@@ -218,19 +218,19 @@ Where a feeder is supplied from a dc system operating at more than 60 volts, eac
|
||||
* (a) Positive Polarity, Sizes 6 AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means:
|
||||
|
||||
* (1) A continuous red outer finish
|
||||
|
||||
|
||||
* (2) A continuous red stripe durably marked along the conductor's entire length on insulation of a color other than green, white, gray, or black
|
||||
|
||||
|
||||
* (3) Imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.8(B)
|
||||
|
||||
|
||||
* (4) An approved permanent marking means such as sleeving or shrink-tubing that is suitable for the conductor size, at all termination, connection, and splice points, with imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black
|
||||
|
||||
* (b) Negative Polarity, Sizes 6 AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means:
|
||||
|
||||
* (1) A continuous black outer finish
|
||||
|
||||
|
||||
* (2) A continuous black stripe durably marked along the conductor's entire length on insulation of a color other than green, white, gray, or red
|
||||
|
||||
|
||||
* (3) Imprinted minus signs (--) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.8(B)
|
||||
|
||||
|
||||
* (4) An approved permanent marking means such as sleeving or shrink-tubing that is suitable for the conductor size, at all termination, connection, and splice points, with imprinted minus signs (--) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red
|
||||
|
||||