Fire Resistive Wiring Methods
type/encyclopedia-entry
electrical-construction

Fire Resistive Wiring Methods

Requirements

Permitted methods for fire protection of emergency feeders are specified in nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring..

!nfpa-70_700_emergency-systems#700.10(D)(2) Feeder-Circuit Wiring.

the requirements of which only apply to occupancies listed in nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.

!nfpa-70_700_emergency-systems#700.10(D)(1) Occupancies.

Note that even in these occupancies only nfpa-70_100_definitions#Feeder. require fire protection, not nfpa-70_100_definitions#Branch Circuit..

Construction

[!info] Keywords

  • Low Smoke Zero Halogen (LSZH)

Fire Resistive Metal-Clad (MC) Cable

nfpa-70_330_mc-cable

Mineral Insulated (MI) Cable

nfpa-70_332_mi-cable

When terminating single conductors in a ferrous metal enclosure, it is necessary to terminate MI cables in a brass plate to prevent heating due to ferroelectric hysteresis Cut out and replace a section of the enclosure with the plate

When cutting a hole in the enclosure would void its listing, or is otherwise not allowed, the cables can be terminated through a brass plate into a junction box and power brought to the enclosure through a conventional raceway.

[!info] According to Pyrotenax literature, the intermediate junction box method is obligatory for fire pump controllers.

Fire Resistive Cable-in-Conduit (CIC)

Resources

VITALink Fire-Rated Cables | OmniCable

Lifeline® Fire Rated Cable Systems | Prysmian

Chemelex Pyrotenax