--- id: aliases: [] tags: - destiny/fleeting - status/incomplete - topic/electrical - type/encyclopedia title: Conductor Sizing --- # Conductor Sizing Conductors are sized to be suitable for the load, overcurrent protection is sized to protect the conductors. ## "The 80% Rule" "The 80% Rule" is a rule of thumb referring to a common convention of several articles including: * [[nfpa-70_210_branch-circuits#210.19(A)(1) General.]] * [[nfpa-70_215_feeders#215.2(A)(1) General.]] * [[nfpa-70_430_motors#430.22 Single Motor.]] which paraphrased states: > ... the minimum conductor size shall have an ampacity > not less than the noncontinuous load > plus 125 percent of the continuous load When the rule is repeated, the noncontinuous load is ignored and it is stated that conductors are suitable for 80% their listed rating, since 80% is the reciprocal of 125%. ## Branch Circuits ### Receptacle Branch > [!important] > There is no maximum number of receptacles per circuit _in any occupancy_. It is a common misconception that the limit can be calculated with a formula like $$ \frac{1.25(180VA)}{120V} = 1.875A, \quad \frac{20A}{1.875A} = 10.\bar{6} $$ but the 180VA per yoke load specified in [[nfpa-70_220_load-calculations#220.14(I) Receptacle Outlets.|220.14(I)]] is specifically for calculating service and feeder sizing. Per [[nfpa-70_210_branch-circuits#210.19(A)(1) General.|210.19(A)(1)]] a receptacle branch circuit's load is the load of the equipment intended to be served by it. Where general-use receptacles are provided without specific equipment in mind, circuits will be engineered at the minimum load. If a receptacle circuit's load is a whole multiple of 180VA there's a good chance that's the number of devices, or at least was at some point in the design. ## Feeders > [!cite] NEC Article 250 (emphasis added) > ### 250.122 Size of Equipment Grounding Conductors > #### (A) General. > Copper, aluminum, or copper-clad aluminum > equipment grounding conductors of the wire type > shall not be smaller than shown in Table 250.122, > but in no case shall they be required to be larger > than the circuit conductors supplying the equipment... Apparently in the 2026 NEC First Draft Meetings, Code Making Panel 5 clarified that the equipment grounding conductor (EGC) never needs to be larger than the largest ungrounded conductor in any raceway when installed in parallel. I can not find a source to verify this. Statements from other reputable sources including Mike Holt are in contradiction to this idea. *** Given a minimum ampacity, find all valid configurations. > [!cite] NEC Article 310 (emphasis added) > #### 310.10(H) Conductors in Parallel. > ##### (1) General. > Aluminum, copper-clad aluminum, or copper conductors, > for each phase, polarity, neutral, or grounded circuit > shall be permitted to be connected in parallel > (electrically joined at both ends) > _only in sizes 1/0 AWG and larger_ > where installed in accordance with 310.10(H)(2) through (H)(6). Rank by total cost of install. ### Complexity to Ignore #### Conductor Material Tinned copper and copper-clad aluminum conductors can be assumed out of scope. ### Complexity to Respect #### Equipment Grounding Conductor Material Wire and EGC conductors are usually assumed to match, but it is sometimes necessary to use a copper EGC with aluminum wires, either for spec requirements or conduit fill considerations. ## Voltage Drop > [!info] Ohm's Law > > $$ > V = I \times R, \quad R = \frac{V}{I}, \quad I = \frac{V}{R} > $$ ### Step 1: Effective Impedance $Z$ $$ Z = R \cos(\theta) + X \sin(\theta) $$ where * $Z$ = Effective impedance * $R$ = AC resistance * $X$ = Reactance * $\theta$ = Power factor angle = $\arccos(PF)$ #### Parallel Runs The equivalent resistance of parallel resistances is given by $$ \frac{1}{R_{\text{eq}}} = \frac{1}{R_1} + \frac{1}{R_2} + \frac{1}{R_3} + \dots + \frac{1}{R_n} $$ For $n$ parallel resistances of value $R$ $$ \begin{align*} \frac{1}{R_{\text{eq}}} &= n \times \left(\frac{1}{R}\right) \\ &= \frac{n}{R} \\ R_{\text{eq}} &= \frac{R}{n} \end{align*} $$ ### Step 2: Voltage Drop > [!important] > This section assumes a 3-phase > 208Y/120V or 480Y/277V voltage system > [!info] 3-Phase Voltage > > $$ > V_{LL} = \sqrt{3} \times V_{LN}, \quad V_{LN} = \frac{V_{LL}}{\sqrt{3}} > $$ 3% allowable voltage drop for a 120V line-to-neutral load: $$ \text{Max} \Delta V = 0.03 \times 120 \text{V}_{LN} = 3.6 \text{V}_{LN} $$ 3% allowable voltage drop for a 208V line-to-line load: $$ \text{Max} \Delta V = 0.03 \times 208 \text{V}_{LL} = 6.24 \text{V}_{LL} $$ #### Line to Neutral Loads $$ \Delta V_{LN} = I \times Z \times 2L $$ #### Line to Line Loads $$ \Delta V_{LL} = \sqrt{3} \times \left( I \times Z \times 2L \right) $$ #### 3-Phase Loads $$ \Delta V_{3\phi} = \sqrt{3} \times \left( I \times Z \times L \right) $$ where * $\Delta V$ = Voltage drop in volts ($V$) * $I$ = Current in amperes ($A$) * $L$ = Length of wire one way in feet ($\text{ft}$) > [!important] > "Current" is not the OCPD rating, > but the actual load. *** It is often more useful to know the maximum length a certain wiring configuration is suitable for. $$ L = \frac{ \Delta V }{ I \times M } \times \frac{1}{Z} $$ ## Transformers $$ I = \frac{S}{ \sqrt{3} \times V \times E } $$ * $I$ = nameplate current rating * $S$ = nameplate kVA rating * $V$ = feeder voltage * $E$ = efficiency ## Motors 1 electric horsepower = 746 watts full-load current (FLC) / full-load amperes (FLA) minimum circuit ampacity (MCA) $$ \text{MCA} = 1.25 \times \text{FLC} $$