--- id: aliases: [] tags: - occupational/systems/fire-alarm - type/guide --- # Fire Alarm ## Info ## Sequence ### 1. Estimate preparation 1. Initial the OneNote 2. Read about the project specifications and construction type 3. Find Fire Alarm plans (if present) 4. Locate the following rooms: * Fire Command Center (FCC) * Generator Room * Fire Pump Room * Elevator Control Rooms * Elevator Shafts * Stairwells ### 2. Takeoff #### Fire Command Center `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`HEAD END EQUIP`/`... HEAD END` #### Generator Room `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`GENERATOR ROOM ...` #### Fire Pump Room `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FIRE PUMP ROOM ...` #### FACR to Elevator Shafts `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV SHAFT ...` `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV SHAFT ...` Measure Length from the most distant points of the FACR and each shaft. Input adder length to reach the bottom of the pit (Minimum 15ft adder). ``` | 1 shaft | 2 shafts | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | ||=======================|| | ||============||============|| | | | | ``` #### FACR to Elevator Control Rooms `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`ELEV CONTROL ROOM ...` `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO ELEV CONTROL RM ...` * Measure the Horizontal and Vertical Distance from the FACR to the ECR. * Use Typicals for the vertical riser. (Ex// 10' per floor) * Add [[sleeving]] as necessary. #### FACR to Stairwells This is for the Flow/Tamper modules in the stairwells `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES`/`FACR TO STAIRWELLS ...` * Measure from the furthest end of FACR to the furthest end of the stairwell to find length #### Terminal Cabinets `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`TERMINAL CABINET`/`ACE D ACCESSORY CABINET ENCLOSURE (2) 2" ...` * *Garden Style, High Density:* (2) 1"C * *High Rise:* (2) 2"C Horizontal: * Measure from the Fire Command room to all electrical rooms Vertical: * Use 10ft Riser in Typical * Add [[sleeving]] as necessary. #### Annunciator Panels > [!info] Also Known As > * Fire Alarm Annunciator (FAA) > * Fire Alarm Annunciator Panel (FAAP) `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`ANNUNCIATORS`/`REMOTE SERIAL ANNUNCIATOR ...` * Measure from the Fire Command Room to FAA or Lobby #### Smoke Detectors _Design Build:_ Count every stairwell at every level. #### Pull Stations _Design Build:_ Count every stairwell at every level and every exterior exit. #### Flow-Tamper Switches No free air. if wood frame, take off as EMT. _Design Build:_ Count every stairwell at every level. #### Magnetic Door Holders `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`INDICATING DEVICES WITH WIRE - ...`/`MAGNETIC DOOR HOLDER - ...` _Design Build:_ Count every set of double doors. (Typical of elevator lobbies and corridors) #### Speaker Strobes _Design Build:_ * Count every 75 ft, * measure with circles on Bluebeam * or divide relevant SF area by 4415 * $\pi(\frac{75}{2})^2 \approx 4415$ * every elevator lobby, * and every BOH room on the first floor and garage levels. #### Firefighter Phone System * firefighter phone jacks * fire warden station * fire phone cabinet Communicates directly with FACR. Not related to responder radio. `COMMON ASSEMBLIES`/`FIRE ALARM & DAS SYSTEMS`/`COMMUNICATION DEVICES ...`/`...` #### Fire Smoke Dampers (FSD's) Take off both FA `COMMON ASSEMBLIES`/`MISC ASSEMBLIES`/`FSD ...` and Electrical `COMMON ASSEMBLIES`/`MECHANICAL CONNECTIONS (UP TO 100A)`/.../... ### 3. Extension (Review and Checking) * Sleeving