@@ -414,21 +414,20 @@ All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles in the area
|
||||
* (8) Assisted living facilities
|
||||
|
||||
> [!info] Informational Note No. 1:
|
||||
> This requirement would include receptacles identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-
|
||||
2016, Wiring Devices — Dimensional Specifications.
|
||||
> This requirement would include receptacles identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2016, Wiring Devices — Dimensional Specifications.
|
||||
|
||||
> [!info] Informational Note No. 2:
|
||||
> Assisted living facilities are Institutional Use Group I-1 per IBC 2015.
|
||||
|
||||
> [!important] Exception to (1), (2), (3), (4), (5), (6), (7) and (8):
|
||||
> Receptacles in the following locations shall not be required to be tamper resistant:
|
||||
>
|
||||
>
|
||||
> * (1) Receptacles located more than 1.7 m (5 1⁄2 ft) above the floor
|
||||
>
|
||||
>
|
||||
> * (2) Receptacles that are part of a luminaire or appliance
|
||||
>
|
||||
>
|
||||
> * (3) A single receptacle, or a duplex receptacle for two appliances, located within the dedicated space for each appliance that, in normal use, is not easily moved from one place to another and that is cord-and-plug-connected in accordance with 400.10(A)(6), (A)(7), or (A)(8)
|
||||
>
|
||||
>
|
||||
> * (4) Nongrounding receptacles used for replacements as permitted in 406.4(D)(2)(a)
|
||||
|
||||
### 406.13 Single-Pole Separable-Connector Type.
|
||||
@@ -458,17 +457,17 @@ The use of single-pole separable connectors shall be performed by a qualified pe
|
||||
* (2) Line connectors are of the listed sequential-interlocking type so that load connectors are connected in the following sequence and that disconnection is in the reverse sequence:
|
||||
|
||||
* (a) Equipment grounding conductor connection
|
||||
|
||||
|
||||
* (b) Grounded circuit conductor connection, if provided
|
||||
|
||||
|
||||
* (c) Ungrounded conductor connection
|
||||
|
||||
* (3) A caution notice that complies with 110.21(B) is provided on the equipment employing single-pole separable connectors, adjacent to the line connectors, indicating that connections are to be performed in the following sequence and that disconnection is in the reverse sequence:
|
||||
|
||||
* (a) Equipment grounding conductor connectors
|
||||
|
||||
|
||||
* (b) Grounded circuit-conductor connectors, if provided
|
||||
|
||||
|
||||
* (c) Ungrounded conductor connectors
|
||||
|
||||
> [!info] Informational Note:
|
||||
|
||||