# Lightning Protection ## Info Two Types: - Protection \$\$\$ - Prevention \$ - ESE (EARLY STREAMER EMISSIONS) ## Estimate Scope May or may not be included, see proposal on [[bpm|BPM]] ### Subcontractors Find lightning protection subcontractor quotes on BPM > [!tip] > While you have them open, put the quote costs in Accubid. Search the quotes for direction on downlead counts, total length, and conduit size > [!example] > Contractor to furnish 1,980' of 1" PVC conduit and pull string If no quote is available: - **Downlead locations** = building corners + additional locations such that downlead spacing is not greater than 100ft - Minimum 10 locations for High Rise - **Total downlead conduit length** = building height * downlead locations - **Conduit size** = 1-1/4" ### Takeoff ``` Area = "Lightning Protection" // confirm Phase = "Building - BOH, Storage & Common" System = "LPT - Lightning Protection" BidItem = "3 - Building" ``` - Takeoff: `COMMON ASSEMBLIES`/`PDI EMPTY CONDUIT`/`PVC ASSEMBLIES`/`* CONDUIT - PVC40` - **Length** = total downlead conduit length - **Count** = downlead locations - Add item: `ITEM DATABASE`/`BOXES & CABINETS`/`JUNCTION BOXES AND INDUSTRIAL CABINETS`/ `BOXES - HNGD CVR - PAINTED STEEL - NEMA 1`/` 6x 4x 4" BOX HNGD CVR - NEMA 1`