vault backup: 2025-10-07 16:32:57
This commit is contained in:
+3
-3
@@ -39,9 +39,9 @@
|
|||||||
"dynamicStyling": "colorful",
|
"dynamicStyling": "colorful",
|
||||||
"isLeftHanded": false,
|
"isLeftHanded": false,
|
||||||
"iframeMatchExcalidrawTheme": true,
|
"iframeMatchExcalidrawTheme": true,
|
||||||
"matchTheme": false,
|
"matchTheme": true,
|
||||||
"matchThemeAlways": false,
|
"matchThemeAlways": true,
|
||||||
"matchThemeTrigger": false,
|
"matchThemeTrigger": true,
|
||||||
"defaultMode": "normal",
|
"defaultMode": "normal",
|
||||||
"defaultPenMode": "never",
|
"defaultPenMode": "never",
|
||||||
"penModeDoubleTapEraser": true,
|
"penModeDoubleTapEraser": true,
|
||||||
|
|||||||
+42
-34
@@ -9,24 +9,56 @@
|
|||||||
"path": "README.md"
|
"path": "README.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "nfpa-70_article-210_branch-circuits",
|
"basename": "stochastic-branch-takeoff",
|
||||||
"path": "nfpa-70_article-210_branch-circuits.md"
|
"path": "stochastic-branch-takeoff.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "nfpa-70_article-215_feeders",
|
"basename": "electrical",
|
||||||
"path": "nfpa-70_article-215_feeders.md"
|
"path": "electrical.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "nfpa-70_article-220_load-calculations",
|
"basename": "full-takeoff",
|
||||||
"path": "nfpa-70_article-220_load-calculations.md"
|
"path": "full-takeoff.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "nfpa-70_article-310_conductors_for_general_wiring",
|
"basename": "nfpa-70_314_boxes",
|
||||||
"path": "nfpa-70_article-310_conductors_for_general_wiring.md"
|
"path": "nfpa-70_314_boxes.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "nfpa-70_article-110_requirements-for-electrical-installations",
|
"basename": "nfpa-70_450_transformers",
|
||||||
"path": "nfpa-70_article-110_requirements-for-electrical-installations.md"
|
"path": "nfpa-70_450_transformers.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_430_motors",
|
||||||
|
"path": "nfpa-70_430_motors.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_310_conductors_for_general_wiring",
|
||||||
|
"path": "nfpa-70_310_conductors_for_general_wiring.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_220_load-calculations",
|
||||||
|
"path": "nfpa-70_220_load-calculations.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_215_feeders",
|
||||||
|
"path": "nfpa-70_215_feeders.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_210_branch-circuits",
|
||||||
|
"path": "nfpa-70_210_branch-circuits.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "nfpa-70_110_requirements-for-electrical-installations",
|
||||||
|
"path": "nfpa-70_110_requirements-for-electrical-installations.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "alternating-current",
|
||||||
|
"path": "alternating-current.md"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"basename": "construction-estimating",
|
||||||
|
"path": "construction-estimating.md"
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
"basename": "idea",
|
"basename": "idea",
|
||||||
@@ -48,10 +80,6 @@
|
|||||||
"basename": "fixtures",
|
"basename": "fixtures",
|
||||||
"path": "fixtures.md"
|
"path": "fixtures.md"
|
||||||
},
|
},
|
||||||
{
|
|
||||||
"basename": "full-takeoff",
|
|
||||||
"path": "full-takeoff.md"
|
|
||||||
},
|
|
||||||
{
|
{
|
||||||
"basename": "portable-tools",
|
"basename": "portable-tools",
|
||||||
"path": "portable-tools.md"
|
"path": "portable-tools.md"
|
||||||
@@ -72,14 +100,6 @@
|
|||||||
"basename": "this-notebook",
|
"basename": "this-notebook",
|
||||||
"path": "this-notebook.md"
|
"path": "this-notebook.md"
|
||||||
},
|
},
|
||||||
{
|
|
||||||
"basename": "electrical",
|
|
||||||
"path": "electrical.md"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"basename": "3-phase-power",
|
|
||||||
"path": "3-phase-power.md"
|
|
||||||
},
|
|
||||||
{
|
{
|
||||||
"basename": "accubid-setup",
|
"basename": "accubid-setup",
|
||||||
"path": "accubid-setup.md"
|
"path": "accubid-setup.md"
|
||||||
@@ -136,10 +156,6 @@
|
|||||||
"basename": "90-day-performance-review",
|
"basename": "90-day-performance-review",
|
||||||
"path": "90-day-performance-review.md"
|
"path": "90-day-performance-review.md"
|
||||||
},
|
},
|
||||||
{
|
|
||||||
"basename": "construction-estimating",
|
|
||||||
"path": "construction-estimating.md"
|
|
||||||
},
|
|
||||||
{
|
{
|
||||||
"basename": "favorite-quotes",
|
"basename": "favorite-quotes",
|
||||||
"path": "favorite-quotes.md"
|
"path": "favorite-quotes.md"
|
||||||
@@ -183,14 +199,6 @@
|
|||||||
{
|
{
|
||||||
"basename": "functional-estimating",
|
"basename": "functional-estimating",
|
||||||
"path": "functional-estimating.md"
|
"path": "functional-estimating.md"
|
||||||
},
|
|
||||||
{
|
|
||||||
"basename": "estimating-philosophy",
|
|
||||||
"path": "estimating-philosophy.md"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"basename": "construction-estimating-software",
|
|
||||||
"path": "construction-estimating-software.md"
|
|
||||||
}
|
}
|
||||||
],
|
],
|
||||||
"omittedPaths": [],
|
"omittedPaths": [],
|
||||||
|
|||||||
+92
-9
@@ -6,24 +6,107 @@ tags:
|
|||||||
- topic/electrical
|
- topic/electrical
|
||||||
- type/encyclopedia
|
- type/encyclopedia
|
||||||
---
|
---
|
||||||
# 3 Phase Power
|
# Alternating Current
|
||||||
|
|
||||||
|
[Alternating current (AC)](https://en.wikipedia.org/wiki/AC_power)
|
||||||
|
is electric current that reverses direction periodically.
