# Fire Alarm
## Info
> [!info]
> See [[fire-alarm]] for information about fire alarm systems.
### Fire Command Center (FCC)
> [!info] Also Known As
> Emergency Command Center (ECC)
> Fire Alarm Command Center (FACC)
> Fire Alarm Command Room (FACR)
## Sequence
### 1. Preparation
1. Initial the OneNote
2. Read about the project specifications and construction type
3. Find Fire Alarm plans (if present)
4. Locate the following rooms:
* Fire Command Center (FCC)
* Generator Room
* Fire Pump Room
* Elevator Control Rooms
* Elevator Shafts
* Stairwells
### 2. Takeoff
#### Backbone
## Backbone
Put all backbone takeoff in the `Area` of the Fire Command Center.
Include [[sleeving]] as necessary.
Include [[sleeving-takeoff]] as necessary.
##### Fire Command Center
### Fire Command Center
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`HEAD END EQUIP`/`... HEAD END`
##### Generator Room
### Generator Room
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...`
##### Fire Pump Room
### Fire Pump Room
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...`
##### FACR to Elevator Shafts
### FACR to Elevator Shafts
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...`
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...`
Measure Length from the most distant points of the FACR and each shaft.
Input adder length to reach the bottom of the pit
(Minimum 15ft adder).
Input adder length to reach the bottom of the pit (Minimum 15ft).
```
| 1 shaft | 2 shafts |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
| || +--------+ +--------+ || | || +--------+ || +--------+ || |
| ||=======================|| | ||============||============|| |
| | |
```
> [!important] Counting Elevator Shafts
> Adjacent elevators may be in the same or parallel shafts.
> Count the shafts accordingly:
>
> ```
> | 1 shaft | 2 shafts |
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
> | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || |
> | || +--------+ +--------+ || | || +--------+ || +--------+ || |
> | ||=======================|| | ||============||============|| |
> | | |
> ```
##### FACR to Elevator Control Rooms
### FACR to Elevator Control Rooms
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...`
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...`
* Measure the Horizontal and Vertical Distance from the FACR to the ECR.
* Use Typicals for the vertical riser. (Ex// 10' per floor)
* Add [[sleeving]] as necessary.
* Use Typicals for the vertical riser. (10ft per floor)
##### FACR to Stairwells
### FACR to Stairwells
This is for the Flow/Tamper modules in the stairwells
> [!info]
> This is for the Flow/Tamper modules in the stairwells
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS ...`
* Measure from the furthest end of FACR to the furthest end of the stairwell to find length
##### Terminal Cabinets
### Terminal Cabinets
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`TERMINAL CABINET`/`ACE D ACCESSORY CABINET ENCLOSURE (2) 2" ...`
@@ -102,9 +82,9 @@ Horizontal:
Vertical:
* Use 10ft Riser in Typical
* Add [[sleeving]] as necessary.
* Add [[sleeving-takeoff]] as necessary.
##### Annunciator Panels
### Annunciator Panels
> [!info] Also Known As
> * Fire Alarm Annunciator (FAA)
@@ -114,27 +94,27 @@ Vertical:
* Measure from the Fire Command Room to FAA or Lobby
#### Devices
## Devices
##### Smoke Detectors
### Smoke Detectors
_Design Build:_
Count every stairwell at every level.
##### Pull Stations
### Pull Stations
_Design Build:_
Count every stairwell at every level
and every exterior exit.
##### Flow-Tamper Switches
### Flow/Tamper Switches
No free air. if wood frame, take off as EMT.
_Design Build:_
Count every stairwell at every level.
##### Magnetic Door Holders
### Magnetic Door Holders
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...`
@@ -142,7 +122,7 @@ _Design Build:_
Count every set of double doors.
(Typical of elevator lobbies and corridors)
##### Speaker Strobes
### Speaker Strobes
_Design Build:_
* Count every 75 ft,
@@ -152,7 +132,7 @@ _Design Build:_
* every elevator lobby,
* and every BOH room on the first floor and garage levels.
##### Firefighter Phone System
## Firefighter Phone System
* firefighter phone jacks
* fire warden station
@@ -163,16 +143,14 @@ Not related to responder radio.
`COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`COMMUNICATION DEVICES ...`/`...`
##### Fire Smoke Dampers (FSD's)
## Fire Smoke Dampers (FSD's)
Take off both FA
For each damper, take off both
`System` = "FA - Fire Alarm"
`COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`FSD ...`
and Electrical
and "EL - Electrical"
`COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS (UP TO 100A)`/.../...
### 3. Review
* [[sleeving]]