diff --git a/nfpa-70_300_general-requirements.md b/nfpa-70_300_general-requirements.md index 7d46bc8..2a093b9 100644 --- a/nfpa-70_300_general-requirements.md +++ b/nfpa-70_300_general-requirements.md @@ -714,7 +714,7 @@ Intermediate supports shall be provided as necessary to limit supported conductor lengths to not greater than those values specified in Table 300.19(A). -#### Table 300.19(A) Spacings for Conductor Supports +#### Table 300.19(A) Spacings for Conductor Supports ^t300-19a | Conductor Size | Aluminum or Copper-Clad Aluminum | Copper | | -------------------------------- | --------------------------------:| ------:| @@ -731,7 +731,7 @@ to not greater than those values specified in Table 300.19(A). Support methods and spacing intervals for fire-rated cables and conductors shall comply with any restrictions provided in the listing of the electrical circuit protective system used -and in no case shall exceed the values in Table 300.19(A). +and in no case shall exceed the values in [[#^t300-19a|Table 300.19(A)]]. #### 300.19(C) Support Methods. @@ -752,7 +752,7 @@ One of the following methods of support shall be used: the cables being carried on two or more insulating supports and additionally secured thereto by tie wires, if desired. Where this method is used, cables shall be supported at intervals - not greater than 20 percent of the support spacing in Table 300.19(A). + not greater than 20 percent of the support spacing in [[#^t300-19a|Table 300.19(A)]]. 4. Other approved means. diff --git a/units-takeoff.md b/units-takeoff.md index eaea31d..e3c2861 100644 --- a/units-takeoff.md +++ b/units-takeoff.md @@ -130,6 +130,12 @@ from credenza location to behind television location. > > _Eaton 35M2W_ +### Doorbells + +??? + +`HANDICAP DB W/SINGLE HORN/STROBE - 12/2c MC CABLE` + ### Telecom Homeruns #### Residential