|
||||||
|
The voltage and current in an AC circuit oscillate in a sinusoidal manner.
|
||||||
|
The frequency of the oscillation is the number of complete cycles per second measured in hertz (Hz).
|
||||||
|
The frequency of the AC power grid in the United States is 60 Hz.
|
||||||
|
|
||||||
|
* Ungrounded conductor - "Hot"
|
||||||
|
* Grounded conductor - "Neutral"
|
||||||
|
|
||||||
|
## 3-Phase Power
|
||||||
|
|
||||||
The conductors between a voltage source and a load are called lines,
|
The conductors between a voltage source and a load are called lines,
|
||||||
and the voltage between any two lines is called line voltage.
|
and the voltage between any two lines is called line voltage.
|
||||||
The voltage measured between any line and neutral is called phase voltage.
|
The voltage measured between any line and neutral is called phase voltage.
|
||||||
|
|
||||||
%%
|
|
||||||
|
|
||||||
## Scratch
|
|
||||||
|
|
||||||
* Poles vs Phases vs Wires
|
* Poles vs Phases vs Wires
|
||||||
|
|
||||||
3Ø = 3PH 3W
|
* 3Ø = 3PH 3W
|
||||||
3ØY = 3PH 4W
|
* 3ØY = 3PH 4W
|
||||||
|
|
||||||
> Phase abbreviations
|
> [!info] Phase Abbreviations
|
||||||
> * PH
|
> * PH
|
||||||
> * Φ (capital phi)
|
> * Φ (capital phi)
|
||||||
> * Ø (latin O with stroke)
|
> * Ø (latin O with stroke)
|
||||||
|
|
||||||
%%
|
208Y/120V
|
||||||
|
480Y/277V
|
||||||
|
|
||||||
|
### Voltage Systems
|
||||||
|
|
||||||
|
120/240V 1-Phase 3-Wire:
|
||||||
|
- 120V 1-Phase 2-Wire # Line to Neutral
|
||||||
|
- 240V 1-Phase 2-Wire # Line to Line
|
||||||
|
|
||||||
|
120/208V 3-Phase 4-Wire:
|
||||||
|
- 120V 1-Phase 2-Wire # Line to Neutral
|
||||||
|
- 208V 1-Phase 2-Wire # Line to Line
|
||||||
|
- 208V 3-Phase 3-Wire # Line to Lines
|
||||||
|
|
||||||
|
277/480V 3-Phase 4-Wire:
|
||||||
|
- 277V 1-Phase 2-Wire # Line to Neutral
|
||||||
|
- 480V 1-Phase 2-Wire # Line to Line
|
||||||
|
- 480V 3-Phase 3-Wire # Line to Lines
|
||||||
|
|
||||||
|
wiring-configurations:
|
||||||
|
- 1-Phase 2-Wire # Line to Neutral or Line to Line
|
||||||
|
- 1-Phase 3-Wire # Line to Line and Line to Neutral
|
||||||
|
- 3-Phase 3-Wire # Line to Lines
|
||||||
|
- 3-Phase 4-Wire # Line to Lines and Line to Neutral
|
||||||
|
|
||||||
|
## Active and Reactive Power
|
||||||
|
|
||||||
|
As a consequence of the periodic nature of AC,
|
||||||
|
and the electromagnetic "inertia" of inductance and capacitance,
|
||||||
|
inherent of all matter,
|
||||||
|
the power in an AC circuit is divided into two components:
|
||||||
|
|
||||||
|
- **Active Power**
|
||||||
|
(abbreviated $P$, measured in watts)
|
||||||
|
also known as real power, is power that *does work*.
|
||||||
|
|
||||||
|
- **Reactive Power**
|
||||||
|
(abbreviated $Q$, measured in volt-amperes reactive (VAR))
|
||||||
|
transfers no net energy to the load.
|
||||||
|
|
||||||
|
derived from these components are others:
|
||||||
|
|
||||||
|
- **Complex Power**
|
||||||
|
(abbreviated $S$, measured in volt-amperes (VA))
|
||||||
|
is the vector sum of the active and reactive components.
