--- id: aliases: [] tags: - destiny/permanent - occupational - status/incomplete - type/guide title: Pre-Takeoff Research --- # Pre-Takeoff Research ## Requirement Precedence In case of conflict: Requirements of the plans and specs are superseded by the terms of our proposal, which are superseded by specific direction from the bid team. ## Wiring Method Selection See [[wiring-method-selection]]. ## Voltage Drop Unless explicitly stated in the plans or specs, conductors are to be sized according to the relevant schedule, _without respect for voltage drop_. ### Feeders and Unit Subfeeds ### Branch Circuits If voltage drop is to be considered in takeoff, Use the table provided in the drawings. If no table is provided, use the following: | Wire Size | Max Length | | ---------:| ----------:| | #12 | 100ft | | #10 | 200ft | | #8 | >200ft | ## Wiring Device Selection Wiring devices and their wall plates are a common target of [[gold-plating]]. * Device grade: commercial < specification * Minimum rating for general-use receptacles: N5-15R < N5-20R * Device form-factor: Duplex/toggle < Decora * Device cover plate material: Plastic < nylon < aluminum < stainless steel * Device cover plate size: standard < mid-size < oversize "jumbo" * Device cover plate attachment: Standard < screwless * Floor box material: Steel < cast iron * Floor box cover plate material: plastic < brass < aluminum > [!info] Search Terms Relevant to Wiring Device Selection > * "Decora" > [!info] Example Specs Relevant to Wiring Device Selection[^1] > * 26XXXX - Wiring Devices > * 26XXXX - Boxes And Covers For Electrical Systems > * 26XXXX - Lighting Control Devices > * 26XXXX - Network Lighting Controls [^1]: Specification section titles and scope may vary greatly between projects. The examples provided are not an exhaustive list. ## Emergency Systems 1. Find Fire Alarm plans (if present) 2. Locate the following rooms: * Fire Command Center (FCC) * Generator Room * Fire Pump Room * Elevator Control Rooms * Elevator Shafts * Stairwells