--- id: 2026-03-25T08:14:59-0400 title: 2026-03-25 08:14:59 tags: - status/draft - occupational/takeoff date-created: 2026-03-25T08:14:59-04:00 daily: "[[2026-03-25]]" --- # 2026-03-25 08:14:59 ## "Free-Air Per Code" Direction for [[telecom-takeoff]] and [[low-voltage-takeoff]] concerning the proper interpretation of "free-air per code" as used by [[pdi-bid-estimating|Bid]] to qualify our scope. Relevant to [[charlotte-south-end-hotel]]. > [!quote] Charlotte South End Proposal 2025-12-12 Ex. B Notes > * All Fire Alarm and Low Voltage cabling > is to \[be\] installed via free-air > in all areas excepted \[sic.\] by code Strictly speaking, requirements for communications wiring (governed by [[nfpa-70_national-electric-code#Chapter 8 Communications Systems|NEC Chapter 8]]) are minimal. > [!quote] [[joel-jansen]] 2026-03-24 (pp.) > If rough-in for Telecom or a Low Voltage system is included, > even if qualified as "free-air per code" or similar, > always provide backboxes and conduit stub-ups for outlets > in other than units[^1]. Joel confirmed this direction is not region specific. [^1]: Where "free-air per code" applies to units, conduit and backboxes should never be provided for Telecom or LV. See [[2026-04-01_13-24-18#Unit Telecom/LV Outlets Where "Free-Air Per Code"]]