|
||||||
|
It is "complex" because it exists on the real and imaginary axes
|
||||||
|
of active and reactive power respectively.
|
||||||
|
|
||||||
|
- **Apparent Power**
|
||||||
|
(abbreviated $|S|$, measured in volt-amperes (VA))
|
||||||
|
is the magnitude of the complex power vector.
|
||||||
|
|
||||||
|
- **Power Factor**
|
||||||
|
(abbreviated $\text{PF}$, unitless)
|
||||||
|
is the ratio of active power to apparent power.
|
||||||
|
|
||||||
|
$$
|
||||||
|
P = S \times \text{PF}, \quad S = \frac{P}{\text{PF}}, \quad PF = \frac{P}{\text{S}}
|
||||||
|
$$
|
||||||
|
|
||||||
|
### Power Factor Correction
|
||||||
|
|
||||||
|
Capacitance and inductance can both be measured in VAR,
|
||||||
|
but their effects cancel each other out rather than add.
|
||||||
|
|
||||||
|
## Motors
|
||||||
|
|
||||||
|
1hp = 746 watts
|
||||||
|
|
||||||
|
full-load current (FLC) / full-load amperes (FLA)
|
||||||
|
|
||||||
|
minimum circuit ampacity (MCA)
|
||||||
|
|
||||||
|
$$
|
||||||
|
\text{MCA} = 1.25 \times \text{FLC}
|
||||||
|
$$
|
||||||
|
|
||||||
|
|||||||
+69
-21
@@ -9,14 +9,18 @@ tags:
|
|||||||
---
|
---
|
||||||
# Conductor Sizing
|
# Conductor Sizing
|
||||||
|
|
||||||
|
Conductors are sized to be suitable for the load,
|
||||||
|
overcurrent protection is sized to protect the conductors.
|
||||||
|
|
||||||
## "The 80% Rule"
|
## "The 80% Rule"
|
||||||
|
|
||||||
"The 80% Rule" is a rule of thumb
|
"The 80% Rule" is a rule of thumb
|
||||||
referring to a common convention of several articles
|
referring to a common convention of several articles
|
||||||
including:
|
including:
|
||||||
|
|
||||||
- [[nfpa-70_article-210_branch-circuits#210.19(A)(1) General.]]
|
* [[nfpa-70_210_branch-circuits#210.19(A)(1) General.]]
|
||||||
- [[nfpa-70_article-215_feeders#215.2(A)(1) General.]]
|
* [[nfpa-70_215_feeders#215.2(A)(1) General.]]
|
||||||
|
* [[nfpa-70_430_motors#430.22 Single Motor.]]
|
||||||
|
|
||||||
which paraphrased states:
|
which paraphrased states:
|
||||||
|
|
||||||
@@ -45,17 +49,26 @@ $$
|
|||||||
$$
|
$$
|
||||||
|
|
||||||
but the 180VA per yoke load specified in
|
but the 180VA per yoke load specified in
|
||||||
[[nfpa-70_article-220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]]
|
[[nfpa-70_220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]]
|
||||||
is specifically for calculating service and feeder sizing.
|
is specifically for calculating service and feeder sizing.
|
||||||
|
|
||||||
Per [[nfpa-70_article-210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]]
|
Per [[nfpa-70_210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]]
|
||||||
a receptacle branch circuit's load
|
a receptacle branch circuit's load
|
||||||
is the load of the equipment intended to be served by it.
|
is the load of the equipment intended to be served by it.
|
||||||
|
|
||||||
|
Where general-use receptacles are provided
|
||||||
|
without specific equipment in mind,
|
||||||
|
circuits will be engineered at the minimum load.
|
||||||
|
If a receptacle circuit's load is a whole multiple of 180VA
|
||||||
|
there's a good chance that's the number of devices,
|
||||||
|
or at least was at some point in the design.
|
||||||
|
|
||||||
## Feeders
|
## Feeders
|
||||||
|
|
||||||
> [!cite] 250.122 Size of Equipment Grounding Conductors
|
> [!cite] NEC Article 250 (emphasis added)
|
||||||
> **(A) General.** Copper, aluminum, or copper-clad aluminum
|
> ### 250.122 Size of Equipment Grounding Conductors
|
||||||
|
> #### (A) General.
|
||||||
|
> Copper, aluminum, or copper-clad aluminum
|
||||||
> equipment grounding conductors of the wire type
|
> equipment grounding conductors of the wire type
|
||||||
> shall not be smaller than shown in Table 250.122,
|
> shall not be smaller than shown in Table 250.122,
|
||||||
> but in no case shall they be required to be larger
|
> but in no case shall they be required to be larger
|
||||||
@@ -73,8 +86,10 @@ are in contradiction to this idea.
|
|||||||
|
|
||||||
Given a minimum ampacity, find all valid configurations.
|
Given a minimum ampacity, find all valid configurations.
|
||||||
|
|
||||||
> [!cite] 310.10(H) Conductors in Parallel.
