@@ -1204,7 +1204,7 @@ Feeder and branch-circuit conductors shall be protected at the point the conduct
|
||||
For feeder taps specified in 240.21(B)(2), (B)(3), and (B)(4), the tap conductors shall be permitted to be sized in accordance with Table
|
||||
240.92(B).
|
||||
|
||||
Table 240.92(B) Tap Conductor Short-Circuit Current Ratings
|
||||
##### Table 240.92(B) Tap Conductor Short-Circuit Current Ratings
|
||||
|
||||
Tap conductors are considered to be protected under short-circuit conditions when their short-circuit temperature limit is not exceeded.
|
||||
|
||||
@@ -1212,15 +1212,15 @@ Conductor heating under short-circuit conditions is determined by (1) or (2):
|
||||
|
||||
* (1) _Short-Circuit Formula for Copper Conductors_
|
||||
|
||||
$$
|
||||
(I^2|A^2)t = 0.0297 \log_{10} [(T_{2} + 234)/(T_{1} + 234)]
|
||||
$$
|
||||
$$
|
||||
(I^2|A^2)t = 0.0297 \log_{10} [(T_{2} + 234)/(T_{1} + 234)]
|
||||
$$
|
||||
|
||||
* (2) _Short-Circuit Formula for Aluminum Conductor_
|
||||
|
||||
$$
|
||||
(I^2|A^2)t = 0.0125 \log_{10} [(T_{2} + 228)/(T_{1} + 228)]
|
||||
$$
|
||||
$$
|
||||
(I^2|A^2)t = 0.0125 \log_{10} [(T_{2} + 228)/(T_{1} + 228)]
|
||||
$$
|
||||
|
||||
where:
|
||||
|
||||
|
||||