@@ -95,7 +95,7 @@ Where the building is designed and constructed to comply with an energy code ado
|
||||
|
||||
* (4) The continuous load multiplier of 125 percent shall be applied.
|
||||
|
||||
Table 220.12 General Lighting Loads by Non-Dwelling Occupancy
|
||||
##### Table 220.12 General Lighting Loads by Non-Dwelling Occupancy
|
||||
|
||||
| Type of Occupancy | Volt-amperes/m<sup>2</sup> | Volt-amperes/ft<sup>2</sup> |
|
||||
| --------------------------------------------------------------------------------------------------- | -------------------------- | --------------------------- |
|
||||
@@ -247,6 +247,19 @@ shall be considered part of the minimum lighting load.
|
||||
* (2) The receptacle outlets specified in 210.52(E) and (G)
|
||||
* (3) The lighting outlets specified in 210.70
|
||||
|
||||
%%
|
||||
|
||||
> [!quote] NEC 2017
|
||||
> In one-family, two-family, and multifamily dwellings
|
||||
> and in guest rooms or guest suites of hotels and motels,
|
||||
> the outlets specified in (J)(1), (J)(2), and (J)(3)
|
||||
> are included in the general lighting load calculations of 220.12.
|
||||
> No additional load calculations shall be required for such outlets.
|
||||
|
||||
22 volt-amperes/m<sup>2</sup> (2 volt-amperes/ft<sup>2</sup>).
|
||||
|
||||
%%
|
||||
|
||||
#### 220.14(K) Office Buildings.
|
||||
|
||||
In office buildings, the receptacle loads
|
||||
|
||||