|
> [!cite] NEC Article 310 (emphasis added)
|
||||||
> **(1) General.** Aluminum, copper-clad aluminum, or copper conductors,
|
> #### 310.10(H) Conductors in Parallel.
|
||||||
|
> ##### (1) General.
|
||||||
|
> Aluminum, copper-clad aluminum, or copper conductors,
|
||||||
> for each phase, polarity, neutral, or grounded circuit
|
> for each phase, polarity, neutral, or grounded circuit
|
||||||
> shall be permitted to be connected in parallel
|
> shall be permitted to be connected in parallel
|
||||||
> (electrically joined at both ends)
|
> (electrically joined at both ends)
|
||||||
@@ -101,31 +116,64 @@ either for spec requirements or conduit fill considerations.
|
|||||||
## Voltage Drop
|
## Voltage Drop
|
||||||
|
|
||||||
$$
|
$$
|
||||||
V_d = \frac{ I \times R \times L \times M }{ P }
|
V_d = I \times R \times L \times M
|
||||||
$$
|
$$
|
||||||
|
|
||||||
where
|
where
|
||||||
- $V_d$ = Voltage Drop in volts ($V$)
|
* $V_d$ = Voltage Drop in volts ($V$)
|
||||||
- $I$ = Current in Amperes ($A$)
|
* $I$ = Current in Amperes ($A$)
|
||||||
- $R$ = Linear resistance in ohms per foot ($\Omega\text{ft}^{-1}$)
|
* $R$ = Feeder linear resistance in ohms per foot ($VA^{-1}\text{ft}^{-1}$)
|
||||||
- $L$ = Length of wire one way in feet ($\text{ft}$)
|
* $L$ = Length of wire one way in feet ($\text{ft}$)
|
||||||
- $M$ = Multiplier
|
* $M$ = Multiplier
|
||||||
- $2$ for 1-phase
|
* $2$ for 1-phase
|
||||||
- $\sqrt{3}$ for 3-phase
|
* $\sqrt{3}$ for 3-phase
|
||||||
- $P$ = Number of parallel runs
|
|
||||||
|
|
||||||
It is often more useful to know the maximum length
|
It is often more useful to know the maximum length
|
||||||
a certain wiring configuration is suitable for.
|
a certain wiring configuration is suitable for.
|
||||||
|
|
||||||
$$
|
$$
|
||||||
L = \frac{ V_d }{ I \times M } \times \frac{ P }{ R }
|
L = \frac{ V_d }{ I \times M } \times \frac{1}{R}
|
||||||
$$
|
$$
|
||||||
|
|
||||||
- $L$ = Max length of wire one way in feet ($\text{ft}$)
|
* $L$ = Max length of wire one way in feet ($\text{ft}$)
|
||||||
- $\frac{ V_d }{ I \times M }$ = Max circuit resistance in ohms ($\Omega$)
|
* $\frac{ V_d }{ I \times M }$ = Max circuit resistance in ohms ($VA^{-1}$)
|
||||||
- $\frac{ P }{ R }$ = ??? in feet per ohm ($\text{ft}\Omega^{-1}$)
|
|
||||||
|
|
||||||
> [!info] Ohm's Law
|
> [!info] Ohm's Law
|
||||||
|
>
|
||||||
> $$
|
> $$
|
||||||
> V = I \times R, \quad R = \frac{ V }{ I }, \quad I = \frac{ V }{ R }
|
> V = I \times R, \quad R = \frac{ V }{ I }, \quad I = \frac{ V }{ R }
|
||||||
> $$
|
> $$
|
||||||
|
|
||||||
|
> [!important]
|
||||||
|
> "Current" is not the OCPD rating,
|
||||||
|
> but the actual load.
|
||||||
|
|
||||||
|
## Transformers
|
||||||
|
|
||||||
|
$$
|
||||||
|
I = \frac{S}{ \sqrt{3} \times V \times E }
|
||||||
|
$$
|
||||||
|
|
||||||
|
* $I$ = nameplate current rating
|
||||||
|
* $S$ = nameplate kVA rating
|
||||||
|
* $V$ = feeder voltage
|
||||||
|
* $E$ = efficiency
|
||||||
|
|
||||||
|
## Parallel Runs
|
||||||
|
|
||||||
|
$$
|
||||||
|
\frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots
|
||||||
|
$$
|
||||||
|
|
||||||
|
where $R_1 = R_n$:
|
||||||
|
|
||||||
|
$$
|
||||||
|
\begin{align*}
|
||||||
|
\frac{1}{R_{\text{eq}}} &= P \times \left(\frac{1}{R_1}\right) \\
|
||||||
|
&= \frac{P}{R_1} \\
|
||||||
|
R_{\text{eq}} &= \frac{R_1}{P}
|
||||||
|
\end{align*}
|
||||||
|
$$
|
||||||
|
|
||||||
|
where
|
||||||
|
* $P$ = Number of parallel runs
|
||||||
|
|||||||
+22
-3
@@ -48,10 +48,29 @@ Wiring devices and their wall plates are a common target of [[gold-plating]].
