@@ -1770,9 +1770,12 @@ The structural metal frame of a building or structure shall not be used as an eq
|
||||
|
||||
#### 250.122(A) General.
|
||||
|
||||
Copper, aluminum, or copper-clad aluminum equipment grounding conductors of the wire type shall not be smaller than shown in Table
|
||||
250.122. The equipment grounding conductor shall not be required to be larger than the circuit conductors supplying the equipment. If a cable tray, a raceway, or a cable armor or sheath is used as the equipment grounding conductor, as provided in 250.118 and
|
||||
250.134(1), it shall comply with 250.4(A)(5) or (B)(4).
|
||||
Copper, aluminum, or copper-clad aluminum equipment grounding conductors of the wire type
|
||||
shall not be smaller than shown in Table 250.122.
|
||||
The equipment grounding conductor shall not be required
|
||||
to be larger than the circuit conductors supplying the equipment.
|
||||
If a cable tray, a raceway, or a cable armor or sheath is used as the equipment grounding conductor,
|
||||
as provided in 250.118 and 250.134(1), it shall comply with 250.4(A)(5) or (B)(4).
|
||||
|
||||
Equipment grounding conductors shall be permitted to be sectioned within a multiconductor cable, provided the combined circular mil area complies with Table 250.122.
|
||||
|
||||
@@ -1807,9 +1810,7 @@ The equipment grounding conductor in a flexible cord with the largest circuit co
|
||||
|
||||
#### 250.122(F) Conductors in Parallel.
|
||||
|
||||
For circuits of parallel conductors as permitted in 310.10(G), the equipment grounding conductor shall be installed in accordance with
|
||||
|
||||
##### 250.122(F)(1) or (F) (2).
|
||||
For circuits of parallel conductors as permitted in 310.10(G), the equipment grounding conductor shall be installed in accordance with 250.122(F)(1) or (F) (2).
|
||||
|
||||
##### 250.122(F)(1) Conductor Installations in Raceways, Auxiliary Gutters, or Cable Trays.
|
||||
|
||||
|
||||