--- id: aliases: [] tags: - destiny/fleeting - status/incomplete - topic/construction/electrical - type/encyclopedia - authorship/original title: Conductor Sizing --- # Conduit Sizing Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables | Number of Conductors and/or Cables | Cross-Sectional Area (%) | | ---------------------------------- | ------------------------ | | 1 | 53 | | 2 | 31 | | Over 2 | 40 | > [!info] Informational Note No. 1: > Table 1 is based on common conditions of proper cabling and alignment of conductors > where the length of the pull and the number of bends are within reasonable limits. > It should be recognized that, for certain conditions, > a larger size conduit or a lesser conduit fill should be considered. > [!info] Informational Note No. 2: > When pulling three conductors or cables into a raceway, > if the ratio of the raceway (inside diameter) > to the conductor or cable (outside diameter) > is between 2.8 and 3.2, jamming can occur. > While jamming can occur when pulling four or more conductors or cables into a raceway, > the probability is very low.