|
|||||||
|
|
||||||
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/
|
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/
|
||||||
|
|
||||||
##### CU/IP
|
##### Roof Mounted Equipment
|
||||||
|
|
||||||
* Units Condensing Unit
|
Unit condensing units
|
||||||
* Mechanical Connection
|
|
||||||
|
.../`CONDENSOR HOME RUNS`
|
||||||
|
|
||||||
|
.../`CU CONDENSER SLEEVE W/ FLEX - NO HMRN WIRE`
|
||||||
|
|
||||||
|
`NO SLEEVE`:
|
||||||
|
Routed through a "doghouse"
|
||||||
|
(a large weatherproof opening)
|
||||||
|
with several other feeds.
|
||||||
|
Used where drilling openings for individual sleeves
|
||||||
|
would be impractical.
|
||||||
|
|
||||||
|
`PVC SLEEVE`, `EMT SLEEVE`:
|
||||||
|
Routed up through the roof,
|
||||||
|
(optionally through a disconnect)
|
||||||
|
with flex to the equipment.
|
||||||
|
|
||||||
|
Equipment Racks: 20 disconnects per rack
|
||||||
|
|
||||||
|
`DISTRIBUTIION`/`TRAPEZE RACK SUPPORT ...`/`...`
|
||||||
|
|
||||||
##### Trash Chute
|
##### Trash Chute
|
||||||
|
|
||||||
|
|||||||
@@ -119,7 +119,7 @@ shall determine the circuit rating.
|
|||||||
Branch-circuit conductors shall have an ampacity
|
Branch-circuit conductors shall have an ampacity
|
||||||
not less than the larger of 210.19(A)(1)(a) or (A)(1)(b)
|
not less than the larger of 210.19(A)(1)(a) or (A)(1)(b)
|
||||||
and comply with
|
and comply with
|
||||||
[[nfpa-70_article-110_requirements-for-electrical-installations#110.14(C) Temperature Limitations.|110.14(C)]]
|
[[nfpa-70_110_requirements-for-electrical-installations#110.14(C) Temperature Limitations.|110.14(C)]]
|
||||||
for equipment terminations.
|
for equipment terminations.
|
||||||
|
|
||||||
* (a) Where a branch circuit supplies continuous loads
|
* (a) Where a branch circuit supplies continuous loads
|
||||||
@@ -127,13 +127,13 @@ for equipment terminations.
|
|||||||
the minimum branch-circuit conductor size
|
the minimum branch-circuit conductor size
|
||||||
shall have an ampacity not less than the noncontinuous load
|
shall have an ampacity not less than the noncontinuous load
|
||||||
plus 125 percent of the continuous load in accordance with
|
plus 125 percent of the continuous load in accordance with
|
||||||
[[nfpa-70_article-310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts – 2000 Volts.|310.14]].
|
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts – 2000 Volts.|310.14]].
|
||||||
|
|
||||||
* (b) The minimum branch-circuit conductor size
|
* (b) The minimum branch-circuit conductor size
|
||||||
shall have an ampacity not less than the maximum load to be served
|
shall have an ampacity not less than the maximum load to be served
|
||||||
after the application of any adjustment
|
after the application of any adjustment
|
||||||
or correction factors in accordance with
|
or correction factors in accordance with
|
||||||
[[nfpa-70_article-310_conductors_for_general_wiring#310.15 Ampacity Tables.|310.15]].
|
[[nfpa-70_310_conductors_for_general_wiring#310.15 Ampacity Tables.|310.15]].
|
||||||
|
|
||||||
##### 210.19(A)(2) Branch Circuits with More than One Receptacle.
|
##### 210.19(A)(2) Branch Circuits with More than One Receptacle.
|
||||||
|
|
||||||
@@ -38,7 +38,7 @@ and shall comply with 110.14(C).
|
|||||||
shall have an ampacity not less than the maximum load to be served
|
shall have an ampacity not less than the maximum load to be served
|
||||||
after the application of any adjustment or correction factors
|
after the application of any adjustment or correction factors
|
||||||
in accordance with
|
in accordance with
|
||||||
[[nfpa-70_article-310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts – 2000 Volts.|310.14]].
|
[[nfpa-70_310_conductors_for_general_wiring#310.14 Ampacities for Conductors Rated 0 Volts – 2000 Volts.|310.14]].
|
||||||
|
|
||||||
Exception No. 1:
|
Exception No. 1:
|
||||||
If the assembly, including the overcurrent devices protecting the feeder(s),
|
If the assembly, including the overcurrent devices protecting the feeder(s),
|
||||||
@@ -117,8 +117,8 @@ A single piece of equipment consisting of a multiple receptacle
|
|||||||
comprised of four or more receptacles
|
comprised of four or more receptacles
|
||||||
shall be calculated at not less than 90 volt-amperes per receptacle.
|
shall be calculated at not less than 90 volt-amperes per receptacle.
