vault backup: 2025-10-20 16:48:59

This commit is contained in:
2025-10-20 16:48:59 -04:00
parent a5676d625e
commit d5e6edbb72
25 changed files with 260 additions and 1713 deletions
+2 -22
View File
@@ -117,29 +117,9 @@ for all feeders, no matter the location.
`COMMON ASSEMBLIES`/`DISTRIBUTION`/`BUS DUCT`
#### Cable Support
#### Conductor Support
> [!quote] 300.19 Supporting Conductors in Vertical Raceways.
> **(A) Spacing Intervals -- Maximum.**
> Conductors in vertical raceways shall be supported
> if the vertical rise exceeds the values in Table 300.19(A).
> At least one support method shall be provided for each conductor
> at the top of the vertical raceway or as close to the top as practical.
> Intermediate supports shall be provided
> as necessary to limit supported conductor lengths
> to not greater than those values specified in Table 300.19(A).
> [!cite] Table 300.19(A) Spacings for Conductor Supports
>
> | Conductor Size | Aluminum or Copper-Clad Aluminum | Copper |
> | -------------------------------- | --------------------------------:| ------:|
> | 18 AWG through 8 AWG | 100ft | 100ft |
> | 6 AWG through 1/0 AWG | 200ft | 100ft |
> | 2/0 AWG through 4/0 AWG | 180ft | 80ft |
> | Over 4/0 AWG through 350 kcmil | 135ft | 60ft |
> | Over 350 kcmil through 500 kcmil | 120ft | 50ft |
> | Over 500 kcmil through 750 kcmil | 95ft | 40ft |
> | Over 750 kcmil | 85ft | 35ft |
![[nfpa-70_300_general-requirements#300.19 Supporting Conductors in Vertical Raceways.]]
`ITEM DATABASE`/`CONDUIT & FITTINGS`/`CABLE SUPPORT / WEDGES`/`... COMPLETE FITTING`/...