--- id: aliases: - das tags: - destiny/permanent - occupational/takeoff/standalone-systems - status/draft - type/guide - authorship/original title: Distributed Antenna Systems (DAS) --- # Distributed Antenna Systems (DAS) ## Info ### Emergency Responder Radio Communication Systems (ERRCS) Relevant Standard: NFPA 1225 ### Cellular Systems Less common than ERRCS are "cellular DAS" systems ## Sequence ### 1. Preparation Complete [[fire-alarm-takeoff]] preparation and takeoff. ### 2. Takeoff #### FACR to Every Elev. Shaft `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO ELEV PIT = ...` Match Fire Alarm takeoff Length and Count #### FACR to Every Staircase `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO STAIRWELL = ...` Match Fire Alarm takeoff Length and Count #### Stairwell Riser Every 2 Floors `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`STAIRWELL RISER EVERY 2 FLRS = 1 1/2" EMT (20') W/ 16X16X6 BOX` Create a Stairwell typical on every other floor #### FACR to Electric Room `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`FACR TO 2HR-RATED RM = 2" PVC40` Match Fire Alarm takeoff Length #### Electric Room Riser to Every Floor `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`2HR-RATED RM RISER TO EVERY FLR = 2" EMT (15') W/ 16X16X6 BOX` Takeoff in every Electric Room #### Top 2H Rated Room To Roof `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`DAS ASSEMBLIES`/`TOP 2HR RATED RM TO ROOF = 2" EMT W/ RMC WEATHERHEAD & IMC STUB` Use 15' or Height of ceiling on last building level #### Horizontal CORRIDORS EMT OH = 1 1/2" EMT W/ 16X16X6 BOX EVERY 80' CA.28.31.23 CORRIDORS DECK = 1 1/2" PVC40, STUBBY, FLEX W/ 16X16X6 BOX EVERY 80' CA.28.31.21 1-1/2 through corridors w/ 16x16x6 J-Box Length for every corridor/garage ### 3. Review