|
||||||
This provision shall not be applicable to the receptacle outlets
|
This provision shall not be applicable to the receptacle outlets
|
||||||
specified in [[nfpa-70_article-210_branch-circuits#210.11(C)(1) Small-Appliance Branch Circuits.|210.11(C)(1)]]
|
specified in [[nfpa-70_210_branch-circuits#210.11(C)(1) Small-Appliance Branch Circuits.|210.11(C)(1)]]
|
||||||
and [[nfpa-70_article-210_branch-circuits#210.11(C)(2) Laundry Branch Circuits.|(C)(2)]].
|
and [[nfpa-70_210_branch-circuits#210.11(C)(2) Laundry Branch Circuits.|(C)(2)]].
|
||||||
|
|
||||||
#### 220.14(J) Dwelling Units.
|
#### 220.14(J) Dwelling Units.
|
||||||
|
|
||||||
@@ -1,11 +1,25 @@
|
|||||||
---
|
---
|
||||||
id:
|
id:
|
||||||
aliases: []
|
aliases:
|
||||||
|
- nec-314
|
||||||
tags:
|
tags:
|
||||||
- authorship/other
|
- authorship/other
|
||||||
|
- destiny/uncertain
|
||||||
|
- status/incomplete
|
||||||
- topic/electrical
|
- topic/electrical
|
||||||
|
- type/encyclopedia
|
||||||
---
|
---
|
||||||
# 314.28 Pull and Junction Boxes and Conduit Bodies.
|
# Article 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; and Handhole Enclosures
|
||||||
|
|
||||||
|
## Part I. Scope and General
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
|
|
||||||
|
## Part II. Installation
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
|
|
||||||
|
### 314.28 Pull and Junction Boxes and Conduit Bodies.
|
||||||
|
|
||||||
Boxes and conduit bodies used as pull or junction boxes
|
Boxes and conduit bodies used as pull or junction boxes
|
||||||
shall comply with 314.28(A) through (E).
|
shall comply with 314.28(A) through (E).
|
||||||
@@ -14,7 +28,7 @@ shall comply with 314.28(A) through (E).
|
|||||||
> Terminal housings supplied with motors shall comply with
|
> Terminal housings supplied with motors shall comply with
|
||||||
> the provisions of 430.12.
|
> the provisions of 430.12.
|
||||||
|
|
||||||
## (A) Minimum Size.
|
#### (A) Minimum Size.
|
||||||
|
|
||||||
For raceways containing conductors of 4 AWG or larger that are required to be insulated,
|
For raceways containing conductors of 4 AWG or larger that are required to be insulated,
|
||||||
and for cables containing conductors of 4 AWG or larger,
|
and for cables containing conductors of 4 AWG or larger,
|
||||||
@@ -24,14 +38,14 @@ Where an enclosure dimension is to be calculated based on the diameter of enteri
|
|||||||
the diameter shall be the metric designator (trade size)
|
the diameter shall be the metric designator (trade size)
|
||||||
expressed in the units of measurement employed.
|
expressed in the units of measurement employed.
|
||||||
|
|
||||||
### (1) Straight Pulls.
|
##### (1) Straight Pulls.
|
||||||
|
|
||||||
In straight pulls,
|
In straight pulls,
|
||||||
the length of the box or conduit body
|
the length of the box or conduit body
|
||||||
shall not be less than eight times the metric designator (trade size)
|
shall not be less than eight times the metric designator (trade size)
|
||||||
of the largest raceway.
|
of the largest raceway.
|
||||||
|
|
||||||
### (2) Angle or U Pulls, or Splices.
|
##### (2) Angle or U Pulls, or Splices.
|
||||||
|
|
||||||
Where splices or where angle or U pulls are made,
|
Where splices or where angle or U pulls are made,
|
||||||
the distance between each raceway entry inside the box or conduit body
|
the distance between each raceway entry inside the box or conduit body
|
||||||
@@ -58,7 +72,7 @@ When transposing cable size into raceway size in 314.28(A)(1) and (A)(2),
|
|||||||
the minimum metric designator (trade size) raceway
|
the minimum metric designator (trade size) raceway
|
||||||
required for the number and size of conductors in the cable shall be used.
|
required for the number and size of conductors in the cable shall be used.
|
||||||
|
|
||||||
### (3) Smaller Dimensions.
|
##### (3) Smaller Dimensions.
|
||||||
|
|
||||||
Listed boxes or listed conduit bodies
|
Listed boxes or listed conduit bodies
|
||||||
of dimensions less than those required in 314.28(A)(1) and (A)(2)
|
of dimensions less than those required in 314.28(A)(1) and (A)(2)
|
||||||
@@ -93,24 +107,24 @@ as part of the product listing.
|
|||||||
> the applicable product standards evaluate the fill markings covered here
|
> the applicable product standards evaluate the fill markings covered here
|
||||||
> based on conductors with Type XHHW insulation.
|
> based on conductors with Type XHHW insulation.
|
||||||
|
|
||||||
## (B) Conductors in Pull or Junction Boxes.
|
#### (B) Conductors in Pull or Junction Boxes.
|
||||||
|
|
||||||
In pull boxes or junction boxes having any dimension over 1.8 m (6 ft),
|
In pull boxes or junction boxes having any dimension over 1.8 m (6 ft),
|
||||||
all conductors shall be cabled or racked up in an approved manner.
