> however, this phrasing is ambiguous and non-universal.
|
||||
> Confirm with [[pdi-estimating#Bid Estimating|bid team]] on what must be included.
|
||||
|
||||
Determine which Systems and Codes are required:
|
||||
* _IBC/IECC 2021 or later:_ all fixtures 0-10V dimmable.
|
||||
|
||||
## PDI Lighting Control Configurations
|
||||
|
||||
### Stand Alone
|
||||
|
||||
0-10V dim -- "LV cable" is 2 conductor
|
||||
|
||||
Takeoff rough-in for switches and occupancy sensors
|
||||
* **Branch Length** = length of room
|
||||
|
||||
Takeoff the lighting control relay (DLM)
|
||||
|
||||
Takeoff an additional controller if receptacles are controlled
|
||||
|
||||
Takeoff homeruns to the DLM (one per controlled circuit)
|
||||
* Note: Not necessarily per room, several rooms may share a lighting circuit.
|
||||
|
||||
### Networked
|
||||
|
||||
#### Devices
|
||||
|
||||
##### Room Controllers
|
||||
|
||||
No room controllers are necessary,
|
||||
lighting zones are switched from a central lighting control panel (LCP)
|
||||
|
||||
##### Switches and Sensors
|
||||
|
||||
Takeoff rough-in for switches and occupancy sensors
|
||||
|
||||
??
|
||||
(only if time based; length based on closeness to sw/occ sensor)
|
||||
??
|
||||
|
||||
#### Homeruns
|
||||
|
||||
Takeoff 1 circuit homerun per lighting zone.
|
||||
|
||||
### Wattstopper
|
||||
|
||||
PDI default configuration
|
||||
|
||||
Takeoff (1) DLM controller for the fixtures
|
||||
and (1) Plug controller for the receptacle
|
||||
* If room has both dimmable fixtures and the controlled receptacle,
|
||||
only (1) DLM controller and (1) Plug controller
|
||||
* Use MC to cover room if drop
|
||||
* Use EMT if exposed or MC not permitted
|
||||
|
||||
Takeoff normal power to the controlled load
|
||||
* Add LV cable to fixture branch
|
||||
* Use 12/3 for receptacles
|
||||
|
||||
Takeoff rough-in for both the occ sensors and the LV switch
|
||||
* Free air if possible
|
||||
* **Length** = length of room
|
||||
|
||||
Cat cabling from the controllers on is likely provided by systems
|
||||
* Confirm with chief or quote language
|
||||
|
||||
#### Corridor Occupancy Sensors
|
||||
|
||||
If occupancy sensors are shown in the corridors:
|
||||
|
||||
Takeoff homerun back to the electric room
|
||||
|
||||
Takeoff (1) DLM controller for each electric room
|
||||
* Run free air down corridor
|
||||
|
||||
Takeoff rough-in for each occupancy sensor shown.
|
||||
|
||||
#### Network Bridge
|
||||
|
||||
Check systems quote to determine if network bridges are needed.
|
||||
|
||||
Takeoff (1) back box for every ==group of rooms you want together==
|
||||
|
||||
??
|
||||
If not showing, put one in every room with a controller
|
||||
??
|
||||
|
||||
#### Homeruns
|
||||
|
||||
Need a HR into the room for the controllers
|
||||
* Can link multiple controllers (aka rooms) together if you have the same circuit
|
||||
* Go back to closest electric room
|
||||
|
||||
## Custom Switch Boxes
|
||||
|
||||
For switch combinations not in `COMMON ASSEMBLIES`,
|
||||
|
||||