id:
|
||||
aliases: []
|
||||
title: Fire Alarm Takeoff
|
||||
tags:
|
||||
- authorship/original
|
||||
- destiny/permanent
|
||||
- occupational/takeoff/fire-alarm
|
||||
- occupational/takeoff
|
||||
- status/draft
|
||||
- type/guide
|
||||
title: Fire Alarm Takeoff
|
||||
---
|
||||
# Fire Alarm Takeoff
|
||||
|
||||
@@ -28,46 +28,58 @@ _Mid Rise, High Density (Wood frame):_ Free air, conduit only where required.
|
||||
|
||||
## Backbone
|
||||
|
||||
Put all backbone takeoff in the `Area` of the Fire Command Center.
|
||||
Include [[sleeving-takeoff]] as necessary.
|
||||
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/...
|
||||
|
||||
### Fire Command Center
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`HEAD END EQUIP`/`... HEAD END`
|
||||
1. * `Area` = As shown.
|
||||
* `Phase` = As shown.
|
||||
|
||||
.../`HEAD END EQUIP`/`... HEAD END`
|
||||
|
||||
### Generator Room
|
||||
|
||||
1. `Area` = Same as FACR
|
||||
1. * `Area` = Same as FACR.
|
||||
* `Phase` = Same as FACR.
|
||||
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...`
|
||||
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...`
|
||||
|
||||
### Fire Pump Room
|
||||
|
||||
1. `Area` = Same as FACR
|
||||
1. * `Area` = Same as FACR.
|
||||
* `Phase` = Same as FACR.
|
||||
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
|
||||
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
|
||||
|
||||
### Elevator Control Rooms
|
||||
|
||||
> Also "Elevator Machine Room"
|
||||
|
||||
* `Area` = Same as FACR.
|
||||
* `Phase` = Same as FACR.
|
||||
|
||||
For each Elevator Control Room (ECR):
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
|
||||
1. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
|
||||
* **Count** = 1
|
||||
|
||||
2. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
|
||||
2. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
|
||||
* **Length** = Length measured from the most distant points of the FACR and ECR.
|
||||
* Input adder length to reach the level of the ECR (Minimum 15ft).
|
||||
* Input adder length to reach the level of the ECR (Minimum 15ft).
|
||||
|
||||
### Elevator Shafts
|
||||
|
||||
* `Area` = Same as FACR.
|
||||
* `Phase` = Same as FACR.
|
||||
|
||||
For each elevator shaft:
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...`
|
||||
1. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...`
|
||||
* **Count** = 1
|
||||
|
||||
2. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...`
|
||||
2. .../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...`
|
||||
* **Length** = Length measured from the most distant points of the FACR and elevator shaft.
|
||||
* Input adder length to reach the level of the shaft (Minimum 15ft).
|
||||
|
||||
@@ -91,7 +103,10 @@ For each elevator shaft:
|
||||
|
||||
For each stairwell:
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS 1" CONDUIT ...`
|
||||
1. * `Area` = Same as FACR.
|
||||
* `Phase` = Same as FACR.
|
||||
|
||||
.../`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS 1" CONDUIT ...`
|
||||
* **Length** = Length measured from the most distant points of the FACR and stairwell.
|
||||
* Input adder length to reach the level of the stairwell (Minimum 15ft).
|
||||
|
||||
@@ -104,8 +119,8 @@ For each stairwell:
|
||||
|
||||
1. Horizontal:
|
||||
|
||||
* `Area` = Same as FACR
|
||||
|
||||
* `Area` = Same as FACR.
|
||||
|
||||
`... HORIZONTAL RUN`
|
||||
* **Length** = Length measured from FACR to all electrical rooms
|
||||
|
||||
@@ -128,10 +143,10 @@ For each stairwell:
|
||||
## Central Monitoring Loop
|
||||
|
||||
> [!important]
|
||||
> Garden Style only.
|
||||
> Garden Style only.
|
||||
|
||||
> Fire Alarm Control Panels from each building will send a signal to a central location.
|
||||
>
|
||||
>
|
||||
> In case of an emergency,
|
||||
> the fire department will go to the central fire alarm station
|
||||
> and find out what the issue is.
|
||||
@@ -141,32 +156,23 @@ For each stairwell:
|
||||
### Smoke Detectors
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES WITH WIRE - ...`/`SMOKE DETECTOR W/ BASE - ...`
|
||||
|
||||
_Design Build:_
|
||||
Count every stairwell at every level.
|
||||
* **Count:** As shown, otherwise (1) every stairwell at every level.
|
||||
|
||||
### Pull Stations
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES WITH WIRE - ...`/`PULL STATION - ...`
|
||||
|
||||
_Design Build:_
|
||||
Count every stairwell at every level
|
||||
and every exterior exit.
|
||||
* **Count:** As shown, otherwise (1) every stairwell at every level and every exterior exit.
|
||||
|
||||
### Flow/Tamper Switches
|
||||
|
||||
No free-air. If wood frame, take off as EMT.
|
||||
|
||||
_Design Build:_
|
||||
Count every stairwell at every level.
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INITIATING DEVICES ...`/`ADDRESSABLE DUAL MONITOR MODULE - FLOW/TAMPER - ...` (No free-air)
|
||||
* **Count:** As shown, otherwise (1) every stairwell at every level.
|
||||
|
||||
### Magnetic Door Holders
|
||||
|
||||
1. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...`
|
||||
|
||||
_Design Build:_
|
||||
Count 2 for every set of double doors.
|
||||
(Typical of elevator lobbies and corridors)
|
||||
* **Count:** As shown, otherwise (2) every set of double doors.
|
||||
(Typical of elevator lobbies and corridors)
|
||||
|
||||
### Horns, Speakers, and Strobes
|
||||
|
||||
@@ -177,8 +183,8 @@ _Design Build (method 1):_
|
||||
* measure with circles on Bluebeam
|
||||
* or divide relevant SF area by 4415
|
||||
* $\pi(\frac{75}{2})^2 \approx 4415$
|
||||
* every elevator lobby,
|
||||
* and every BOH room on the first floor and garage levels.
|
||||
* every elevator lobby, and
|
||||
* every BOH room on the first floor and garage levels.
|
||||
|
||||
_Design Build (alternative method):_
|
||||
* 15ft from end of corridor,
|
||||
|
||||