|
all conductors shall be cabled or racked up in an approved manner.
|
||||||
|
|
||||||
## (C) Covers.
|
#### (C) Covers.
|
||||||
|
|
||||||
All pull boxes, junction boxes, and conduit bodies
|
All pull boxes, junction boxes, and conduit bodies
|
||||||
shall be provided with covers compatible with the box or conduit body construction
|
shall be provided with covers compatible with the box or conduit body construction
|
||||||
and suitable for the conditions of use.
|
and suitable for the conditions of use.
|
||||||
Where used, metal covers shall comply with the grounding requirements of 250.110.
|
Where used, metal covers shall comply with the grounding requirements of 250.110.
|
||||||
|
|
||||||
## (D) Permanent Barriers.
|
#### (D) Permanent Barriers.
|
||||||
|
|
||||||
Where permanent barriers are installed in a box,
|
Where permanent barriers are installed in a box,
|
||||||
each section shall be considered as a separate box.
|
each section shall be considered as a separate box.
|
||||||
|
|
||||||
## (E) Power Distribution Blocks.
|
#### (E) Power Distribution Blocks.
|
||||||
|
|
||||||
Power distribution blocks shall be permitted
|
Power distribution blocks shall be permitted
|
||||||
in pull and junction boxes over 1650 cm3 (100 in.3)
|
in pull and junction boxes over 1650 cm3 (100 in.3)
|
||||||
@@ -120,32 +134,38 @@ and where the installation complies with 314.28(E)(1) through (5).
|
|||||||
> [!exception]
|
> [!exception]
|
||||||
> Equipment grounding terminal bars shall be permitted in smaller enclosures.
|
> Equipment grounding terminal bars shall be permitted in smaller enclosures.
|
||||||
|
|
||||||
### (1) Installation.
|
##### (1) Installation.
|
||||||
|
|
||||||
Power distribution blocks installed in boxes shall be listed.
|
Power distribution blocks installed in boxes shall be listed.
|
||||||
Power distribution blocks installed on the line side of the service equipment
|
Power distribution blocks installed on the line side of the service equipment
|
||||||
shall be listed and marked "suitable for use on the line side of service equipment" or equivalent.
|
shall be listed and marked "suitable for use on the line side of service equipment" or equivalent.
|
||||||
|
|
||||||
### (2) Size.
|
##### (2) Size.
|
||||||
|
|
||||||
In addition to the overall size requirement in the first sentence of 314.28(A)(2),
|
In addition to the overall size requirement in the first sentence of 314.28(A)(2),
|
||||||
the power distribution block shall be installed in a box
|
the power distribution block shall be installed in a box
|
||||||
with dimensions not smaller than specified in the installation instructions
|
with dimensions not smaller than specified in the installation instructions
|
||||||
of the power distribution block.
|
of the power distribution block.
|
||||||
|
|
||||||
### (3) Wire Bending Space.
|
##### (3) Wire Bending Space.
|
||||||
|
|
||||||
Wire bending space at the terminals of power distribution blocks
|
Wire bending space at the terminals of power distribution blocks
|
||||||
shall comply with 312.6.
|
shall comply with 312.6.
|
||||||
|
|
||||||
### (4) Live Parts.
|
##### (4) Live Parts.
|
||||||
|
|
||||||
Power distribution blocks shall not have uninsulated live parts exposed within a box,
|
Power distribution blocks shall not have uninsulated live parts exposed within a box,
|
||||||
whether or not the box cover is installed.
|
whether or not the box cover is installed.
|
||||||
|
|
||||||
### (5) Through Conductors.
|
##### (5) Through Conductors.
|
||||||
|
|
||||||
Where the pull or junction boxes are used for conductors
|
Where the pull or junction boxes are used for conductors
|
||||||
that do not terminate on the power distribution block(s),
|
that do not terminate on the power distribution block(s),
|
||||||
the through conductors shall be arranged
|
the through conductors shall be arranged
|
||||||
so the power distribution block terminals are unobstructed following installation.
|
so the power distribution block terminals are unobstructed following installation.
|
||||||
|
|
||||||
|
## Part III. Construction Specifications
|
||||||
|
|
||||||
|
### 314.40 Metal Boxes, Conduit Bodies, and Fittings.
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
@@ -0,0 +1,55 @@
|
|||||||
|
---
|
||||||
|
id:
|
||||||
|
aliases:
|
||||||
|
- nec-430
|
||||||
|
tags:
|
||||||
|
- authorship/other
|
||||||
|
- destiny/uncertain
|
||||||
|
- status/incomplete
|
||||||
|
- topic/electrical
|
||||||
|
- type/encyclopedia
|
||||||
|
---
|
||||||
|
# Article 430 Motors, Motor Circuits, and Controllers
|
||||||
|
|
||||||
|
## Part I. General
|
||||||
|
|
||||||
|
### 430.1 Scope.
|
||||||
|
|
||||||
|
This article covers motors,
|
||||||
|
motor branch-circuit and feeder conductors and their protection,
|
||||||
|
motor overload protection, motor control circuits,
|
||||||
|
motor controllers, and motor control centers.
