vault backup: 2025-09-09 16:53:35
This commit is contained in:
@@ -11,6 +11,8 @@ tags:
|
||||
|
||||
### Emergency Responder Radio Communication Systems (ERRCS)
|
||||
|
||||
Relevant Standard: NFPA 1225
|
||||
|
||||
### Cellular Systems
|
||||
|
||||
Less common than ERRCS are "cellular DAS" systems
|
||||
@@ -25,43 +27,37 @@ Complete [[fire-alarm]] preparation and takeoff.
|
||||
|
||||
#### FACR to Every Elev. Shaft
|
||||
|
||||
FACR TO ELEV PIT = 2" PVC40
|
||||
CA.28.31.5
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO ELEV PIT = ...`
|
||||
|
||||
Match Fire Alarm takeoff Length and Count
|
||||
|
||||
#### FACR to Every Staircase
|
||||
|
||||
FACR TO STAIRWELL = 2" PVC40
|
||||
CA.28.31.8
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO STAIRWELL = ...`
|
||||
|
||||
Match Fire Alarm takeoff Length and Count
|
||||
|
||||
#### Stairwell Riser Every 2 Floors
|
||||
|
||||
STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX
|
||||
CA.28.31.12
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX`
|
||||
|
||||
Create a Stairwell typical on every other floor
|
||||
|
||||
#### FACR to Electric Room
|
||||
|
||||
FACR TO 2HR-RATED RM = 2" PVC40
|
||||
CA.28.31.14
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO 2HR-RATED RM = 2" PVC40`
|
||||
|
||||
Match Fire Alarm takeoff Length
|
||||
|
||||
#### Electric Room Riser to Every Floor
|
||||
|
||||
2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX
|
||||
CA.28.31.18
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX`
|
||||
|
||||
Takeoff in every Electric Room
|
||||
|
||||
#### Top 2H Rated Room To Roof
|
||||
|
||||
FACR TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB
|
||||
CA.28.31.18
|
||||
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`TOP 2HR RATED RM TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB`
|
||||
|
||||
Use 15' or Height of ceiling on last building level
|
||||
|
||||
|
||||
Reference in New Issue
Block a user