@@ -25,6 +25,10 @@ In precast slab garages, use EMT.
## Receptacles
> [!important]
> Receptacle symbols are not standard.
> Always check the electrical legend.
## Floor Boxes
`COMMON ASSEMBLIES`/`FLOOR BOXES`/...
@@ -47,10 +51,21 @@ even where serving Amenity spaces.
## Mechanical Connections
### General
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/...
When using length-based assemblies use adders per [[feeders-takeoff]].
%% TODO
#### PVC Connection Assemblies
#### Flex
[[wiring-method-selection#Liquidtight Flex]]
%%
### Stair Pressurization Fans
Assume branch circuit conductors must be protected
@@ -60,17 +75,27 @@ per [[fire-resistive-wiring-methods-takeoff]].
#### Unit Condensing Units
##### Homeruns
* `Area` = _Match unit_
.../`CONDENSOR HOME RUNS`
* **Horizontal:** Distance from load center to FCU.
(~50ft expected)
* **Vertical:** floor-to-floor distance from FCU to CU
| Level | Horizontal | Vertical | Length |
|:-------- | ----------:| --------:| ------:|
| :------- | ---------: | -------: | -----: |
| Level 01 | 150 | 40 | 190 |
| Level 02 | 150 | 30 | 180 |
| Level 03 | 150 | 20 | 170 |
| Level 04 | 150 | 10 | 160 |
Put homeruns on the `Area` of the dwelling unit.
Put connections on the `Area` of the CU.
##### Connections
.../`CONDENSOR HOME RUNS`
* `Area` = _Match CU (usually roof)_
.../`CU CONDENSER SLEEVE W/ FLEX - NO HMRN WIRE`
@@ -92,7 +117,7 @@ Max 20 disconnects per rack
`DISTRIBUTION`/`TRAPEZE RACK SUPPORT ...`/`...`
### Trash Chute
## Trash Chute
1. **Horizontal:**
@@ -106,7 +131,7 @@ Max 20 disconnects per rack
Takeoff: `COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`TRASH CHUTE RISER CIRCUIT...`
* **Length** = average floor to floor height
### Fire/Smoke Dampers
## Fire/Smoke Dampers
[[fire-alarm-takeoff#Fire/Smoke Dampers (FSD's)]]