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
|
|
||||||
|
## Part II. Motor Circuit Conductors
|
||||||
|
|
||||||
|
### 430.21 General.
|
||||||
|
|
||||||
|
Part II specifies ampacities of conductors
|
||||||
|
that are capable of carrying the motor current
|
||||||
|
without overheating under the conditions specified.
|
||||||
|
|
||||||
|
Part II shall not apply to motor circuits rated over 1000 volts, nominal.
|
||||||
|
|
||||||
|
Informational Note:
|
||||||
|
For over 1000 volts, nominal, see Part XI.
|
||||||
|
|
||||||
|
Articles 250, 300, and 310 shall not apply
|
||||||
|
to conductors that form an integral part of equipment,
|
||||||
|
such as motors, motor controllers, motor control centers,
|
||||||
|
or other factory-assembled control equipment.
|
||||||
|
|
||||||
|
Informational Note:
|
||||||
|
See 110.14(C) and 430.9(B) for equipment device terminal requirements.
|
||||||
|
|
||||||
|
### 430.22 Single Motor.
|
||||||
|
|
||||||
|
Conductors that supply a single motor
|
||||||
|
used in a continuous duty application
|
||||||
|
shall have an ampacity of not less than 125 percent
|
||||||
|
of the motor full-load current rating,
|
||||||
|
as determined by 430.6(A)(1),
|
||||||
|
or not less than specified in 430.22(A) through (G).
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
@@ -0,0 +1,61 @@
|
|||||||
|
---
|
||||||
|
id:
|
||||||
|
aliases:
|
||||||
|
- nec-450
|
||||||
|
tags:
|
||||||
|
- authorship/other
|
||||||
|
- destiny/uncertain
|
||||||
|
- status/incomplete
|
||||||
|
- topic/electrical
|
||||||
|
- type/encyclopedia
|
||||||
|
---
|
||||||
|
# Article 450 Transformers and Transformer Vaults (Including Secondary Ties)
|
||||||
|
|
||||||
|
## Part I. General Provisions
|
||||||
|
|
||||||
|
### 450.1 Scope.
|
||||||
|
|
||||||
|
This article covers the installation of all transformers.
|
||||||
|
|
||||||
|
Exception No. 1:
|
||||||
|
Current transformers.
|
||||||
|
|
||||||
|
Exception No. 2:
|
||||||
|
Dry-type transformers
|
||||||
|
that constitute a component part of other apparatus
|
||||||
|
and comply with the requirements for such apparatus.
|
||||||
|
|
||||||
|
Exception No. 3:
|
||||||
|
Transformers that are an integral part
|
||||||
|
of an X-ray, high-frequency, or electrostatic-coating apparatus.
|
||||||
|
|
||||||
|
Exception No. 4:
|
||||||
|
Transformers used with Class 2 and Class 3 circuits
|
||||||
|
that comply with Article 725.
|
||||||
|
|
||||||
|
Exception No. 5:
|
||||||
|
Transformers for sign and outline lighting
|
||||||
|
that comply with Article 600.
|
||||||
|
|
||||||
|
Exception No. 6:
|
||||||
|
Transformers for electric-discharge lighting
|
||||||
|
that comply with Article 410.
|
||||||
|
|
||||||
|
Exception No. 7:
|
||||||
|
Transformers used for power-limited fire alarm circuits
|
||||||
|
that comply with Part III of Article 760.
|
||||||
|
|
||||||
|
Exception No. 8:
|
||||||
|
Transformers used for research, development, or testing,
|
||||||
|
where effective arrangements are provided
|
||||||
|
to safeguard persons from contacting energized parts.
|
||||||
|
|
||||||
|
This article covers the installation of transformers
|
||||||
|
dedicated to supplying power to a fire pump installation
|
||||||
|
as modified by Article 695.
|
||||||
|
|
||||||
|
This article also covers the installation of transformers
|
||||||
|
in hazardous (classified) locations
|
||||||
|
as modified by Articles 501 through 504.
|
||||||
|
|
||||||
|
<!-- TODO: TEXT OMITTED -->
|
||||||
@@ -0,0 +1,24 @@
|
|||||||
|
---
|
||||||
|
id:
|
||||||
|
aliases: []
|
||||||
|
tags:
|
||||||
|
- destiny/fleeting
|
||||||
|
- topic/electrical
|
||||||
|
- topic/estimating
|
||||||
|
- type/idea
|
||||||
|
---
|
||||||
|
# Stochastic Branch Takeoff
|
||||||
|
|
||||||
|
generate a BOM from point loads distributed in a space.
|
||||||
|
|
||||||
|
```yaml
|
||||||
|
- x: 302.84
|
||||||
|
y: 2364.47
|
||||||
|
kW: 5.3
|
||||||
|
voltage: 277
|
||||||
|
phases: 1
|
||||||
|
...
|
||||||
|
```
|
||||||
|
|
||||||
|
determine relative impact of factors
|
||||||
|
* allowable voltage drop
|
||||||
Reference in New Issue
Block a user