Subfeeds Takeoff

Use adders appropriate for the difference in elevation. Use an additional 10ft for makeup when using cable.

Tip

Identify if and where typicals can be used

Multi-Circuit Homerun Subfeeds

Typical of hotels and dormitories.

Route from panel to center of the room.

Wiring Method Selection

wiring-method-selection#Multi-Circuit Homeruns

Voltage Drop

If voltage drop is to be considered in takeoff, Use the table provided in the drawings. If no table is provided, use the following:

Wire Size Max Length
#12 100ft
#10 200ft
#8 >200ft

Unit Load Center Subfeeds

Route from meter center to unit load center.

Voltage Drop

Larger of the listed demand current and 80% of the panel rating.

Pigtail Adaptors

distribution-equipment#Pigtail Adaptors

Use where conductors are oversized (for voltage drop or otherwise).

Load Center Size Max Feeder Size
100A 2/0 AWG
125A 3/0 AWG
150A 4/0 AWG
225A 300 kcmil
400A 500 kcmil

ITEM DATABASE/WIRE & CABLE ACCESSORIES/WIRE LUGS & SPLICING/PIGTAIL ADAPTORS.../ADAPTOR STRAIGHT PIGTAIL - ...

Meter Center Troughs

Only for PVC subfeeds where we own voltage drop.

  • Area = "Typical - Building Levels With Meter Centers"
  • System = "Electrical"
  • Phase = "Sub Feeders"

ITEM DATABASE/DISTRIBUTION/BUDGET ITEMS $ & LBR/METER CENTER WIRE TROUGH ($400/E)