vault backup: 2026-03-30 22:54:00

This commit is contained in:
2026-03-30 22:54:00 -04:00
parent 3202306f62
commit ded28a372d
73 changed files with 212 additions and 155 deletions
+2 -2
View File
@@ -75,7 +75,7 @@ Where ground-fault circuit interrupter protection for personnel is supplied by p
> [!important] Exception:
> Where conditions of supervision and maintenance ensure that only qualified persons will service the installation, flexible cords or cables identified in Table 400.4 for hard usage or extra-hard usage shall be permitted in cable trays used only for temporary wiring. All cords or cables shall be installed in a single layer. A permanent sign shall be attached to the cable tray at intervals not to exceed 7.5 m (25 ft). The sign shall read
>
>
> CABLE TRAY FOR TEMPORARY WIRING ONLY
#### 518.3(C) Emergency Systems.
@@ -90,7 +90,7 @@ The fixed wiring methods shall be metal raceways, flexible metal raceways, nonme
> [!important] Exception:
> Fixed wiring methods shall be as provided in the following:
>
>
> * (1) Audio signal processing, amplification, and reproduction equipment --- Article 640
> * (2) Communications systems --- Chapter 8
> * (3) Class 2 and Class 3 remote-control and signaling circuits --- Article 725