title: Article 800 General Requirements for Communications Systems
|
||||
tags:
|
||||
- exclude-from-word-count
|
||||
- topic/construction/electrical
|
||||
- type/media/reference
|
||||
up: "[[nfpa-70_national-electric-code]]"
|
||||
---
|
||||
# Article 800 General Requirements for Communications Systems
|
||||
|
||||
## Part IV. Installation Methods Within Buildings
|
||||
|
||||
### 800.110 Raceways, Cable Routing Assemblies, and Cable Trays.
|
||||
|
||||
#### 800.110(A) Types of Raceways.
|
||||
|
||||
Wires and cables shall be permitted to be installed in raceways that comply with either 800.110(A)(1) or (A)(2).
|
||||
Medium-power network-powered broadband communications cables
|
||||
shall not be permitted to be installed in raceways that comply with 800.110(A)(2).
|
||||
|
||||
##### 800.110(A)(1) Raceways Recognized in Chapter 3.
|
||||
|
||||
Wires and cables shall be permitted to be installed in any raceway included in Chapter 3.
|
||||
The raceways shall be installed in accordance with the requirements of Chapter 3.
|
||||
|
||||
##### 800.110(A)(2) Communications Raceways.
|
||||
|
||||
Wires and cables shall be permitted to be installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways selected in accordance with Table 800.154(b),
|
||||
listed in accordance with 800.182,
|
||||
and installed in accordance with 800.113 and 362.24 through 362.56,
|
||||
where the requirements applicable to [[nfpa-70_362_ent|electrical nonmetallic tubing (ENT)]] apply.
|
||||
|
||||
##### 800.110(A)(3) Innerduct for Communications Wires and Cables, Coaxial Cables, or Network-Powered Broadband Communications Cables.
|
||||
|
||||
Listed plenum communications raceways,
|
||||
listed riser communications raceways,
|
||||
and listed general-purpose communications raceways
|
||||
selected in accordance with Table 800.154(b)
|
||||
shall be permitted to be installed as innerduct
|
||||
in any type of listed raceway permitted in Chapter 3.
|
||||
|
||||
#### 800.110(B) Raceway Fill.
|
||||
|
||||
The raceway fill requirements of Chapters 3 and 9
|
||||
shall apply to medium-power network-powered broadband communications cables.
|
||||
|
||||
#### 800.110(C) Cable Routing Assemblies.
|
||||
|
||||
Cables shall be permitted to be installed in plenum cable routing assemblies,
|
||||
riser cable routing assemblies,
|
||||
and general-purpose cable routing assemblies
|
||||
selected in accordance with Table 800.154(c),
|
||||
listed in accordance with 800.182,
|
||||
and installed in accordance with 800.110(C)(1) and (C)(2) and 800.113.
|
||||
|
||||
##### 800.110(C)(1) Horizontal Support.
|
||||
|
||||
Cable routing assemblies shall be supported where run horizontally
|
||||
at intervals not to exceed 900 mm (3 ft) and at each end or joint,
|
||||
unless listed for other support intervals.
|
||||
In no case shall the distance between supports exceed 3 m (10 ft).
|
||||