--- id: aliases: [] title: 2026-02-11 12:12:16 tags: - authorship/original - destiny/permanent - status/draft - type/periodic/timestamped daily: "[[2026-02-11]]" dg-publish: true monthly: "[[2026-02]]" quarterly: "[[2026-Q1]]" weekly: "[[2026-W07]]" yearly: "[[2026]]" --- # 2026-02-11 12:12:16 Hello Team, Below is a comprehensive list of means & methods for {Project Name}. Please confirm you have received this email and respond with any questions or comments. * **Takeoff Request Stage:** Full Takeoff * **Delivery Method:** Plans & Specs * **Document Stage:** Permit * **Drawings Date:** 2025-12-05 * **Project Manual Date:** 2025-10-29 * **Proposal Date:** 2026-02-11 ## Project Specification Callouts * **Conduit:** * EMT Fittings: Set-screw. _---Spec 260533.13 (p. 1423)_ * **Wire:** * Material: Aluminum 100A and larger * Acceptable Manufacturers: * Alpha Wire; Brand of Belden, Inc. * Belden Inc. * Cerro Wire LLC * Encore Wire Corporation * General Cable; Prysmian Group North America * Okonite Company * Service Wire Co. * Southwire Company, LLC * WESCO * **MC Cable:** * Application: * Acceptable Manufacturers: * AFC Cable Systems; Atkore International * Alpha Wire; Brand of Belden, Inc. * Belden Inc. * Cerro Wire LLC * Encore Wire Corporation * General Cable; Prysmian Group North America * Okonite Company * Southwire Company, LLC * WESCO * **Steel Box Depth:** * Telecom: 2-1/8" _---Spec 270500 (p. 1673)_ * Security: 2-1/8" _---Spec 280500 (p. 1753)_ * Other Applications: Not specified * **Floor Boxes:** * Box Material: * Cover Material: * **Wiring Devices:** * Units: * BOH/Common Areas: * **Switchboards:** * Acceptable Manufacturers: _---Spec 262413 (p. 1502)_ * ABB, Electrification Business * Eaton * Siemens Industry, Inc., Energy Management Division * Square D; Schneider Electric USA * General Electric * Bus Material: Aluminum _---Spec 262413 (p. 1503)_ * Breaker Types: * AIC Ratings: * **Panelboards:** * Acceptable Manufacturers: _---Spec 262413 (p. 1514-1515)_ * ABB, Electrification Business * Eaton * Siemens Industry, Inc., Energy Management Division * Square D; Schneider Electric USA * Bus Material: * Breaker Types: * ACI Ratings: * **Transformers:** * Winding Material: Aluminum _---Spec 262213 (p. 1495)_ * K-Rating: Not specified * **Generator:** (1) 600kW Diesel * Enclosure Specs: Level 2 Sound Attenuating Weatherproof Enclosure. _---Dwg. E014_ * Remote Tank: None shown or specified. * Tank Size: 24hrs at 100% load. _---Spec 263213.13 (p. 1604)_ * Load Banks: Internal, 50% load. _---Dwg. E014, Spec 263213.13 (p. 1608)_ * Acceptable Manufacturers: _---Spec 263213.13 (p. 1600)_ * Caterpillar, Inc.; Electric Power Division * Cummins Power Generation * Generac * Hipower Systems * Kohler Power Systems * Rolls-Royce Solutions America Inc ## Project Drawing/Detail Callouts * **Describe conflicts between drawings / proposal:** * **Cost drivers in details not shown elsewhere on plans:** * ## PDI System Execution Plan * **Primaries:** Conduit and wiring excluded. _---Proposal 2026-01-22, Ex. B, Exclusions, Line 27_ * **Secondaries:** Wiring excluded. _---Proposal 2026-01-22, Ex. B, Exclusions, Line 28_ * **Feeders:** * **Unit Subfeeds:** EMT-SS, MC OH; PVC UG * **Units:** * **Telecom:** * **EV Chargers:** * **Fire Alarm:** Devices PVC in-slab, Risers EMT. * **DAS:** System included * **Low Voltage:** Free-air where allowed by code. ## Lighting Control * **Scope:** * **Area:** * BOH: * Corridor: * Amenity: * Site/Landscape: * Garage Entry Point * Office: ## Tasks/Quotes Needed for WBS * Electrical VDC * Coordination Study Thank you,