating units,
|
||||
or other utilization equipment.
|
||||
|
||||
#### 210.23(D) Branch Circuits Larger Than 50 Amperes.
|
||||
|
||||
Branch circuits larger than 50 amperes
|
||||
shall supply only nonlighting outlet loads.
|
||||
|
||||
<!-- TODO: TEXT OMITTED -->
|
||||