@@ -214,16 +214,16 @@ shall be based on Table 310.16 as appropriately modified by 310.12.
|
||||
* (a) Termination provisions of equipment for circuits rated 100 amperes or less,
|
||||
or marked for 14 AWG through 1 AWG conductors,
|
||||
shall be used only for one of the following:
|
||||
|
||||
|
||||
* (1) Conductors rated 60°C (140°F).
|
||||
|
||||
* (2) Conductors with higher temperature ratings,
|
||||
provided the ampacity of such conductors
|
||||
is determined based on the 60°C (140°F) ampacity of the conductor size used.
|
||||
|
||||
|
||||
* (3) Conductors with higher temperature ratings
|
||||
if the equipment is listed and identified for use with such conductors.
|
||||
|
||||
|
||||
* (4) For motors marked with design letters B, C, or D,
|
||||
conductors having an insulation rating of 75°C (167°F) or higher
|
||||
shall be permitted to be used,
|
||||
|
||||
Reference in New Issue