--- title: Lightning Protection Takeoff tags: - occupational/takeoff - status/draft - type/guide up: "[[takeoff-scripts]]" aliases: - lightning protection takeoff --- # Lightning Protection Takeoff > [!info] > See [[lightning-protection]] for more on lightning protection systems. > [!important] ConEst Scope > Lightning protection takeoff may or may not be necessary, > see proposal on [[pdi-bpm|BPM]]. > Only takeoff if LP is included in the base bid. ### Subcontractors Find lightning protection subcontractor quotes on BPM, search for direction on downlead counts, total length, and conduit size > [!example] > Contractor to furnish 1,980' of 1" PVC conduit and pull string > [!tip] > While you have the quotes open, > put the costs in the Subcontractors tab in [[accubid|Accubid]]. If no quote is available: * **Downlead locations** = building corners + additional locations such that downlead spacing is not greater than 100ft * Minimum 10 locations for High-rise * **Total downlead conduit length** = building height * downlead locations * **Conduit size** = 1-1/4" ### Takeoff > * `Area` = "01 - Lightning Protection Building" > * `Phase` = "Building - BOH, Storage & Common" > * `System` = "LPT - Lightning Protection" > * `BidItem` = "3 - Building" * Takeoff: `COMMON ASSEMBLIES`/`PDI EMPTY CONDUIT`/`PVC ASSEMBLIES`/`* CONDUIT - PVC40` * **Length** = total downlead conduit length * **Count** = downlead locations * Add item: `ITEM DATABASE`/`BOXES & CABINETS`/`JUNCTION BOXES AND INDUSTRIAL CABINETS`/ `BOXES - HNGD CVR - PAINTED STEEL - NEMA 1`/` 6x 4x 4" BOX HNGD CVR - NEMA 1`