Wiring Methods Selection

Seek to use the cheapest method, as determined by Senior Construction Estimator and Database Administrator, as allowed for the situation.

!pre-takeoff-research#Requirement Precedence

By Construction Type

See ibc-construction-types for more info.

Construction Types I, II

Nonmetallic-sheathed cables (NM, SE, etc.) are not fire code permissible in these types.

PVC < MC < EMT < IMC < RMC

Construction Types III, IV, V

NM/SE < PVC < EMT < IMC < RMC

By Wiring Method

Electrical Metallic Tubing (EMT)

Fittings

Set-screw < compression

[!info] EMT has a third coupling type "indenter", which are crimped onto the conduit using a special tool. These are usually only mentioned in specifications to say that they are unacceptable.

[!info] Edge Case: Vanderbilt Central Neighborhood Residential College

[!cite] Vanderbilt Central Neighborhood Residential College - Project Specifications (pp.) Fittings for Type EMT Duct Raceways:

  • Coupling Method: Compression coupling or Setscrew coupling. Setscrew couplings with only single screw per conduit are unacceptable.

[!quote] Joel Jansen via Microsoft Teams @ 2025-10-15 09:33 AM use set screw 🙂

Rigid Polyvinyl Chloride Conduit (PVC)

Not usually permissible exposed indoors in any construction, except in Florida.

May require rigid stub-ups in certain cases, which could make EMT more cost-effective. Consult with the Senior Construction Estimator in this case.

By Use-Case

Multi-Circuit Homeruns

[!quote] Art Baldwin (pp.) Multi-circuit MC is not cost-effective when considering the difficulty of rework. Use conduit, even EMT if necessary.

By Market Type

Assisted Living

MC-AP may be required.

Searching Specifications

[!info] Example Specs Relevant to Wiring Methods Selection

  • 26XXXX - Raceway And Boxes For Electrical Systems

  • 26XXXX - Conduits For Electrical Systems

  • 26XXXX - Underground Ducts And Raceways For Electrical Systems

  • 26XXXX - Low-Voltage Electrical Power Conductors And Cables

  • 26XXXX - General Requirements For Electrical

  • 26XXXX - Common Work Results For Electrical