@@ -406,22 +406,22 @@ Nonshielded, ozone-resistant insulated conductors with a maximum phase-to-phase
|
||||
|
||||
> [!important] Exception No. 1:
|
||||
> Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 2400 volts under the following conditions:
|
||||
>
|
||||
>
|
||||
> * (1) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking.
|
||||
>
|
||||
>
|
||||
> * (2) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath.
|
||||
>
|
||||
>
|
||||
> * (3) Insulation and jacket thicknesses shall be in accordance with Table 311.10(B).
|
||||
|
||||
> [!important] Exception No. 2:
|
||||
> Nonshielded insulated conductors listed by a qualified testing laboratory shall be permitted for use up to 5000 volts to replace existing nonshielded conductors, on existing equipment in industrial establishments only, under the following conditions:
|
||||
>
|
||||
>
|
||||
> * (1) Where the condition of maintenance and supervision ensures that only qualified personnel install and service the installation.
|
||||
>
|
||||
>
|
||||
> * (2) Conductors shall have insulation resistant to electric discharge and surface tracking, or the insulated conductor(s) shall be covered with a material resistant to ozone, electric discharge, and surface tracking.
|
||||
>
|
||||
>
|
||||
> * (3) Where used in wet locations, the insulated conductor(s) shall have an overall nonmetallic jacket or a continuous metallic sheath.
|
||||
>
|
||||
>
|
||||
> * (4) Insulation and jacket thicknesses shall be in accordance with Table 311.10(B).
|
||||
|
||||
> [!info] Informational Note:
|
||||
|
||||