`COMMON ASSEMBLIES`/`DISTRIBUTION`/`BUS DUCT`
|
||||
|
||||
#### Cable Support
|
||||
#### Conductor Support
|
||||
|
||||
> [!quote] 300.19 Supporting Conductors in Vertical Raceways.
|
||||
> **(A) Spacing Intervals -- Maximum.**
|
||||
> Conductors in vertical raceways shall be supported
|
||||
> if the vertical rise exceeds the values in Table 300.19(A).
|
||||
> At least one support method shall be provided for each conductor
|
||||
> at the top of the vertical raceway or as close to the top as practical.
|
||||
> Intermediate supports shall be provided
|
||||
> as necessary to limit supported conductor lengths
|
||||
> to not greater than those values specified in Table 300.19(A).
|
||||
|
||||
> [!cite] Table 300.19(A) Spacings for Conductor Supports
|
||||
>
|
||||
> | Conductor Size | Aluminum or Copper-Clad Aluminum | Copper |
|
||||
> | -------------------------------- | --------------------------------:| ------:|
|
||||
> | 18 AWG through 8 AWG | 100ft | 100ft |
|
||||
> | 6 AWG through 1/0 AWG | 200ft | 100ft |
|
||||
> | 2/0 AWG through 4/0 AWG | 180ft | 80ft |
|
||||
> | Over 4/0 AWG through 350 kcmil | 135ft | 60ft |
|
||||
> | Over 350 kcmil through 500 kcmil | 120ft | 50ft |
|
||||
> | Over 500 kcmil through 750 kcmil | 95ft | 40ft |
|
||||
> | Over 750 kcmil | 85ft | 35ft |
|
||||
![[nfpa-70_300_general-requirements#300.19 Supporting Conductors in Vertical Raceways.]]
|
||||
|
||||