--- id: aliases: [] tags: - authorship/original - destiny/permanent - topic/construction/electrical - type/encyclopedia-entry - status/incomplete title: Medium Voltage --- # Medium Voltage "Medium voltage" refers to voltage systems greater than 600V. ## Insulation Level > [!example] > > > [!cite] 343 Madison Avenue Project Specifications, emphasis added > > 2.2 MEDIUM VOLTAGE CABLES (CON EDISON) > > * ... > > * H. Construction > > * ... > > * 3. Insulation > > * ... > > * c. _The minimum average insulation thickness shall be not less than 175 mils._ > > The minimum thickness at any cross-section of the insulation > > shall be not less than 90% of the specified minimum average thickness. > > In this case 100% insulation level is appropriate for 15kV conductors. [[nfpa-70_311_mv-conductors#311.10(B) Thickness of Insulation and Jacket for Nonshielded Insulated Conductors.]] | Voltage Rating | Insulation Level | Insulation Thickness | | --------------:| ----------------:| --------------------:| | 5kV | 100% | 90 mils | | 5kV | 133% | 115 mils | | 5kV | 173% | 140 mils | | 8kV | 100% | 115 mils | | 8kV | 133% | 140 mils | | 8kV | 173% | 175 mils | | 15kV | 100% | 175 mils | | 15kV | 133% | 220 mils | | 15kV | 173% | 260 mils | | 25kV | 100% | 260 mils | | 25kV | 133% | 320 mils | | 25kV | 173% | 420 mils | | 35kV | 100% | 345 mils | | 35kV | 133% | 420 mils | | 35kV | 173% | 580 mils |