--- title: Electrical Takeoff tags: - occupational/takeoff - status/draft - type/guide up: "[[takeoff-scripts]]" aliases: - electrical takeoff --- # Electrical Takeoff > [!important] > Complete [[pre-takeoff-research]], > including [[conest-wiring-method-selection]] and [[conest-wiring-device-research]], > before beginning takeoff. > [!tip] > Use [[heating-designations]] for uncertain scope. ## Garage In conventional slab garages, use ENT and PVC as permitted. In precast slab garages, use EMT. ## Receptacles > [!important] > Receptacle symbols are not standard. > Always check the electrical legend. ## Floor Boxes `COMMON ASSEMBLIES`/`FLOOR BOXES`/... ### Poke-Thru's Use suitable floor box assembly, delete floor box items, add `ITEM DATABASE`/`WIRING & SYSTEM DEVICES`/`FLOOR BOXES & FITTTINGS`/`GENERIC - FLOOR BOXES & ACCESS`/`POKE-THRU W/ DUPLEX RECEPTACLE` ## Homeruns ### Lighting Homeruns > [!info] Breakdowns > * `Area` = "XX - Level XX Building" > * `Phase` = "Building - Back of House (BOH)" Takeoff homeruns in Building breakdowns, even where serving Amenity spaces. ## Mechanical Connections ### General `COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/... When using length-based assemblies use adders per [[feeders-takeoff]]. %% TODO #### PVC Connection Assemblies #### Flex [[conest-wiring-method-selection#Liquidtight Flex]] %% ### Stair Pressurization Fans Assume branch circuit conductors must be protected per [[fire-resistive-wiring-methods-takeoff]]. ### Roof Mounted Equipment #### Unit Condensing Units ##### Homeruns > [!info] Breakdowns > * `Area` = _Match unit_ .../`CONDENSOR HOME RUNS` * **Horizontal:** Distance from load center to FCU. (~50ft expected)[^1] * **Vertical:** floor-to-floor distance from FCU to CU [^1]: [[2026-05-04_14-57-49#Unit Condensing Units]] | Level | Horizontal | Vertical | Length | | :------- | ---------: | -------: | -----: | | Level 01 | 150 | 40 | 190 | | Level 02 | 150 | 30 | 180 | | Level 03 | 150 | 20 | 170 | | Level 04 | 150 | 10 | 160 | ##### Connections > [!info] Breakdowns > * `Area` = _Match CU (usually roof)_ .../`CU CONDENSER SLEEVE W/ FLEX - NO HMRN WIRE` `NO SLEEVE`: Routed through a "doghouse" (a large weatherproof opening) with several other feeds. Used where drilling openings for individual sleeves would be impractical. `PVC SLEEVE`, `EMT SLEEVE`: Routed up through the roof, (optionally through a disconnect) with flex to the equipment. #### Equipment Racks Max 20 disconnects per rack `DISTRIBUTION`/`TRAPEZE RACK SUPPORT ...`/... ## Trash Chute 1. **Horizontal:** `COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS ...`/... * **Length** = Length per drawings, 100ft if not shown. 2. **Vertical (Riser):** * `Area` = "Typical - Building All Levels" Takeoff: `COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`TRASH CHUTE RISER CIRCUIT...` * **Length** = average floor to floor height ## Fire/Smoke Dampers [[fire-alarm-takeoff#Fire/Smoke Dampers (FSD's)]] ## Clubline Raceway [Raceway Systems - CRG](https://crg.us.com/products/raceway-systems/) Clubline Raceway, also called CRG Raceway, is a glorified cable management trough. It is not a [[nfpa-70_376|wireway]], so conductors must be run in a [[nfpa-70_national-electric-code#Chapter 3 Wiring Methods and Materials|Chapter 3]] wiring method. Count receptacles normally, using ==surface-mount EMT assemblies==. Create a temporary item for the raceway itself.