Fire Alarm Takeoff
Important
Complete emergency-systems-research before beginning takeoff.
[!info] See fire-alarm for information about fire alarm systems.
Assembly Selection
Free Air < PVC in Slab < EMT
High Rise (Steel & slab): Free air in Units, use conduit elsewhere. Mid Rise, High Density (Wood frame): Free air, conduit only where required.
Backbone
Put all backbone takeoff in the Area of the Fire Command Center.
Include sleeving-takeoff as necessary.
Fire Command Center
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/HEAD END EQUIP/... HEAD END
Generator Room
Area = Same as FACR
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/GENERATOR ROOM ...
Fire Pump Room
Area = Same as FACR
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FIRE PUMP ROOM ...
FACR to Elevator Shafts
Area = Same as FACR
For each elevator shaft:
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/ELEV SHAFT ...
Count = 1
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO ELEV SHAFT ...
Length = Length measured from the most distant points of the FACR and elevator shaft.
- Input adder length to reach the level of the shaft (Minimum 15ft).
[!important] Counting Elevator Shafts Adjacent elevators may be in the same or parallel shafts. Count the shafts accordingly:
| | | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | || | Elev 1 | | Elev 2 | || | || | Elev 1 | || | Elev 2 | || | | || +--------+ +--------+ || | || +--------+ || +--------+ || | | ||=======================|| | ||============||============|| | | 1 shaft | 2 shafts |
FACR to Elevator Control Rooms
For each Elevator Control Room (ECR):
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/ELEV CONTROL ROOM ...
Count = 1
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO ELEV CONTROL RM ...
Length = Length measured from the most distant points of the FACR and ECR.
- Input adder length to reach the level of the ECR (Minimum 15ft).
FACR to Stairwells
[!info] This is for the Flow/Tamper modules in the stairwells
For each stairwell:
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/GEN, ELEV, FIRE PUMP & FA ROOM ASSEMBLIES/FACR TO STAIRWELLS 1" CONDUIT ...
Length = Length measured from the most distant points of the FACR and stairwell.
- Input adder length to reach the level of the stairwell (Minimum 15ft).
Terminal Cabinets
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/TERMINAL CABINET/ACE D ACCESSORY CABINET ENCLOSURE ...
- Garden Style, High Density: (2) 1"C
- High Rise: (2) 2"C
Horizontal:
Area = Same as FACR
Length = Length measured from FACR to all electrical rooms
Vertical:
Area = "Typical - Building All Levels"
Length = 10ft
Annunciator Panels
[!info] Also Known As
- Fire Alarm Annunciator (FAA)
- Fire Alarm Annunciator Panel (FAAP)
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/ANNUNCIATORS/REMOTE SERIAL ANNUNCIATOR ...
Length = Length measured from the FACR to FAA or Lobby
Devices
Smoke Detectors
Design Build: Count every stairwell at every level.
Pull Stations
Design Build: Count every stairwell at every level and every exterior exit.
Flow/Tamper Switches
No free-air. If wood frame, take off as EMT.
Design Build: Count every stairwell at every level.
Magnetic Door Holders
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INDICATING DEVICES WITH WIRE - .../MAGNETIC DOOR HOLDER - ...
Design Build: Count 2 for every set of double doors. (Typical of elevator lobbies and corridors)
Speaker Strobes
Design Build:
- Count every 75 ft,
- measure with circles on Bluebeam
- or divide relevant SF area by 4415
\pi(\frac{75}{2})^2 \approx 4415
- every elevator lobby,
- and every BOH room on the first floor and garage levels.
Design Build (alt):
- 15ft from end of corridor,
- then every 50ft
Firefighter Phone System
- firefighter phone jacks
- fire warden station
- fire phone cabinet
Communicates directly with FACR. Not related to responder radio.
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/COMMUNICATION DEVICES .../...
Fire Smoke Dampers (FSD's)
For each damper, take off both
System = "FA - Fire Alarm"
COMMON ASSEMBLIES/FIRE ALARM & DAS SYSTEMS/INITIATING DEVICES .../ADDRESSABLE OUTPUT RELAY MODULE ...
and System = "EL - Electrical"
COMMON ASSEMBLIES/MISC ASSEMBLIES/FSD ...