Determine which Systems and Codes are required:
|
||||
* _IBC/IECC 2021 or later:_ all fixtures 0-10V dimmable.
|
||||
|
||||
## PDI Lighting Control Configurations
|
||||
* `System` = "LV - Lighting Control System"
|
||||
|
||||
> [!important]
|
||||
> This section is currently not practical
|
||||
## Wall Switches
|
||||
|
||||
### Stand Alone
|
||||
> [!tip]
|
||||
> For switch combinations not in `COMMON ASSEMBLIES`,
|
||||
> create [[heating-designations]] based on the most similar.
|
||||
|
||||
0-10V dim --- "LV cable" is 2 conductor
|
||||
## Analog Controls
|
||||
|
||||
Takeoff rough-in for switches and occupancy sensors
|
||||
* **Branch Length** = length of room
|
||||
24V sensors. Typical of BOH spaces too large for wall sensors.
|
||||
|
||||
Takeoff the lighting control relay (DLM)
|
||||
1. `COMMON ASSEMBLIES`/`SWITCHES`/`CEILING OCC SENSOR ...`
|
||||
**Count:** as shown.
|
||||
|
||||
Takeoff an additional controller if receptacles are controlled
|
||||
2. `COMMON ASSEMBLIES`/`SWITCHES`/`POWER PACK FOR OCC SENSOR ...`
|
||||
**Count:** each circuit controlled by analog sensors. Minimum 1 per sensor.
|
||||
|
||||
Takeoff homeruns to the DLM (one per controlled circuit)
|
||||
* Note: Not necessarily per room, several rooms may share a lighting circuit.
|
||||
## Digital Controls
|
||||
|
||||
### Networked
|
||||
Applicable to all digital control systems
|
||||
(i.e. "Standalone" and "Centralized", wired and wireless)
|
||||
|
||||
"LV Cable" is [[twisted-pair-cable]]
|
||||
|
||||
#### Room Controllers
|
||||
|
||||
No room controllers are necessary,
|
||||
lighting zones are switched from a central lighting control panel (LCP)
|
||||
|
||||
#### Switches and Sensors
|
||||
|
||||
Takeoff rough-in for switches and occupancy sensors
|
||||
|
||||
??
|
||||
(only if time based; length based on proximity to switch or occupancy sensor)
|
||||
??
|
||||
|
||||
#### Homeruns
|
||||
|
||||
Takeoff 1 circuit homerun per lighting zone.
|
||||
|
||||
### Wattstopper
|
||||
|
||||
PDI default configuration
|
||||
|
||||
#### Room Controllers
|
||||
|
||||
For all rooms with dimmable fixtures
|
||||
and/or automatically controlled receptacles,
|
||||
take off (1) of either or both as appropriate.
|
||||
|
||||
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...`
|
||||
|
||||
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`REC PLUG CONTROLLER - ...`
|
||||
### General
|
||||
|
||||
Takeoff normal power to the controlled load
|
||||
* Add LV cable to fixture branch
|
||||
* Use \#12/3 for controlled receptacles
|
||||
* Use switched assemblies (\#12/3) for controlled receptacles
|
||||
|
||||
Takeoff rough-in for both the occ sensors and the LV switch
|
||||
#### Digital Sensors
|
||||
|
||||
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... LV SW - WALL ROUGH IN ...`
|
||||
1. `COMMON ASSEMBLIES`/`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/...
|
||||
* `... LV SW - WALL ROUGH IN ...`
|
||||
* `... SENSOR LOW VOLTAGE - ROUGH IN ...`
|
||||
|
||||
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`... SENSOR LOW VOLTAGE - ROUGH IN ...`
|
||||
### "Standalone" Systems
|
||||
|
||||
* Free air if possible
|
||||
* **Length** = length of room
|
||||
Room controllers distributed throughout controlled areas.
|
||||
|
||||
Cat cabling from the controllers on is likely provided by systems
|
||||
* Confirm with chief or quote language
|
||||
> [!important] "Room controllers"
|
||||
> As I have always understood it, and other manufacturers tend to agree,
|
||||
> a room controller _necessarily_ controls multiple zones
|
||||
> (otherwise "zone controller" would be better),
|
||||
> however PDI terminology is based on Wattstopper's.
|
||||
|
||||
#### Corridor Occupancy Sensors
|
||||
`COMMON ASSEMBLIES`/`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/...
|
||||
|
||||
If occupancy sensors are shown in the corridors:
|
||||
1. .../`DLM LTG RM CONTROLLER - ...`
|
||||
**Count:** each lighting control zone.
|
||||
|
||||
Takeoff homerun back to the electric room
|
||||
2. .../`REC PLUG CONTROLLER - ...`
|
||||
**Count:** each receptacle control zone.
|
||||
|
||||
Takeoff (1) DLM controller for each electric room
|
||||
3. `HEATING`/`Network Bridge - Blank 4SQ`
|
||||
**Count:** each controller.
|
||||
|
||||
`SWITCHES`/`LOW VOLTAGE SWITCHES & OCC SENSORS - ROUGH IN`/`DLM LTG RM CONTROLLER - ...`
|
||||
Coordinate with PDS to determine if necessary.
|
||||
|
||||
??
|
||||
Run free-air down corridor
|
||||
??
|
||||
4. `COMMON ASSEMBLIES`/`PDI BRANCH CKT HOME RUNS`/... (_without_ dimming cable)
|
||||
**Count:** each _circuit_.
|
||||
|
||||
* **Length** = Length of corridor
|
||||
### "Centralized" Systems
|
||||
|
||||
Takeoff rough-in for each occupancy sensor shown.
|
||||
Zones switched and dimmed from central lighting control panel (LCP).
|
||||
|
||||
#### Network Bridge
|
||||
1. `COMMON ASSEMBLIES`/`DISTRIBUTION`/`LIGHTING CONTROL PANEL INSTALLATION`/...
|
||||
|
||||
Check systems quote to determine if network bridges are needed.
|
||||
2. `COMMON ASSEMBLIES`/`PDI BRANCH CKT HOME RUNS`/... (_with_ dimming cable)
|
||||
**Count:** each _lighting control zone_.
|
||||
|
||||
Takeoff (1) back box for every ==group of rooms you want together==
|
||||
%%
|
||||
|
||||
??
|
||||
If not showing, put one in every room with a controller
|
||||
??
|
||||
### Somewhere In Between
|
||||
|
||||
#### Homeruns
|
||||
The dichotomy of [[#"Standalone" Systems]] vs. [[#"Centralized" Systems]]
|
||||
assumes zones will be controlled either
|
||||
(1) right next to the fixture or (2) in the nearest electrical room.
|
||||
|
||||
Need a HR into the room for the controllers
|
||||
* Can link multiple controllers (aka rooms) together if you have the same circuit
|
||||
* Go back to closest electric room
|
||||
I think just as common is 3--5 circuit controllers above the ceiling.
|
||||
|
||||
## Custom Switch Boxes
|
||||
1. `HEATING`/`Lighting Control Room Controller - n Circuit`
|
||||
**Count:** each controller.
|
||||
|
||||
For switch combinations not in `COMMON ASSEMBLIES`,
|
||||
create [[heating-designations]] based on the most similar.
|
||||
2. `COMMON ASSEMBLIES`/`PDI BRANCH CKT HOME RUNS`/... (_without_ dimming cable)
|
||||
**Length:** route to room.
|
||||
**Count:** each circuit.
|
||||
|
||||
%%
|
||||