@@ -56,7 +56,7 @@ Class 2 and Class 3 circuit conductors in compartments, enclosures, device boxes
2. The circuit conductors operate at 150 volts or less to ground and also comply with one of the following:
* a. The Class 2 and Class 3 circuits are installed using Type CL3, CL3R, or CL3P or permitted substitute cables, provided these Class 3 cable conductors extending beyond the jacket are separated by a minimum of 6 mm (0.25 in.) or by a nonconductive sleeve or nonconductive barrier from all other conductors.
* b. The Class 2 and Class 3 circuit conductors are installed as a Class 1 circuit in accordance with 725.41.
#### 725.136(E) Enclosures with Single Opening.