@@ -100,14 +100,14 @@ in excess of the temperature specified for the type of insulation involved.
|
||||
shall comply with the installation requirements
|
||||
of [[nfpa-70_334_nm-cable#Part II. Installation|Part II of Article 334]],
|
||||
excluding [[nfpa-70_334_nm-cable#334.80 Ampacity.|334.80]].
|
||||
|
||||
|
||||
* (2) Where more than two Type SE cables
|
||||
containing two or more current-carrying conductors in each cable
|
||||
are installed in contact with thermal insulation, caulk, or sealing foam
|
||||
without maintaining spacing between cables,
|
||||
the ampacity of each conductor shall be adjusted
|
||||
in accordance with [[nfpa-70_310_conductors_for_general_wiring#Table 310.15(C)(1) Adjustment Factors for More Than Three Current-Carrying Conductors|Table 310.15(C)(1)]].
|
||||
|
||||
|
||||
* (3) For Type SE cable with ungrounded conductor sizes 10 AWG and smaller,
|
||||
where installed in contact with thermal insulation,
|
||||
the ampacity shall be in accordance with 60°C (140°F) conductor temperature rating.
|
||||
@@ -122,7 +122,7 @@ in excess of the temperature specified for the type of insulation involved.
|
||||
where installed as exterior wiring,
|
||||
shall be installed in accordance with Part I of Article 225.
|
||||
The cable shall be supported in accordance with 334.30.
|
||||
|
||||
|
||||
* (2) Type USE cable installed as underground feeder and branch circuit cable
|
||||
shall comply with Part II of Article 340.
|
||||
|
||||
|
||||